Plan Review Details - Permit 04030129
Plan Review Stops For Permit 04030129
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-08-18 Cont ID  
Sent By lsmith Date 2004-08-18 Time 12:37 Rev Time 0.50
Received By lsmith Date 2004-08-18 Time 12:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-08-06 Cont ID  
Sent By btrobaug Date 2004-08-17 Time 15:05 Rev Time 0.25
Received By lsmith Date 2004-08-06 Time 07:45 Sent To  
Notes
2004-08-06 00:00:00SEE PLUMBING & ELECTRICAL NOTES
 REGARDING TITLE BLOCK REQUIREMENTS.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-06-07 Cont ID  
Sent By kstevens Date 2004-08-05 Time 17:58 Rev Time 0.50
Received By lsmith Date 2004-06-07 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-04-07 Time 12:14 Rev Time 0.75
Received By lsmith Date 2004-03-15 Time 09:30 Sent To  
Notes
2004-03-15 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. PLANS HAVE TITLE BLOCK SHOWING WITH
 ANOTHER ENGINEER.REMOVE TITLE BLOCK
  
 2. SHOW METHOD OF PROTECTING POOL FROM
 HOUSE OPENINGS.
  
 3. SUBMIT CONTRACT TO VERIFY VALUE FOR
 PERMIT.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-08-17 Cont ID  
Sent By btrobaug Date 2004-08-17 Time 15:04 Rev Time 0.33
Received By btrobaug Date 2004-08-17 Time 14:42 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-08-16 Time 10:36 Rev Time 0.33
Received By btrobaug Date 2004-07-26 Time 10:01 Sent To P
Notes
2004-07-26 00:00:00 
 PLEASE NOTE THAT A TITLE BLOCK WITH
 INFORMATION REQUIRED BY 61G15-23.002
 FAC, MUST ACCOMPANY THE ENGINEERS SEAL.
 PLEASE ADD SAME AND RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-05-24 Cont ID  
Sent By lsmith Date 2004-07-23 Time 12:16 Rev Time 0.25
Received By dpalmer Date 2004-05-24 Time 07:57 Sent To P
Notes
2004-05-24 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004,
 PLEASE INCLUDE ALL INFORMATION AS
  
 2)NOTE: PLEASE SEE FS 481.221, WHICH
 REQUIRES A SIGNATURE. THIS SIGNATURE
 MUST BE A MIN OF FIRST AND LAST NAME
 AS SHOWN ON SEAL/LICENSE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:33 Rev Time 0.33
Received By dpalmer Date 2004-04-27 Time 05:44 Sent To B
Notes
2004-04-27 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE CORRELATE PLUMB/ BLDG
 AND ELECTRICAL PLANS. SOME AREAS SHOW
 HEATER N/A , ELECTRICAL WIRING DIAGRAM
 SHOWS A HEATER.THE CONTRACT FROM CONT
 MENTIONS A HEATER. PLUMB RISER DOES NOT
 INDICATE A HEATER NOR DOES IT SHOW A
 SECOND PUMP AS ON ELECTRICAL??
  
 PLEASE CORRELATE ALL OF THE ABOVE.
  
