Plan Review Details - Permit 04021378
Plan Review Stops For Permit 04021378
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-10-07 Cont ID  
Sent By rmcdouga Date 2005-10-07 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2005-10-07 Time 07:38 Sent To  
Notes
2005-10-07 00:00:00REVISED SHEET A-13.1 IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-24 Cont ID  
Sent By rmcdouga Date 2005-05-24 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2005-05-24 Time 14:18 Sent To  
Notes
2005-05-24 00:00:00REVISED ROOF SHINGLES TO CERTAINTEED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-04-27 Cont ID  
Sent By rmcdouga Date 2005-04-27 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2005-04-27 Time 16:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By jwitmer Date 2004-03-23 Time 15:15 Rev Time 3.50
Received By jwitmer Date 2004-03-23 Time 15:15 Sent To  
Notes
2004-03-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021378 (5 UNIT)
 ADD: 1710 MISSION COURT
 CONT: WCI
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW/
 DID NOT COME IN UNDER PLAN CHECK!!!
 ACTION: DENIED
 NOTE:
 AS NOTED PREVIOUSLY, A SIGNED AND
 SEALED LETTER FROM THE ARCHITECT OF
 RECORD INDICATING THE PLANS SUBMITED ARE
 A OCCUPANCY TYPE: (R2). WITH THE PLANS
 AND SOILS REPORTS STATING TOWNHOUSE,
 TOWNHOMES OR ROWHOUSES, IT IS TO BE MADE
 CLEAR THAT ALL DOCUMENTS SUBMITED ARE IN
 EFFECT TO BE BUILT AS A (R2) FOR USE AS
 CONDOMINIUM.
  
 1) 105.3 CITY ADMINISTRATIVE CODE,
 RESIDENT INSPECTOR, TO BE REQUIRED.
 CONTACT HAROLD PISKURA @ 805-6711.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A SITE PLAN SHALL BE REQUIRED INDICATING
 ALL SITE AMENITIES WITH DIMENSIONS
 BETWEEN BUILDINGS INDICATING ASSUMED
 PROPERTY LINES. TO CALCULATE ALLOWABLE
 OPENINGS SEE TABLE 600. PLANS CAN ONT
 BE CHECKED FOR ALLOWABLE OPENING SIZES
 UNTIL A SITE PLAN WITH DIMENSIONS AND
 ASSUMED PROPERTY LINES BETWEEN BUILDINGS
 ARE PROVIDED.
  
 3) SOILS REPORT NOT ORIGINAL SIGNATURE!
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) PROVIDE NOC RECORDED WITH THE CLERK
 0F COURT BEFORE A PERMIT CAN BE ISSUED.
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) PROVIDE A SITE PLAN FOR FAIR HOUSING,
 PROVIDE AN ACCESSIBLE ROUTE TO ALL COM-
 MON ELEMENTS, INCLUDING CLUBHOUSE, GAZE-
 BOES, DUMPSTERS, POOLS, PARKING, AND A
 PATH OF TRAVEL TO THE PUBLIC WAY.
  
 8) PLANS ARE INCORRECT IN THE HEIGHT
 OF THE BUILDING, SEE CHAPTER 2 DEFINI-
 TIONS FOR GRADE AND HEIGHT, BUILDING,
 CORRECT A-7 & A-8.SHEET A-8 CORRECT
 MEAN ROF HEIGHT STILL LOW.
  
 9) SEE S-5:
 A) CORRECT: DOOR & WINDOW PRESSURE
 SCHEDULE, WALL AREAS, INTERIOR ZONES
 SHOULD BE REPRESENTED BY ZONE(4), NOT
 ZONE (1) AND END ZONES SHOULD BE REPRE-
 SENTED BY ZONE (5) NOT ZONE (2).
 B) ROOF NAILING ZONES, ZONE (3) NOTE
 DIFFICULT TO UNDERSTAND, IT CAN BE PRE-
 CEVED THAT ZONE (3) MAY BE NAILED THE
 SAME AS ZONE 2 OR NAILED AS NOTE FOR
 ZONE (3).
 C) ROOF NAILING CHART IS ONLY GOOD TO
 35' ABOVE GRADE. THE TRUE HEIGHT OF THE
 BUILDING WILL BE > THAN 35', THE ENGIN-
 EER OF RECORD SHALL PROVIDE THE ADDITION
 AL INFORMATION FOR REQUIRED FOR THE
 NAILING REQUIREMENTS FOR THE EFFECTED
 ROOF NAILING ZONES.
  
 10) AMARR GARAGE DOORS DO NOT MEET THE
 NEGATIVE PRESSURES FOR A BUILDING > THAN
 35' TALL WITH A ADJUSTMENT COEFFICIENT
 OF 1.09.SEE 1606.2D/1606.2E.
  
