Plan Review Details - Permit 04021406
Plan Review Stops For Permit 04021406
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-28 Cont ID  
Sent By jwitmer Date 2004-04-28 Time 15:01 Rev Time 2.22
Received By jwitmer Date 2004-04-28 Time 14:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-03 Cont ID  
Sent By nmccray Date 2004-04-27 Time 10:56 Rev Time 1.00
Received By jwitmer Date 2004-04-03 Time 08:21 Sent To PC
Notes
2004-04-03 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021406
 ADD: 2201 45TH ST
 CONT: BOVIS LEND LEASE
 TEL: (561)704-1928
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET A1.20 INDICATES THE DEMOLISHION
 OFA EXISTING FENCE AND AWNING ABOVE.
 THE VARIOUS SECTIONS OF THE NEW FOOTER
 SLAB AND 10'-0" X 1'-0" CMU WALL WITH
 2" OF EFIS. THERE IS NO INFORMATION
 ON THE SIZE OF FOOTER SIZE AND NUMBER
 OF REBAR NOR THE UPRIGHTS.
 THE PLANS ALSO DO NOT INDICATE THE
 DEPTH OF THE FOOTER NOR IS THERE INFOR-
 MATION THAT WIND AND MOMENT OF OVER
 TURNING WAS CONSIDERED, OR IF THE FRAME
 WORK FOR THE AWNING WILL TRANSFER THESE
 LOADS?
 THE THIRD ITEM MISSING IS TYPE OF
 CONCRETE AND STRENGHT FOR VARIOUS POURS.
 THE SLAB DOESN'T INDICATE IF WIRE-
 MESH OR FIBERMESH IS TO BE USED?
 SINCE THIS A EXTERIOR AREA AND PARTS
 OF THE FLOOR SLAB INDICATE A CHAIN LINK
 OPEN AIR ROOF AREA HOW WILL RAIN WATER
 BE REMOVED FROM SLAB.
 INDICATE THE TRANSITION FROM THE INTER
 IOR OF THE BUILDING TO DECK?
 INDICATE IF THIS IS A EGRESS DOOR FROM
 THE INTERIOR AND IF SO WILL THE GATE BE
 LOCKED.
 THE AWNING IF CANVAS TO BE UNDER A SEP
 ERATE PERMIT AND WILL HAVE TO BE FIRE
 RESISTANT MATERIALS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-03-08 Time 07:19 Rev Time 0.33
Received By dpalmer Date 2004-03-08 Time 06:55 Sent To  
Notes
2004-03-08 00:00:00PLANS REDLINED TO INDICATE 2002 NEC

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-27 Cont ID  
Sent By nmccray Date 2004-04-27 Time 10:56 Rev Time 0.00
Received By nmccray Date 2004-04-27 Time 10:56 Sent To B
Notes
2004-04-27 00:00:00RESUB LETTER CONFIRMING COMPLIANCE TO
 NOTES.N.A. MCCRAY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-02 Cont ID  
Sent By alange Date 2004-04-22 Time 13:01 Rev Time 0.00
Received By mcarsill Date 2004-03-02 Time 13:12 Sent To  
Notes
2004-03-02 00:00:001) ARE THE DOORS LOCATED IN THE
 TEMPORARY PARTITION IN COMMON AREA
 1-107 SWINGING IN THE RIGHT DIRECTION.
 IF THE OCCUPANT LOAD IS 50 OR MORE
 PERSONS, THEN THESE DOORS SHOULD
 SWING IN THE DIRECTION OF EXIT
 TRAVEL. (PAGE AO.11)
  
 2) IS THE CANVAS COVER PLANNED FOR
 THE TEMPORARY SMOKING AREA FIRE
 RETARDANT. (PAGE AO.11)
  
 3) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR NEW CEILING TILES
 PLANNED ON PAGES A1.01-A1.04.
  
 4) PROVIDE SEPARATE PLANS AND PERMITS
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 13:01 Rev Time 0.00
Received By alange Date 2004-04-22 Time 13:01 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-03-01 Time 11:56 Rev Time 0.00
Received By jwitmer Date 2004-03-01 Time 11:55 Sent To PC
Notes
2004-03-01 00:00:00TO COMM BD#60

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-03-02 Cont ID  
Sent By pkrauss Date 2004-03-02 Time 15:41 Rev Time 0.20
Received By pkrauss Date 2004-03-02 Time 15:41 Sent To  
Notes
2004-03-02 00:00:00NO MECHANICAL PLANS OR WORK INDICATED ON
 PLAN.PLEASE PROVIDE PLANS AND SCOPE OF
 WORK WITH MECHANICAL PERMIT APPLICAITON.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-12 Cont ID  
Sent By kstevens Date 2004-03-12 Time 16:37 Rev Time 0.50
Received By kstevens Date 2004-03-12 Time 16:37 Sent To  
Notes
2004-03-12 00:00:00PASSED/PROVISO - SINK ON SHTS A8.01 AND
 A8.11 SHALL COMPLY WITH 11-4.24 AND ALL
 SUBSECTIONS.