Plan Review Details - Permit 04030130
Plan Review Stops For Permit 04030130
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-08-18 Cont ID  
Sent By lsmith Date 2004-08-18 Time 14:55 Rev Time 0.50
Received By lsmith Date 2004-08-18 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-08-06 Cont ID  
Sent By lsmith Date 2004-08-06 Time 07:40 Rev Time 0.25
Received By lsmith Date 2004-08-06 Time 07:40 Sent To  
Notes
2004-08-06 00:00:00SEE PLUMBING & ELECTRICAL NOTES ON
 TITLE BLOCK REQUIREMENTS.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-08 Cont ID  
Sent By kstevens Date 2004-08-05 Time 18:16 Rev Time 0.50
Received By lsmith Date 2004-04-08 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-04-07 Time 11:44 Rev Time 0.75
Received By lsmith Date 2004-03-15 Time 09:13 Sent To  
Notes
2004-03-15 00:00:00BUILDING PLAN REVIEW FAILED;
  
 METHOD OF PROTECTING HOUSE OPENINGS FROM
 POOL MUST BE SHOWN ON PLANS.
  
 SUBMIT CONTRACT TO VERIFY VALUE FOR
 PERMIT.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLAN REVIEW
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-08-17 Cont ID  
Sent By btrobaug Date 2004-08-17 Time 15:06 Rev Time 0.33
Received By btrobaug Date 2004-08-17 Time 15:06 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-08-16 Time 10:36 Rev Time 0.33
Received By btrobaug Date 2004-07-26 Time 09:15 Sent To P
Notes
2004-07-26 00:00:00 
 PLEASE NOTE THAT ATITLE BLOCK WITH
 INFORMATION REQUIRED PER 61G15-23.002
 IS MUST BE ON THE PLAN. PLEASE ADD SAME
 AND RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-05-24 Cont ID  
Sent By lsmith Date 2004-07-23 Time 12:18 Rev Time 0.33
Received By dpalmer Date 2004-05-24 Time 07:43 Sent To P
Notes
2004-05-24 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 PLEASE PROVIDE ALL INFORMATION ON TITLE
 BLOCK ASR EQUIRED.
  
 2)NOTE: PLEASE SEE FS 481.221, REQUIRES
 A FULL SIGNATURE WHICH CONTAINS A MIN
 OF FIRST AND LAST NAME AS SHOWN ON SEAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:32 Rev Time 0.25
Received By dpalmer Date 2004-04-27 Time 06:06 Sent To B
Notes
2004-04-27 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE CORRELATE CONTRACT WITH
 ELECTRICAL AND ELECTRICAL W/ PLUMB.
 CONTRACT MENTIONS GAS HEATER?
 ELECTRICAL SHOWS AN ELEC HEATER?
 PLUMB SHOWS NO HEATER?
 BLDG SHEET SAYS HEATER N/A?
  