 11) SHEET A-12 DETAIL# 2 IS MISSING THE
 FIRE STOP BETWEEN VERTICAL & HORIZONTAL
 AREAS 2ND TO 3RD FLOOR WALL SHEATHING
 MISSING AT THIRD FLOOR STUD WALL.
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2ND REQUEST !!!!!FOR THE PRODUCT TESTING
 REPORTS FOR THE STRUCTURAL COMPONENTS-
 TRUSS ANCHORS, CONCRETE TO WOOD, AND
 WOOD TO WOOD.
  
 13) 2ND REQUEST !!! PROVIDE TRUSS ENGIN-
 EERING SHEETS WITH ALL LOADING CASES, VE
 RTICAL, HORIZONTAL & GRAVITY LOADS.
 PLANS DO NOT INDICATE THE LOADING, ONLY
 THE ALLOWABLE VALUE FOR ANCHORS.
  
 14) SHEET M-1, M-2:
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
  
 15)GARAGE TO LIVING QUARTERS, GARAGE
 DOOR IS NOT LISTED ON THE GARAGE
 SCHEDULE. A 3/4 HR RATING IS REQUIRED 41
 1.2.6., 705.1.3.5, DOOR SHALL BE EQUIPED
 WITH AN APPROVED CLOSER.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-04-27 Cont ID  
Sent By rmcdouga Date 2005-04-27 Time 16:19 Rev Time 0.00
Received By rmcdouga Date 2005-04-27 Time 16:19 Sent To  
Notes
2005-04-27 00:00:00PASSED UNDER MASTER

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-16 Cont ID  
Sent By btrobaug Date 2004-07-16 Time 14:56 Rev Time 1.00
Received By btrobaug Date 2004-07-16 Time 07:26 Sent To  
Notes
2004-07-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE DRAWING SHOWS 8 METERS AND A MAIN
 DISCONNECT, THE RISER SHOWS 5 AND NO
 MAIN. PLEASE CORRELATE.
  
 2} THERE IS NO DISCONNECT SHOWN FOR THE
 CONDENSER FOR UNIT 1424.
  
 3} THE LOW VOLTAGE SYMBOLS IN THE LEGEND
 DO NOT MATCH THE SYMBOLS ON THE
 DRAWING.
  
 4} A CERTIFICATE OF AUTHORIZATION NUMBER
 IS REQUIRED IN THE ENGINEERS TITLE
 BLOCK PER 61G15-23.002.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 15:12 Rev Time 1.00
Received By btrobaug Date 2004-04-05 Time 14:12 Sent To  
Notes
2004-04-05 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE SIZE OF THE EQUIPMENT
 GROUNDING CONDUCTOR WITH THE FEEDERS ON
 THE RISER DIAGRAM.
  
 2} THE RISER SHOWS A MAIN DISCONNECT
 ANDTHE DRAWING SHOWS METERS
 & DISCONNECT, PLEASE CORRELATE.
  
 3}THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.116(B).(1500 VA).
  
 4} PLEASE LABLE THE ROOMS ON THE ELECTR-
 ICAL PLANS TO CORRESPOND TO THE ARCHITEC
 TURAL PLANS.
  
 5} PLEASE PROVIDE PLANS FOR ALL UNITS,
 INCLUDING REVERSE UNITS.
  
 6} THE PANEL SCHEDULE REFERS TO "LIVING/
 BREAKFAST" ROOM.THE "BREAKFAST" ROOM
 MUST COMPLY WITH 210.52(B),20 AMP CIRC.
  
 7} THE "NOOK" AND DINING ROOM MUST COMPL
 Y WITH 210.52(B).
  
 8} THE DINING ROOM IN "2203" NEEDS TWO R
 ECEPTACLES ADDED TO COMPLY WITH 210.52.A
  
 9} SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE
 STAMPS ARE NOT ACCEPTABLE PER F.B.P.E.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-12 Cont ID  
Sent By mamini Date 2004-04-12 Time 14:38 Rev Time 1.00
Received By mamini Date 2004-04-12 Time 14:37 Sent To  
Notes
2004-04-12 00:00:00PASSED :
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-08 Cont ID  
Sent By mamini Date 2004-03-08 Time 16:23 Rev Time 0.50
Received By mamini Date 2004-03-08 Time 16:22 Sent To  
Notes
2004-03-08 00:00:00FAILED :
 1. PLEASE SUBMIT CIVIL PLANS FOR
 PERMITTING, NOTE THAT CIVIL PLANS WERE
 REVIEWED UNDER # 03101412 (PLAN REVIEW),
 AT YOUR OPTION UNDERGROUND UTILITIES &
 SITE WORK COULD BE UNDER SEPARATE PERMIT
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-04-27 Cont ID  
Sent By rmcdouga Date 2005-04-27 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2005-04-27 Time 16:18 Sent To  
Notes
2005-04-27 00:00:00PASSED UNDER MASTER 04071169

