Plan Review Details - Permit 04030414
Plan Review Stops For Permit 04030414
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-20 Cont ID  
Sent By jwitmer Date 2004-04-20 Time 09:01 Rev Time 0.25
Received By jwitmer Date 2004-04-20 Time 09:01 Sent To  
Notes
2004-04-20 00:00:00BUILDING REVISION# 1- OKJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-08 Cont ID  
Sent By jwitmer Date 2004-04-08 Time 16:25 Rev Time 0.75
Received By jwitmer Date 2004-04-08 Time 16:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-03 Cont ID  
Sent By jwitmer Date 2004-04-03 Time 13:16 Rev Time 0.77
Received By jwitmer Date 2004-04-03 Time 13:15 Sent To PC
Notes
2004-04-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04030414
 ADD: 201 NARCISSUS AV# 902
 CONT:PLAN REVIEW O/B KORMAN, HARVEY
 TEL: (561)804-6655
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE INFO ON THE NEW FIRE RATED
 ENTRY DOOR AND JAMB.
  
 3) THE FRONT DOOR IS CONSIDERED COMMON
 AREA NOT PART OF WHAT A O/B OR DRYWALL
 CONTRACTOR IS LICENSED UNDER, OUT OF
 SCOPE OF LICENSURE.
  
 4) PROVIDE A DETAIL FOR SOFFITS WITH
 SPACING OF STUDS, HOW VERTICAL FRAMING
 MEMBERS ARE TO BE SECURED TO THE DECK
 ABOVE AND TO THE HORIZONTAL FRAMING
 MEMBERS OF THE SOFFIT.
  
 5) THIS BUILDING IS A TYPE I OR II
 BUILDING, ALL FRAMING AND BACKING TO
 BE FIRE RETARDANT TREATED WOOD 609.2.1.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-13 Cont ID  
Sent By dpalmer Date 2004-04-13 Time 09:31 Rev Time 0.33
Received By dpalmer Date 2004-04-13 Time 09:29 Sent To  
Notes
2004-04-13 00:00:00O/B SHOULD NOT BE ISSUED UNTIL CO OF
 BLDG FROM SUFFOLK CONST. PER FS 489

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-26 Cont ID  
Sent By btrobaug Date 2004-03-26 Time 09:39 Rev Time 0.50
Received By btrobaug Date 2004-03-26 Time 09:19 Sent To  
Notes
2004-03-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE WATTAGE OF THE
 LUMINAIRES BEING ADDED (INDIVIDUALLY).
  
 2} PLEASE SHOW ADDED LOADS, RECALCULATE
 TO SHOW EXISTING AND ADDED LOAD TOTALS.
 SEE 220.3(B)(4) FOR RECESSED LUMINAIRES.
  
 3} PLEASE VERIFY WHETHER THE FIXTURES ON
 CIRCUIT #34, SHEET E-01, ARE EXISTING,
 OR BEING ADDED.
  
 4} SEE PLUMBING REVIEW COMMENT REGARDING
 ARCHITECTS SIGNATURE AND FIRM NUMBER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-08 Cont ID  
Sent By mcarsill Date 2004-04-08 Time 13:53 Rev Time 0.00
Received By mcarsill Date 2004-04-08 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By mcarsill Date 2004-03-09 Time 16:44 Rev Time 0.00
Received By mcarsill Date 2004-03-09 Time 16:44 Sent To  
Notes
2004-03-09 00:00:001) PLANS DO NOT ILLUSTRATE THE REQUIRED
 SMOKE DETECTORS LOCATED WITHIN THE
 UNITS.
  
 2) THE BUILDING HAS NOT RECEIVED A
 CERTIFICATE OF OCCUPANCY YET.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-08 Cont ID  
Sent By csiegber Date 2004-04-08 Time 11:33 Rev Time 0.00
Received By csiegber Date 2004-04-08 Time 11:32 Sent To  
Notes
2004-04-08 00:00:00TO COMM BD#

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-09 Time 09:24 Rev Time 0.00
Received By csiegber Date 2004-03-09 Time 09:24 Sent To  
Notes
2004-03-09 00:00:00TO COMM BD#23

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-04-13 Cont ID  
Sent By hmoser Date 2004-04-13 Time 08:30 Rev Time 0.25
Received By hmoser Date 2004-04-13 Time 08:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-04-09 Cont ID  
Sent By hmoser Date 2004-04-09 Time 14:57 Rev Time 0.50
Received By hmoser Date 2004-04-09 Time 14:57 Sent To  
Notes
2004-04-09 00:00:00PLAN DENIED
 1) PLANS ARE NOT SEALED BY ARCHITEC
 2) REFER TO SECTION 601.4 BALANCED
 RETURN AIR
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-09 Cont ID  
Sent By pkrauss Date 2004-04-02 Time 08:09 Rev Time 0.35
Received By hmoser Date 2004-04-02 Time 08:09 Sent To  
Notes
2004-04-02 00:00:00DENIED:
 PLEASE PROVIDE ADDITIONAL INFORMATION
 AS TO WHICH DUCTS ARE TO BE EXTENDED.
 INDICATE ANY CHANGES IN DUCT SIZE OR
 DIFFUSERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-13 Cont ID  
Sent By jleech Date 2004-04-13 Time 08:27 Rev Time 0.25
Received By jleech Date 2004-04-13 Time 08:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-03-22 Time 08:23 Rev Time 0.33
Received By kstevens Date 2004-03-22 Time 08:23 Sent To  
Notes
2004-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SANITARY AND WATER RISER DIAGRAM ARE
 REQUIRED PER SECTION 104.3.1.1
 2) SIGNATURE REQUIRED ON SEAL PER FAC
 61G1-16.003 & FS 481.2055 - INITIALS ARE
 NOT ACCEPTABLE. MINIMUM FIRS & LAST NAME
 AS SHOWN ON ARCHITECT'S LICENSE.
 3) CERTIFICATE OF AUTHORIZATION REQUIRED
 ON TITLE BLOCK PER FS 481.219
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]