 IF ANY TYPE OF HEATER IS GOING TO BE
 INSTALLED, PLEASE SUBMIT SPEC SHEETS,
 SHOW LISTING OF EQUIPMENT.
 IF IT WILL BE AN ELECTRICAL HEAT PUMP,
 PLEASE SUBMIT LOAD CALCULATIONS OF EXIST
 -ING AND ALL NEW LOADS BEING ADDED.
 PLEASE ALSO INDICATE SIZE OF EXISTING
 SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-10 Cont ID  
Sent By kstevens Date 2004-04-24 Time 17:29 Rev Time 0.33
Received By btrobaug Date 2004-03-10 Time 07:04 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 10:36 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 10:36 Sent To E
Notes
2004-08-16 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-23 Cont ID  
Sent By lsmith Date 2004-07-23 Time 12:17 Rev Time 0.00
Received By lsmith Date 2004-07-23 Time 12:17 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:32 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:32 Sent To E
Notes
2004-05-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:55 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 08:55 Sent To P
Notes
2004-03-23 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-09 Time 08:34 Rev Time 0.00
Received By csiegber Date 2004-03-09 Time 08:34 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-04 Cont ID  
Sent By mmclean Date 2004-03-08 Time 09:40 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 11:27 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2004-08-18 Cont ID  
Sent By kstevens Date 2004-08-18 Time 09:00 Rev Time 0.50
Received By kstevens Date 2004-08-18 Time 09:00 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2004-08-05 Cont ID  
Sent By btrobaug Date 2004-08-17 Time 15:06 Rev Time 0.50
Received By kstevens Date 2004-08-05 Time 18:16 Sent To B
Notes
2004-08-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ONLY ONE COPY OF THE SURVEY HAS BEEN
 RETURNED THIS RESUBMITTAL. TWO COMPLETE
 SETS OF PLANS SHALL BE SUBMITTED FOR RE-
 VIEW. SECTION 104.2.1
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-06-07 Cont ID  
Sent By btrobaug Date 2004-07-26 Time 09:42 Rev Time 1.50
Received By kstevens Date 2004-06-07 Time 16:27 Sent To B
Notes
2004-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) PLANS HAVE CHANGED SINCE THEY WERE
 PASSED BY PLUMBING REVIEW. NOW COMMENTS
 FROM PREVIOUS REVIEW AND NEW COMMENTS
 ARE NOW TO BE ADDRESSED.
 1) SKIMMER LINE AND VACUUM LINES ARE NOT
 LABELED CORRECTLY PLEASE CORRELATE IN-
 FORMATION ON PLANS. SECTION 104.2.1.
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 3) AS REQUIRED BY 104.3.1.1 OF THE CODE,
 TWO OR MORE COPIES OF SPECIFICATIONS, &
 DRAWINGS DRAWN TO SCALE WITH SUFFICIENT
 CLARITY AND DETAIL TO INDICATE THE NAT-
 URE AND CHARACTER OF THE WORK SHALL AC-
 COMPANY THE APPLICATION FOR A PERMIT. -
 SUBMIT 2 COMPLETE SETS OF PLANS FOR RE-
 VIEW. LOOSE SHEETS ARE NOT ACCEPTABLE.
 SURVEY SHEETS ARE NOT ATTACHED TO NEW
 SHEETS. SHEET 2 IS NOT CLEAR AND READ-
 ABLE AND SHALL BE CHANGED. SUBMIT ONE
 SET OF OLD SHEETS FOR COMPARISON.
 4) SHT 2 THE PIPING DIAGRAM SHALL REFLE-
 CT THE PIPING INSTALLATION OF THE POOL
 DELETE REFERENCES TO FLOOR CLEANING
 HEADS, SPA MAIN DRAINS, THERAPY JETS,
 AND TELESCOPING FOUNTAIN. ADD SECOND
 SKIMMER. THIS SHALL REFLECT THE INSTALL-
 ATION FOR THIS POOL.
 5) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE. 61G1-16.003
 6) SEE 61G1-16.004 FOR INFORMATION REQ-
 UIRED ON TITLE BLOCK. FS 481.2055.
 7) ALL PLANS SUBMITTED SHALL BE SIGNED &
 SEALED BY THE ARCHITECT OF RECORD. SECT-
 ION 104.2.2.
 8) SEE ATTACHED SHEET - BACKFLOW SHALL
 BE INSTALLED AND INSPECTED PRIOR TO THE
 POOL PERMIT BEING ISSUED. CITY CODE #
 2853-95.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-04-24 Cont ID  
Sent By dpalmer Date 2004-05-24 Time 07:44 Rev Time 0.50
Received By kstevens Date 2004-04-24 Time 17:28 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-07 Cont ID  
Sent By kstevens Date 2004-04-07 Time 10:19 Rev Time 1.50
Received By kstevens Date 2004-04-07 Time 10:19 Sent To B
Notes
2004-04-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 - THE FOLLOWING COMMENTS HAVE NOT BEEN
 ADDRESSED FROM THE PREVIOUS REVIEW. ALL
 COMMENT NUMBERS SHALL REMAIN THE SAME TO
 AVOID CONFUSION.
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 THIS IS NOT SHOWN TO FBC-2001 SATISFACT-
 ION.
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) - NOT SHOWN
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) - THE VACUUM LINE IS NOT TO BE
 CONSIDERED AS A SUCTION INLET FOR THE
 SECTION REFERED TO ABOVE. SEE OFFICIAL
 INTERPRETATION SUBMITTED BY B.O.A.F.
 4) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. - MINIMUM MEASUREMENT NOT
 SHOWN
 ***********NEW COMMENT*******
 1B FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2B INFORMATIONAL - TYP. SPAS FOR VINYL
 POOLS DETAIL UNCLEAR. THIS DETAIL SHALL
 BE CORRECTED IF SPA IS PART OF FUTURE
 INSTALLATIONS.
 3B) THERE IS A THIRD LINE CONNECTED TO
 THE POOL RETURN LINE THAT TERMINATES IN
 THE POOL. IS THIS A THIRD POOL RETURN?
 GENERAL SPECIFICATION INDICATE ONLY TWO
 POOL RETURN LINES PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:55 Rev Time 1.00
Received By kstevens Date 2004-03-13 Time 15:07 Sent To B
Notes
2004-03-13 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) - NO MAIN DRAINS SHOWN
 4) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 6) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7) POOL PIPING DIAGRAM SHOWS A HEATER, 2
 PUMPS, FLOOR CLEANING HEADS, SPA MAIN
 DRAINS, THERAPY JETS, FOUNTAIN ECT. -
 SUBMIT A PIPING DIAGRAM THAT REFLECTS
 THE POOL PIPING AND EQUIPMENT THAT WILL
 BE INSTALLED.
 8) THE PLANS THAT ARE SUBMITTED ARE UN-
 CLEAR AND HARD TO READ. IN SOME PLACES
 THEY ARE IMPOSSIBLE TO READ. PER SECTION
 104.2.1 AND 104.3.1.1 OF THE CODE, TWO
 OR MORE COPIES OF DRAWINGS WITH SUFFICI-
 ENT CLAITY AND DETAIL SHALL ACCOMPANY
 THE APPLICATION FOR A PERMIT.
 9) DELETE TITLE BLOCK FOR ENGINEER THAT
 IS NOT SIGNING AND SEALING PLANS. ONE
 TITLE BLOCK ONLY.
  
  
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By kstevens Date 2004-08-18 Time 09:00 Rev Time 0.00
Received By mmclean Date 2004-03-08 Time 09:40 Sent To I
Notes
***NONE***