| Plan Review Stops For Permit 04021424 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-18 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2004-05-18 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2004-05-18 00:00:00 | OK, TO ISSUE PER ART LANGE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-04-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-08 |
Time |
12:56 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2004-04-19 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2004-04-19 00:00:00 | DENIED | | | ITEMS NOT ADDRESSED FROM PRIOR REVIEW. | | | | | | 1.ROOF SHEATHING NAILING DOES NOT | | | COMPLY WITH FBC CHAPTER 23. PERIMETER | | | ZONES REQUIRE 4" SPACING ON PERIMETER | | | AND 6" IN THE FIELD.SHOW ON PLANS. | | | | | | 2.PRODUCT APPROVALS: | | | A. PRODUCT APPROVALS FOR PREMDOR ENTRY | | | SYSTEMS NOT LISTED ON THE DCA PRODUCT | | | APPROVAL SITE. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | B. GAF MATERIALS MISSING ONE SET. | | | | | | C.JEN-WELD DOORS NO NOA'S SUBMITTED. | | | SUBMIT 2 COPIES. | | | | | | D. MADDEN MFG STORM PANELS, INCOMPLETE | | | APPROVALS SUBMITTED.SUBMIT 2 COMPLETE | | | SETS OF NOA'S. | | | | | | PERMITS CAN NOT BE ISSUED UNTIL ALL | | | REQUIRED PRODUCT APPROVAL INFO HAS | | | BEEN SUBMITTED. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-03-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-17 |
Time |
16:19 |
Rev Time |
2.00 |
| Received By |
alange |
Date |
2004-03-29 |
Time |
11:23 |
Sent To |
P |
|
| Notes |
| 2004-03-29 00:00:00 | DENIED | | | 1. BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 2.ENERGY CALCS NOT SIGNED | | | | | | 3.BUILDING VALUATION TOO LOW.A | | | CALCULATED VALUATION HAS BEEN DONE PER | | | SBCCI BUILDING VALUATION DATA TABLES. | | | BUILDING VALUE HAS BEEN ADJUSTED TO | | | $108,253.00 ADDITIONAL PERMIT FEES OF | | | $487.36 ARE DUE BEFORE A PERMIT CAN BE | | | ISSUED. | | | | | | 4.INCLUDE A ROOF SHEATHING FASTENING | | | SCHEDULE SHOWING SIZE AND SPACING OF | | | FASTENERS. PER CHAPTER 23 OF THE FBC | | | | | | 5.CROSS OF DETAILS ON PLANS THAT DO | | | NOT APPLY TO THIS BUILDING. | | | | | | 6.INCLUDE A WINDOW BUCK DETAIL. BUCKS | | | SHALL EXTEND BEYOND THE INTERIOR FACE | | | OF THE WINDOW OR DOOR FRAME SUCH THAT | | | FULL SUPPORT OF THE FRAME IS PROVIDED. | | | | | | 7.PRODUCT APPROVALS FOR PREMDOR | | | ENTRY SYSTEMS NOT LISTED ON THE FBC | | | PRODUCT APPROVAL SITE. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 8.IMPLACT PROTECTION REQUIRED. | | | SUBMIT 2 COPIES OF PRODUCT APPROVALS. | | | | | | 9. SHOW CONNECTOR SCHEDULE FOR USP-NFM3 | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-18 |
Time |
10:51 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-05-18 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2004-05-18 00:00:00 | **** PLANS REDLINED **** | | | 210.52 2' OF WALL | | | 210.52C1 FOR KITCHEN COUNTERSPACE. | | | 210.12, PER 2002 NEC | | | 210.12 SHOWN FOR BATHS??? |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-05-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-08 |
Time |
12:56 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-05-08 |
Time |
12:50 |
Sent To |
B |
|
| Notes |
| 2004-05-08 00:00:00 | *** NOTE *** | | | | | | REDLINE DTHE FOLLOWING STILL MISSING | | | ON PLANS. | | | 210.52C1 | | | 210.52 | | | ARC FAULT PER 2002 NEC NOT 1999 AS | | | NOTED ON PLANS.ALL OUTLETS, NOT JUST | | | RECEPTS. | | | | | | | | | PERSON RESPONSIBLE FOR PLANS MUST COME | | | IN PRINT NAME AND SIGN ELECTRICAL | | | PLANS BEFORE ISSUE OF PERMIT.FBC 104.2.1 | | | | | | PLANS STAMPED FOR ELECTRICAL ONLY. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2004-04-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-06 |
Time |
15:02 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-04-17 |
Time |
16:09 |
Sent To |
B |
|
| Notes |
| 2004-04-17 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 2) NOTE: PLEASE SHOW OUTLET SPACING PER | | | 210.52. 2',6`,12` RULE. | | | MASTER BEDRM. | | | | | | 3)) NOTE: PLEASE SEE MISSING RECEPTS FOR | | | FRONT AND/OR REAR OF DWELLING. | | | 210.52EREAR) | | | | | | 4)NOTE: PLEASE SEE MISSING RECEPT ALONG | | | KITCHEN COUNTERSPACE PER 210.52C1 | | | | | | 5)NOTE: PLEASE LIST REQ'D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE | | | PER 210.12 2002 NEC. | | | | | | 6)NOTE: PLEASE SEE SD NEXT TO BATH, | | | PLEASE SEE NFPA-72 8-1.4.2 MUST BE A | | | MIN OF 3' FROM BATH. | | | | | | 7)NOTE: PLEASE SEE GARAGE DR OPENER IS | | | SHOWN AS 220V?? PLEASE VERIFY. | | | | | | 8)NOTE: PLEASE SEE RISER, SHOWS PANEL | | | BACK TO BACK W/ METER. | | | PLEASE SEE 230.70 LOCAL AMENDMENTS, | | | IF MORE THAN 8' OF UNPROTECTED CONDUCTOR | | | -S INSIDE BDLG W/OUT OCP, A MAIN IS | | | REQ'D ON OUTSIDE OF BLDG W/ OCP. | | | PANEL IS SHOWN ON PLANS ON THE OTHER | | | SIDE OF GARAGE.?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2004-03-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-16 |
Time |
09:25 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-03-17 |
Time |
07:22 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-05-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-06 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-06 |
Time |
15:02 |
Sent To |
E |
|
| Notes |
| 2004-05-06 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-04-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-07 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-07 |
Time |
11:52 |
Sent To |
P |
|
| Notes |
| 2004-04-07 00:00:00 | TO KS BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-03-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-04-07 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-27 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2004-03-09 00:00:00 | SOIL TESTS/ATTACH TO PKG | | 2004-03-03 00:00:00 | TO Z | | | TO SFD RACK/E |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-03-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-03-17 |
Time |
09:21 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2004-03-22 |
Time |
07:37 |
Sent To |
P |
|
| Notes |
| 2004-03-22 00:00:00 | PROVISO: | | | A MINIMUM OF 9" RETURN REQUIRED FROM | | | BEDROOM #1 & 2. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-04-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-16 |
Time |
09:24 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-04-16 |
Time |
09:24 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-03-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-07 |
Time |
11:52 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-03-29 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2004-03-29 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS NOR DOES IT REFLECT | | | THE FLOOR PLAN. | | | A) LAV IN BATHROOM NOT VENTED AND IS AN | | | "S" TRAP. SECTIONS 901.2.1 & 1002.3 | | | B) HORIZONTAL DRY VENT NOT APPROVED. | | | SECTION 905.3 | | | C) TUB TO BE UPSTREAM OF W/C AND ALL | | | FIXTURES ON SAME WALL IN 2ND BATH. | | | SECTION 104.2.1 | | | D) W/C AND SHOWER ON WRONG WALL. | | | E) SEE ATTACHED SHEET FOR RISER DIAGRAM | | | THAT MEETS CODE AND REFLECTS THE FLOOR | | | PLAN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-03-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-27 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-03-02 |
Time |
11:22 |
Sent To |
I |
|
| Notes |
|
|