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-06-16 Cont ID  
Sent By mcarsill Date 2004-06-16 Time 15:15 Rev Time 0.00
Received By mcarsill Date 2004-06-16 Time 15:15 Sent To  
Notes
2004-06-16 00:00:001) THE FIRE SPRINKLER DRAWINGS INDICATES
 THIS BUILDING CONTAINS EIGHT-UNITS
 BUT ACTUALLY CONTAINS FIVE. ALSO THE
 TYPE OF CONSTRUCTION MAY NOT BE CORRECT.
  
 2) YOUR COMMENT RESPONSE IS INCORRECT
 REGARDING INTERIOR FINISH. YOU MUST
 ANNOTE THE PLANS AS CLASS A, B, OR C
 NOT JUST PAINTED. THAT EXPLAINS NOTHING.
  
 3) YOUR COMMENT RESPONSE IS INCORRECT
 REGARDING THE MONITORING OF THE FIRE
 SPRINKLER SYSTEM. PLEASE ANNOTE THE
 PLANS THAT THE FIRE SPRINKLER SYSTEM
 WILL BE MONITORED BY A LICENSED UL
 COMPANY LISTED FOR CENTRAL STATION
 SERVICE.
  
 4) WHAT FIRE HYDRANTS WILL BE AVAILABLE
 FOR USE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-07 Cont ID  
Sent By mcarsill Date 2004-04-07 Time 13:36 Rev Time 0.00
Received By mcarsill Date 2004-04-07 Time 13:36 Sent To  
Notes
2004-04-07 00:00:00PLAN REVIEW PERFORMED ON 3/4/04
  
 1) ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS PLEASE ANNOTE PLANS.
  
 2) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 3) THE REQUIRED FIRE SPRINKLER SYSTEM
 SHALL BE MONITORED BY BY A UL LISTED
 CENTRAL STATION APPROVED FOR CENTRAL
 STATION SERVICE.
  
 4) BUILDING ADDRESSES NOT SHOWN ON
 ELEVATION DRAWINGS. IF THE FRONT DOORS
 DO NOT FRONT A STREET, ADDRESSES WILL
 BE REQUIRED ON BOTH SIDES FOR FIRE,
 PARAMEDICAL AND POLICE.
  
 5) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 6) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 7) PLEASE EXPLAIN EXITING RATIONALE FROM
 INSIDE THE UNITS.
  
 8) EMERGENCY INSTRUCTIONS FOR THE
 RESIDENTS SHALL BE PROVIDED.
  
 9) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 10) SUITABLE ROADS ARE REQUIRED DURING
 CONSTRUCTION.
  
 11) PLEASE INDICATE IF GARAGE DOOR
 IS RATED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-10-05 Cont ID  
Sent By pkrauss Date 2005-10-05 Time 10:20 Rev Time 0.00
Received By pkrauss Date 2005-10-05 Time 10:20 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 17:32 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 17:32 Sent To P
Notes
2005-09-26 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 19:33 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 19:33 Sent To B
Notes
2005-09-21 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 17:17 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 17:17 Sent To M
Notes
2005-09-15 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 16:14 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 16:14 Sent To B
Notes
2005-05-18 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-04-18 Cont ID  
Sent By adarroug Date 2005-04-18 Time 10:12 Rev Time 0.00
Received By adarroug Date 2005-04-18 Time 10:12 Sent To B
Notes
2005-04-18 00:00:00TO "RMCDOUGAL" DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 09:55 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 09:55 Sent To  
Notes
2004-06-15 00:00:00TO COMM BD #28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-05-07 Time 08:21 Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 10:37 Sent To  
Notes
2004-03-03 00:00:00TO COMM BD#48/ROLLS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2005-10-05 Cont ID  
Sent By pkrauss Date 2005-10-05 Time 10:21 Rev Time 0.30
Received By pkrauss Date 2005-10-05 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-09-28 Cont ID  
Sent By rregueir Date 2005-09-28 Time 19:14 Rev Time 0.00
Received By rregueir Date 2005-09-28 Time 18:54 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-02 Cont ID  
Sent By pkrauss Date 2004-07-02 Time 09:56 Rev Time 0.30
Received By pkrauss Date 2004-07-02 Time 09:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 16:50 Rev Time 0.15
Received By pkrauss Date 2004-05-14 Time 16:50 Sent To  
Notes
2004-05-14 00:00:00PER MTG 5-14-04 COMMENTS ADDRESSED
 PLANS OKAY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-26 Cont ID  
Sent By pkrauss Date 2004-03-26 Time 08:30 Rev Time 0.40
Received By pkrauss Date 2004-03-26 Time 08:28 Sent To  
Notes
2004-03-26 00:00:00DENIED:
 1.PLEASE NOTE, DETAIL OF UL DESIGN
 L528, IN THE UL DIRECTORY DOES NOT
 INDICATE ANY PENETRATIONS THROUGH THIS
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR THE PENETRATIONS THROUGH THE RATED
 ASSEMBLY.
  