 IF AN ELECTRICAL TYPE HEATER IS INSTALL-
 ED. PLEASE SUBMIT SPECS FOR HEATER
 SHOWING LISTING.
 PLEASE SUBMIT LOAD CALCULATION OF EXIST-
 ING SERVICE W/ ALL NEW LOADS ADDED.
 PLEASE ALSO INDICATE SIZE IF SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-09 Cont ID  
Sent By kstevens Date 2004-04-24 Time 17:10 Rev Time 0.25
Received By btrobaug Date 2004-03-09 Time 18:11 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-08-16 Cont ID  
Sent By csiegber Date 2004-08-16 Time 10:36 Rev Time 0.00
Received By csiegber Date 2004-08-16 Time 10:36 Sent To E
Notes
2004-08-16 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-23 Cont ID  
Sent By lsmith Date 2004-07-23 Time 12:16 Rev Time 0.00
Received By lsmith Date 2004-07-23 Time 12:16 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 14:33 Sent To E
Notes
2004-05-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:51 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 08:51 Sent To P
Notes
2004-03-23 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-03-09 Time 08:34 Rev Time 0.00
Received By csiegber Date 2004-03-09 Time 08:34 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-04 Cont ID  
Sent By mmclean Date 2004-03-08 Time 09:33 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 12:30 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2004-08-18 Cont ID  
Sent By kstevens Date 2004-08-18 Time 07:49 Rev Time 0.50
Received By kstevens Date 2004-08-18 Time 07:49 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2004-08-05 Cont ID  
Sent By btrobaug Date 2004-08-17 Time 15:05 Rev Time 0.50
Received By kstevens Date 2004-08-05 Time 17:58 Sent To B
Notes
2004-08-05 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) ONLY ONE COPY OF THE SURVEY HAS BEEN
 RETURNED WITH THIS SUBMITTAL. TWO COM-
 PLETE SETS OF PLANS ARE REQUIRED FOR RE-
 VIEW. SECTION 104.2.1
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-06-07 Cont ID  
Sent By btrobaug Date 2004-07-26 Time 10:01 Rev Time 1.50
Received By kstevens Date 2004-06-07 Time 14:43 Sent To B
Notes
2004-06-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) PLANS HAVE CHANGED SINCE THEY WERE
 PASSED BY PLUMBING REVIEW. NOW COMMENTS
 FROM PREVIOUS REVIEW AND NEW COMMENTS
 ARE NOW TO BE ADDRESSED.
 1) SKIMMER LINE AND VACUUM LINES ARE NOT
 LABELED CORRECTLY. PLEASE CORRELATE IN-
 FORMATION ON PLANS. SECTION 104.2.1
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)- NOW ONLY ONE SKIMMER SHOWN
 ON PLANS.
 3) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 4) THERE IS A THIRD LINE CONNECTED TO
 THE POOL RETURN LINE THAT TERMINATES IN
 THE POOL. IS THIS A THIRD POOL RETURN?
 GENERAL SPECIFICATION INDICATE ONLY TWO
 POOL RETURN LINES. PLEASE CLARIFY. SECT-
 ION 104.2.1
 5) AS REQUIRED BY 104.3.1.1 OF THE CODE,
 TWO OR MORE COPIES OF SPECIFICATIONS, &
 DRAWINGS DRAWN TO SCALE WITH SUFFICIENT
 CLARITY AND DETAIL TO INDICATE THE NAT-
 URE AND CHARACTER OF THE WORK SHALL AC-
 COMPANY THE APPLICATION FOR A PERMIT. -
 SUBMIT 2 COMPLETE SETS OF PLANS FOR RE-
 VIEW. LOOSE SHEETS ARE NOT ACCEPTABLE.
 SURVEY SHEETS ARE NOT ATTACHED TO NEW
 SHEETS. SHEET 2 IS NOT CLEAR AND
 READABLE AND SHALL BE CHANGED. SUBMIT
 ONE SET OF OLD PLANS FOR COMPAIRISON.
 6) SHT 2 THE PIPING DIAGRAM SHALL REF-
 LECT THE PIPING INSTALLATION OF THE POOL
 DELETE REFERENCES TO THE FLOOR CLEANING
 HEADS, SPA MAIN DRAINS, THERAPY JETS, &
 TELESCOPING FOUNTAIN. ADD SECOND SKIMMER
 7) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE. 61G1-16.003
 8) SEE 61G1-16.004 FOR INFORMATION REQ-
 UIRED ON TITLE BLOCK. FS 481.2055
 9) ALL PLANS SHALL BE SIGNED AND SEALED
 BY ARCHITECT OF RECORD.
 10) SEE ATTACHED SHEET - BACKFLOW SHALL
 BE INSTALLED AND INSPECTED PRIOR TO THE
 POOL PERMIT BEING ISSUED. CITY CODE
 2853-95.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-04-24 Cont ID  
Sent By dpalmer Date 2004-05-24 Time 07:57 Rev Time 0.50
Received By kstevens Date 2004-04-24 Time 17:10 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-07 Cont ID  
Sent By kstevens Date 2004-04-07 Time 11:37 Rev Time 1.50
Received By kstevens Date 2004-04-07 Time 11:37 Sent To B
Notes
2004-04-07 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 - THE FOLLOWING COMMENTS HAVE NOT BEEN
 ADDRESSED FROM THE PREVIOUS REVIEW. ALL
 COMMENT NUMBERS SHALL REMAIN THE SAME TO
 AVOID CONFUSION.
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 THIS IS NOT SHOWN TO FBC-2001 SATISFACT-
 ION.
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL) - NOT SHOWN
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL) - THE VACUUM LINE IS NOT TO BE
 CONSIDERED AS A SUCTION INLET FOR THE
 SECTION REFERED TO ABOVE. SEE OFFICIAL
 INTERPRETATION SUBMITTED BY B.O.A.F.
 4) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER. - MINIMUM MESUREMENT NOT
 SHOWN.
 *************NEW COMMENT***************
 1B FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 2B INFORMATIONAL - TYP. SPAS FOR VINYL
 POOLS DETAIL UNCLEAR. THIS DETAIL SHALL
 BE CORRECTED IF SPA IS PART OF FUTURE
 INSTALLATIONS.
 3B THERE IS A THIRD LINE CONNECTED TO
 THE POOL RETURN LINE THAT TERMINATES IN
 THE POOL. IS THIS A THIRD POOL RETURN?
 GENERAL SPECIFICATION INDICATE ONLY TWO
 POOL RETURN LINES. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-13 Cont ID  
Sent By csiegber Date 2004-03-23 Time 08:51 Rev Time 0.75
Received By kstevens Date 2004-03-13 Time 15:30 Sent To B
Notes
2004-03-13 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 4) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 5) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 6) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7) POOL PIPING DIAGRAM SHALL REFLECT
 THE POOL LAYOUT AND SHOW PIPING AND
 EQUIPMENT THAT WILL BE INSTALLED AND
 PIPING AND EQUIPMENT NOT TO BE INSTALLED
 SHALL BE DELETED FROM DIAGRAM.
 8) THE PLANS THAT ARE SUBMITTED ARE UN-
 CLEAR AND HARD TO READ. IN SOME PLACES
 THEY ARE IMPOSSIBLE TO READ. PER SECTION
 104.2.1 AND 104.3.1.1 OF THE CODE, TWO
 OR MORE COPIES OF DRAWINGS WITH SUFFICI-
 ENT CLARITY AND DETAIL SHALL ACCOMPANY
 THE APPLICATION FOR A PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By kstevens Date 2004-08-18 Time 07:49 Rev Time 0.00
Received By mmclean Date 2004-03-08 Time 09:33 Sent To I
Notes
***NONE***