Plan Review Details - Permit 04021424
Plan Review Stops For Permit 04021424
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-18 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2004-05-18 Time 11:01 Sent To  
Notes
2004-05-18 00:00:00OK, TO ISSUE PER ART LANGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-19 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 12:56 Rev Time 1.00
Received By alange Date 2004-04-19 Time 12:54 Sent To  
Notes
2004-04-19 00:00:00DENIED
 ITEMS NOT ADDRESSED FROM PRIOR REVIEW.
  
 1.ROOF SHEATHING NAILING DOES NOT
 COMPLY WITH FBC CHAPTER 23. PERIMETER
 ZONES REQUIRE 4" SPACING ON PERIMETER
 AND 6" IN THE FIELD.SHOW ON PLANS.
  
 2.PRODUCT APPROVALS:
 A. PRODUCT APPROVALS FOR PREMDOR ENTRY
 SYSTEMS NOT LISTED ON THE DCA PRODUCT
 APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 B. GAF MATERIALS MISSING ONE SET.
  
 C.JEN-WELD DOORS NO NOA'S SUBMITTED.
 SUBMIT 2 COPIES.
  
 D. MADDEN MFG STORM PANELS, INCOMPLETE
 APPROVALS SUBMITTED.SUBMIT 2 COMPLETE
 SETS OF NOA'S.
  
 PERMITS CAN NOT BE ISSUED UNTIL ALL
 REQUIRED PRODUCT APPROVAL INFO HAS
 BEEN SUBMITTED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By dpalmer Date 2004-04-17 Time 16:19 Rev Time 2.00
Received By alange Date 2004-03-29 Time 11:23 Sent To P
Notes
2004-03-29 00:00:00DENIED
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.ENERGY CALCS NOT SIGNED
  
 3.BUILDING VALUATION TOO LOW.A
 CALCULATED VALUATION HAS BEEN DONE PER
 SBCCI BUILDING VALUATION DATA TABLES.
 BUILDING VALUE HAS BEEN ADJUSTED TO
 $108,253.00 ADDITIONAL PERMIT FEES OF
 $487.36 ARE DUE BEFORE A PERMIT CAN BE
 ISSUED.
  
 4.INCLUDE A ROOF SHEATHING FASTENING
 SCHEDULE SHOWING SIZE AND SPACING OF
 FASTENERS. PER CHAPTER 23 OF THE FBC
  
 5.CROSS OF DETAILS ON PLANS THAT DO
 NOT APPLY TO THIS BUILDING.
  
 6.INCLUDE A WINDOW BUCK DETAIL. BUCKS
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED.
  
 7.PRODUCT APPROVALS FOR PREMDOR
 ENTRY SYSTEMS NOT LISTED ON THE FBC
 PRODUCT APPROVAL SITE.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.IMPLACT PROTECTION REQUIRED.
 SUBMIT 2 COPIES OF PRODUCT APPROVALS.
  
 9. SHOW CONNECTOR SCHEDULE FOR USP-NFM3
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-05-18 Cont ID  
Sent By dpalmer Date 2004-05-18 Time 10:51 Rev Time 0.50
Received By dpalmer Date 2004-05-18 Time 10:51 Sent To  
Notes
2004-05-18 00:00:00**** PLANS REDLINED ****
 210.52 2' OF WALL
 210.52C1 FOR KITCHEN COUNTERSPACE.
 210.12, PER 2002 NEC
 210.12 SHOWN FOR BATHS???

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-08 Cont ID  
Sent By dpalmer Date 2004-05-08 Time 12:56 Rev Time 0.33
Received By dpalmer Date 2004-05-08 Time 12:50 Sent To B
Notes
2004-05-08 00:00:00*** NOTE ***
  
 REDLINE DTHE FOLLOWING STILL MISSING
 ON PLANS.
 210.52C1
 210.52
 ARC FAULT PER 2002 NEC NOT 1999 AS
 NOTED ON PLANS.ALL OUTLETS, NOT JUST
 RECEPTS.
  
  
 PERSON RESPONSIBLE FOR PLANS MUST COME
 IN PRINT NAME AND SIGN ELECTRICAL
 PLANS BEFORE ISSUE OF PERMIT.FBC 104.2.1
  
 PLANS STAMPED FOR ELECTRICAL ONLY.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-17 Cont ID  
Sent By csiegber Date 2004-05-06 Time 15:02 Rev Time 0.50
Received By dpalmer Date 2004-04-17 Time 16:09 Sent To B
Notes
2004-04-17 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 MASTER BEDRM.
  
 3)) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52EREAR)
  
 4)NOTE: PLEASE SEE MISSING RECEPT ALONG
 KITCHEN COUNTERSPACE PER 210.52C1
  
 5)NOTE: PLEASE LIST REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210.12 2002 NEC.
  
 6)NOTE: PLEASE SEE SD NEXT TO BATH,
 PLEASE SEE NFPA-72 8-1.4.2 MUST BE A
 MIN OF 3' FROM BATH.
  
 7)NOTE: PLEASE SEE GARAGE DR OPENER IS
 SHOWN AS 220V?? PLEASE VERIFY.
  
 8)NOTE: PLEASE SEE RISER, SHOWS PANEL
 BACK TO BACK W/ METER.
 PLEASE SEE 230.70 LOCAL AMENDMENTS,
 IF MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S INSIDE BDLG W/OUT OCP, A MAIN IS
 REQ'D ON OUTSIDE OF BLDG W/ OCP.
 PANEL IS SHOWN ON PLANS ON THE OTHER
 SIDE OF GARAGE.??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-17 Cont ID  
Sent By kstevens Date 2004-04-16 Time 09:25 Rev Time 0.50
Received By btrobaug Date 2004-03-17 Time 07:22 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-06 Cont ID  
Sent By csiegber Date 2004-05-06 Time 15:02 Rev Time 0.00
Received By csiegber Date 2004-05-06 Time 15:02 Sent To E
Notes
2004-05-06 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:52 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 11:52 Sent To P
Notes
2004-04-07 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-29 Cont ID  
Sent By mmclean Date 2004-04-07 Time 11:52 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 09:40 Sent To  
Notes
2004-03-09 00:00:00SOIL TESTS/ATTACH TO PKG
2004-03-03 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-22 Cont ID  
Sent By btrobaug Date 2004-03-17 Time 09:21 Rev Time 0.25
Received By pkrauss Date 2004-03-22 Time 07:37 Sent To P
Notes
2004-03-22 00:00:00PROVISO:
 A MINIMUM OF 9" RETURN REQUIRED FROM
 BEDROOM #1 & 2.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-16 Cont ID  
Sent By kstevens Date 2004-04-16 Time 09:24 Rev Time 0.50
Received By kstevens Date 2004-04-16 Time 09:24 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:52 Rev Time 0.50
Received By kstevens Date 2004-03-29 Time 17:47 Sent To  
Notes
2004-03-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS NOR DOES IT REFLECT
 THE FLOOR PLAN.
 A) LAV IN BATHROOM NOT VENTED AND IS AN
 "S" TRAP. SECTIONS 901.2.1 & 1002.3
 B) HORIZONTAL DRY VENT NOT APPROVED.
 SECTION 905.3
 C) TUB TO BE UPSTREAM OF W/C AND ALL
 FIXTURES ON SAME WALL IN 2ND BATH.
 SECTION 104.2.1
 D) W/C AND SHOWER ON WRONG WALL.
 E) SEE ATTACHED SHEET FOR RISER DIAGRAM
 THAT MEETS CODE AND REFLECTS THE FLOOR
 PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:40 Rev Time 0.00
Received By mmclean Date 2004-03-02 Time 11:22 Sent To I
Notes
***NONE***