 2.PLEASE CLARIFY RATING ON PLAN SHEET
 A-10 DETAIL #4, THE 1HR RATING IS AT THE
 CEILING CORRECT?IF THIS CORRECT,
 THE FIRE DAMPER INDICATED ON PLAN SHEET
 M-1 IS NOT REQUIRED BECAUSE THE WALL OR
 RATING DOES NOT CONTINUE ABOVE THE
 CEILING.
  
 3.CLARIFY O.A. DUCT, IT APPEARS TO BE
 ABOVE THE CEILING AND DOES NOT PENETRATE
 AT THE POINT OF ENTRY, FIRE DAMPER IS
 NOT REQUIRED.
  
 4.PER 2001 FBC 705.2.2 EXCEPTION #1,
 A SHAFT ENCLOSURE IS NOT REQUIRED FOR
 OPENINGS TOTALLY WITHIN A DWELLING UNIT
 & CONNECTING FOUR STORIES OR LESS.
  
 5.PLANS SHALL BE SIGNED BY THE
 ENGINEER AND NOT STAMPED WITH THEIR
 SIGNATURE AND NOT STAMPED WITH THEIR
 SIGNATURE PER FS 471.025.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-10-07 Cont ID  
Sent By jleech Date 2005-10-07 Time 13:25 Rev Time 0.50
Received By jleech Date 2005-10-07 Time 13:24 Sent To  
Notes
2005-10-07 00:00:00REVISED PLUMBING PAGES P-1 & P-2 OK PAGE
 P-3 DENIED NOT CLOUDED.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-15 Cont ID  
Sent By jleech Date 2005-06-15 Time 17:20 Rev Time 0.33
Received By jleech Date 2005-06-15 Time 17:20 Sent To  
Notes
2005-06-15 00:00:00ADDED WATER METERS TO EACH UNIT

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-04-27 Cont ID  
Sent By rmcdouga Date 2005-04-27 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2005-04-27 Time 16:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-19 Cont ID  
Sent By kstevens Date 2004-07-19 Time 18:34 Rev Time 0.50
Received By kstevens Date 2004-07-19 Time 18:33 Sent To  
Notes
2004-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT P-1 WATER RISER DIAGRAM UNCLEAR
 AND HARD TO READ. SOME INFORMATION IS
 NOT READABLE. SECTION 104.2.1
 2) SHT P-1 WHITE OUT IS USED ON SOME
 PLUMBING NOTES. THIS IS NOT APPROVED.
 NOTES SHALL BE DELETED. SEC 1104.2.1.3
 3) SHT P-2 WATER RISER DIAGRAM IS UN-
 CLEAR AND HARD TO READ, RISER DOES NOT
 REFLECT THE FLOOR PLAN. FIRST AND SECOND
 FLOOR BATHROOM ARE NOT SHOWN ON RISER
 DIAGRAM. SECTION 104.2.1
 4) CERTIFICATE OF AUTHORIZATION IS NOT
 IN TITLE BLOCK AS REQUIRED. SEE BELOW..
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-03-15 Time 10:00 Rev Time 0.50
Received By kstevens Date 2004-03-15 Time 09:59 Sent To  
Notes
2004-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A WATER RISER DIAGRAM IS REQUIRED FOR
 ALL UNIT TYPES. SECTION 104.3.1.1
 2) SHTS P-1 & P-2 SIGNATURE REQUIRED ON
 SEAL, SIGNATURE STAMP NOT ACCEPTABLE.
 CERTIFICATE OF AUTHORIZATION REQUIRED.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) - FS 471.
 025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2005-04-14 Cont ID  
Sent By eschneid Date 2005-04-14 Time 13:30 Rev Time 0.20
Received By eschneid Date 2005-04-14 Time 13:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By sgraham Date 2004-03-22 Time 09:13 Rev Time 0.00
Received By sgraham Date 2004-03-22 Time 09:18 Sent To  
Notes
2004-03-22 00:00:001. NO SITE & LANDSCAPE PLANS INCLUDED.
 2. MUST SHOW BUILDING HEIGHT MEETS CODE
 REQUIREMENTS ON ELEVATION SHEETS
 A-9,A-10,A-11,A-12
 3. FALSE CHIMNEY EXCEEDS HEIGHT
 EXCEPTION.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved