Plan Review Details - Permit 04021372
Plan Review Stops For Permit 04021372
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-05-05 Cont ID  
Sent By rmcdouga Date 2005-05-05 Time 12:47 Rev Time 0.00
Received By rmcdouga Date 2005-05-05 Time 12:47 Sent To  
Notes
2005-05-05 00:00:00REVISED ROOF SHINGLES TO CERTAINTEED

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By rmcdouga Date 2005-02-23 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2005-02-23 Time 17:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-07-23 Cont ID  
Sent By rmcdouga Date 2004-07-23 Time 08:22 Rev Time 4.00
Received By rmcdouga Date 2004-07-23 Time 08:22 Sent To  
Notes
2004-07-23 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) NO REDLINE CHANGES INITIALED & DATED
 BY THE DESIGNER OF RECORD ARE ALLOWED ON
 MASTER PLAN. REVISE THE ORIGINAL
 DRAWINGS.
  
 3) CITY AMENDMENTS TO FBC TABLE 2306.1
 REQUIRES THE ROOF SHEATHING TO BE NAILED
 WITH 8D RING SHANK NAILS IN ZONE THREE
 FOR BUILDINGS WITH A MEAN ROOF HEIGHT
 OF 25'- 35'. REVISE SCHEDULE ON S4.
  
 4) PROVIDE A SCHEDULE FOR THE CASTCRETE
 LINTELS THAT WILL BE USED ON THE PLANS.
 SPECIFY THE ALLOWABLE SAFE LOADS IN THE
 SCHEDULE.
  
 5) PROVDE STRUCTURAL DETAILS FOR THE
 GABLE END ROOF FRAMING AND OVERHANG.
 THE PLANS AND TRUSS LAYOUT ARE NOT CLEAR
 IN THIS AREA.
  
 6) SPECIFY THE GRAVITY LOAD CAPACITY FOR
 THE CCO SIMPSON COLUMN CAP ON THE PLANS.
  
 7) SPECIFY THE FASTENERS AND EMBED DEPTH
 ON THE STEEL COLUMN BASE DETAIL ON S5.
 CLARIFY THE NOTE THAT STATES WHERE
 NORMAL EMBEDMENT IS NOT POSSIBLE.
 PROVIDE AN ALTERNATE INSTALLATION DETAIL
 SHOWING EACH OPTION.
  
 8) SPECIFY THE TRUSS CONNECTORS FOR THE
 GR03 ROOF GIRDERS, WHICH ARE SHOWN ON
 THE TRUSS LAYOUT PARALLEL TO ONE HOUR
 TENANT SEPARATION WALL.
  
 9) REVISE CONNECTORS SPECIFIED FOR THE
 THREE PLY GIRDERS (GR01) AND TWO PLY
 GIRDERS (GR02,GR04,GR05) FROM THE
 SIMPSON MGT (MARK D) WHICH IS FOR A ONE
 PLY TRUSS TO AN APPROPRIATE CONNECTOR.
  
 10) REVISE THE UPLIFT VALUE OF THE HETAL
 20 CONNECTOR TO THE VALUE THAT DOES NOT
 INCLUDE A ONE-THIRD INCREASE IN THE
 STEEL CALCULATIONS (1810#). SEE
 FBC 1609.4.3. AND 2004 SIMPSON CATALOG.
  
 11) SUBMIT COVER SHEETS FOR STATE
 PRODUCT APPROVAL WITH FL NUMBERS FOR ALL
 PRODUCTS REQUIRED BY FAC RULE 9B-72.
 MAKE COPIES FOR ALL THREE SETS OF PLANS.
  
 12) PRODUCT APPROVAL THAT WAS SUBMITTED
 FOR THE ENTRY DOOR IS FOR A NON-IMPACT
 RATED DOOR AND WILL REQUIRE IMPACT
 PROTECTION.
  
 13) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING INFO. FOR THE ONE HOUR FIRE
 RATED GLASS BLOCK.
  
 14) THE PRODUCT APPROVALS SUBMITTED FOR
 THE OVERHEAD GARAGE DOORS DO NOT MEET
 THE REQUIRED DESIGN PRESSURES LISTED IN
 THE SCHEDULE ON THE PLANS. SUBMIT INFO.
 FOR GARAGE DOORS WITH ADEQUATE DESIGN
 PRESSURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-31 Cont ID  
Sent By jwitmer Date 2004-03-31 Time 11:34 Rev Time 4.00
Received By jwitmer Date 2004-03-31 Time 11:34 Sent To  
Notes
2004-03-31 00:00:00BUILDING PLAN REVIEW
 PERMIT:04021372
 ADD: 980 MARINA DEL RAY LANE
 CONT: WCI
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2 STORY/ 6 UNIT
  
 2ND REVIEW
  
 ACTION: DENIED
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 PLEASE!!!!!!!!!!!!!!! ON FUTURE REVIEWS
 ON YOUR TRANSMITTAL INDICATE WHERE THE
 REVISIONS HAVE BEEN MADE, NOT SEE STRUCT
 URAL. SECOND INDICATE WITH A CLOUD OR
 DELTA WHERE THE REVISIONS ARE MADE. THIS
 WILL TRUELY EXPEDITE YOUR PERMIT!!!!!!!!
  
 1) SHEET S-2 DETAIL# 1, THERE IS NO
 SCHEDULE FOR TB-1 OR B1 AS INDICATED 2ND
 FLOOR FRAMING PLAN.
  
 2) SECOND REQUEST, S-3TRUSS PLAN DOES
 NOT INDICATE THE TRUSS LOADS, VERTICAL,
 HORIZONTAL AND GRAVITY LOADS. RESPONCE:
 PLEASE TRUSS SHOP DRAWINGS FOR LOADS.
 THERE WAS NO TRUSS SHOP DRAWINGS SUB-
 MITTED.
  
 3) SECOND REQUEST: S-2 MASONARY WALLS
 ARE DESIGNATED AS MW-1, S-4 MASONARY
 WALL SCHEDULE IS #5@48"0.C., NO INFORMA-
 TION ABOUT WINDOWS OR CORNERS?
 RESPONCE SEE STRUCTURAL PLANS. WHERE????
  
 4) 2ND REQUEST: GARAGE BEAMS DO NOT GIVE
 IF LENTELS ARETO BE USED? WHAT ARE THE
 ALLOWABLE SAFE LOADS? RESPONCE: PLEASE
 SEE STRUCTURAL PLANS.WHERE?????????????
 THERE IS NO LENTAL SHEET WITH LOADING
 TABLES???????????????????????????
  
 5) 105.3 CITY ADMINISTRATIVE CODE,
 RESIDENT INSPECTOR REQUIRED.
 CONTACT HAROLD PISKURA @ 805-6711 FOR
 ADDITIONAL INFORMATION.
  
 6) PROVIDE A SITE PLAN TO BE ABLE TO VER
 IFY TABLE 600 ISSUES. TO CALCULATE TABLE
 600 ISSUES, ALLOWABLE OPENING SIZES.
 HIGHLIGHT WHICH BUILDING IS TO BE PERMIT
 ED UNDER THIS PERMIT.
  
 7) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 9) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 10)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) WHEN PLANS ARE DEFICIENT OF INFORMA-
 TION AND THE CODE SECTION IS QUOTED THE
 PLAN NEEDS TO GIVE THIS INFORMATION NOT
 QUOTE THE SECTION OF CODE.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 12) PRODUCT APPROVALS SUBMITTED:
 AMARR DOORS 7X16 LOCATED IN A END ZONE,
 LOW PRESSURES.
  
 13) 2ND REQUEST, FOR PRODUCT TESTING RE-
 PORTS FOR (G) STRUCTURAL COMPONENTS,
 TRUSS ANCHORS, WOOD CONNENCTORS!!!!!!!
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 14) PROVIDE THE FOLLOWING:
 2ND REQUEST!!!! PROVIDE THE TRUSS ENGINE
 ERING SHEETS WITH ALL LOADING CASES,
 VERTICAL, HORIZONTAL AND GRAVITY LOADS.
 PLANS ONLY INDICATE THE ALLOWABLE VALUE
 THE CONNECTOR IS GOOD FOR NOT THE UPLIFT
 VALUES!
  
 15) 2ND REQUEST SEE M-1:
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
 NOTE THAT THE CONDENSATE LINES ARE TO
 END AT LEAST 1'-0" FROM BUILDING.
  
 16) 2ND REQUEST: GARAGE SWING DOOR FROM
 THE GARAGE TO LIVING AREA, DOOR IS NOT
 LISTED ON THE DOOR SCHEDULE, A 3/4HR
 DOOR ISREQUIRED, 411.2.6, 705.1.3.5
 A) THE FLORIDA BUILDING CODE DOES NOT
 INDICATE A "C" LABEL DOOR, IT IS A 45
 MINUTE DOOR.
 B) PROVIDETHE DOOR CLOSER INFORMA-
 TION
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By rmcdouga Date 2005-02-23 Time 17:29 Rev Time 0.00
Received By rmcdouga Date 2005-02-23 Time 17:29 Sent To  
Notes
2005-02-23 00:00:00PASSED UNDER MASTER # 04021372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-15 Cont ID  
Sent By btrobaug Date 2004-07-15 Time 10:17 Rev Time 0.50
Received By btrobaug Date 2004-07-15 Time 08:09 Sent To  
Notes
2004-07-15 00:00:00 
 SEE COMMENTS FOR #04021350.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 12:37 Rev Time 1.00
Received By btrobaug Date 2004-04-05 Time 10:31 Sent To  
Notes
2004-04-05 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.116(B).(1500 VA).
  
 2} PLEASE LABLE THE ROOMS ON THE
 ELECTRICAL PLANS TO CORRESPOND TO THE
 ARCHITECTURAL PLANS.
  
 3} PLEASE PROVIDE PLANS FOR ALL UNITS,
 INCLUDING REVERSE UNITS.
  
 4} THE PANEL SCHEDULE REFERS TO
 "LIVING/BREAKFAST" ROOM.THE "BREAKFAST"
 ROOM MUST COMPLY WITH 210.52, 20 AMP CIR
  
 5} SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 6} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE
 STAMPS ARE NOT ACCEPTABLE PER F.B.P.E.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-12 Cont ID  
Sent By mamini Date 2004-04-12 Time 14:22 Rev Time 1.00
Received By mamini Date 2004-04-12 Time 14:22 Sent To  
Notes
2004-04-12 00:00:00PASSED :
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By mamini Date 2004-03-09 Time 08:25 Rev Time 0.50
Received By mamini Date 2004-03-09 Time 08:25 Sent To  
Notes
2004-03-09 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS FOR
 PERMITTING, NOTE THAT CIVIL PLANS WERE
 REVIEWED UNDER # 03101412 (PLAN REVIEW),
 AT YOUR OPTION UNDERGROUND UTILITIES AND
 SITE WORK COULD BE UNDER SEPARATE PERMIT
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By rmcdouga Date 2005-02-23 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2005-02-23 Time 17:08 Sent To  
Notes
2005-02-23 00:00:00PASSED UNDER MASTER # 04021372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By nmccray Date 2004-07-20 Time 15:44 Rev Time 0.00
Received By nmccray Date 2004-07-20 Time 15:44 Sent To  
Notes
2004-07-20 00:00:00*************DENIED*********************
 1) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 2) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS
 NFPA 101 2000 EDITION.
  
 3) PLEASE EXPLAIN EXITING RATIONALE
 FROM INSIDE THE UNITS.
  
 4) EMERGENCY INSTRUCTIONS FOR RESIDENTS
 SHALL BE PROVIDED.
  
 5) WET FIRE HYDRANTS SHALL BE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 6) SUITABLE AND ACCESSIBLE ROADS ARE
 REQUIRED DURING CONSTRUCTION.
  
 THESE NOTES AND COMMENTS ARE ALSO FOR
 PERMITS: 04021350, 04021376, 04021354
 04021358, 04021356
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-07 Cont ID  
Sent By mcarsill Date 2004-04-07 Time 13:48 Rev Time 0.00
Received By mcarsill Date 2004-04-07 Time 13:48 Sent To  
Notes
2004-04-07 00:00:001) ALL SMOKE DETECTORS SHALL BE A
 MINIMUM OF THREE FEET FROM AC
 DIFFUSERS.
  
 2) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.
  
 3) THE REQUIRED FIRE SPRINKLER SYSTEM
 SHALL BE MONITORED BY UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 4) BUILDING ADDRESSES NOT SHOWN ON
 ELEVATION DRAWINGS.
  
 5) ALL NEW STAIRS SHALL HAVE HANDRAILS
 ON BOTH SIDES.
  
 6) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 7) PLEASE EXPLAIN EXITING RATIONALE
 FROM INSIDE THE UNITS.
  
 8) EMERGENCY INSTRUCTIONS FOR
 RESIDENTS SHALL BE PROVIDED.
  
 9) WET FIRE HYDRANTS SHALL BE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 10) SUITABLE ROADS ARE REQUIRED DURING
 CONSTRUCTION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 11:21 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 11:20 Sent To P
Notes
2005-05-27 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 17:30 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 17:30 Sent To M
Notes
2005-04-29 00:00:00TO "PKRAUSS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 16:31 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 16:31 Sent To B
Notes
2005-04-22 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 13:20 Sent To  
Notes
2005-03-11 00:00:00TO "KSTEVENS"(SFR)

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-02-08 Cont ID  
Sent By adarroug Date 2005-02-08 Time 08:56 Rev Time 0.00
Received By adarroug Date 2005-02-08 Time 08:56 Sent To B
Notes
2005-02-08 00:00:00TO RMCDOUGAL DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 11:18 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 11:18 Sent To  
Notes
2004-06-15 00:00:00TO COMM BD #28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-31 Cont ID  
Sent By jwitmer Date 2004-03-31 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2004-03-03 Time 10:39 Sent To PC
Notes
2004-03-03 00:00:00TO COMM BD#48/ROLLS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-05-03 Cont ID  
Sent By hmoser Date 2005-05-02 Time   Rev Time 0.00
Received By hmoser Date 2005-05-03 Time 09:09 Sent To  
Notes
2005-05-02 00:00:00 
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By rmcdouga Date 2005-02-23 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2005-02-23 Time 17:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 16:48 Rev Time 0.15
Received By pkrauss Date 2004-05-14 Time 16:48 Sent To  
Notes
2004-05-14 00:00:00PER MTG 5-14-04 COMMENTS ADDRESSED
 PLANS OKAY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By pkrauss Date 2004-03-26 Time 09:49 Rev Time 0.45
Received By pkrauss Date 2004-03-26 Time 09:48 Sent To  
Notes
2004-03-26 00:00:00DENIED:
 1.PLAN SHEET A-21 DETAIL 2, INDICATES
 A 1HR FIRE RATED FLOOR/CEILING ASSEMBLY.
 PLEASE PROVIDE UL LISTING FOR
 PENETRATIONS THROUGH THE MEMBRANE AT
 EACH GRILLE.PLEASE CLARIFY.
  
 2.PLEASE NOTE, A SHAFT ENCLOSURE IS
 NOT REQUIRED PER 2001 FBC 705.2.2,
 FIRE DAMPER NOT REQUIRED.
  
 3.PLAN SHEET M-1 UNIT C, O.A. APPEARS
 TO BE LOCATED IN THE GARAGE.FRESH AIR
 INTAKES SHALL BE LOCATED AS NOT TO
 CIRCULATE CARBON MONOXIDE INTO HVAC
 SYSTEM.PLEASE ADVISE.
  
 4.PLAN SHEET M-2 UNIT 2L & 2R RETURN
 AIR JUMPERS ARE NOT SIZED PROPERLY.
 RETURN SHALL BE A MINIMUM OF 14".THE
 TOTAL SUPPLY AIR INTO MASTER SUITE SHALL
 BE USED WHEN SIZING THE RETURN FOR THE
 MASTER SUITE.REVISED 2001 FBC(M)
 601.4 EXCEPTION #1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-06-13 Cont ID  
Sent By jleech Date 2005-06-13 Time 13:41 Rev Time 0.33
Received By jleech Date 2005-06-13 Time 13:41 Sent To  
Notes
2005-06-13 00:00:00ADD WATER METERS TO EACH UNIT

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-04-02 Cont ID  
Sent By jleech Date 2005-04-02 Time 11:52 Rev Time 0.50
Received By jleech Date 2005-04-02 Time 11:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-23 Cont ID  
Sent By rmcdouga Date 2005-02-23 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2005-02-23 Time 17:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-19 Cont ID  
Sent By kstevens Date 2004-07-19 Time 17:19 Rev Time 0.50
Received By kstevens Date 2004-07-19 Time 17:19 Sent To  
Notes
2004-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENT FROM PREVIOUS REVIEW HAS NOT
 BEEN ADDRESSED. COMMENT NUMBER FROM PRE-
 VIOUS REVIEW TO STAY THE SAME TO AVOID
 CONFUSION,
 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 **************NEW COMMENTS**************
 1C) SHT P-1 DOMESTIC WATER SUPPLY DETAIL
 SHOWS THE WATER SUPPLY UNDER THE SLAB &
 SHOWS AN ADAPTOR FROM PVC TO COPPER.
 SUBMIT A DETAIL SHOWING TYPE OF FITTING
 AND MANUF. SPECIFICATION SHOWING APPROV-
 AL FOR UNDER SLAB INSTALLATION FOR THE
 ADAPTOR. SECTION 104.2.1
 2C) SHP P-1 SHOWS MAIN SHUTOFF VALVE IN-
 SIDE THE GARAGE, BUT PLUMBING GENERAL
 NOTES #13 INDICATES THAT VALVE SHALL BE
 LOCATED OUTSIDE OF THE BUILDING. PLEASE
 CLARIFY AND CORRELATE PLANS AND NOTES.
 SECTION 104.2.1
 3C) SHT P-1 PLUMBING GENERAL NOTES #19
 HAS BEEN DELETED WITH WHITE-OUT. THIS IS
 NOT APPROVED. PLEASE DELETE NOTE ON PLAN
 PROPERLY. SECTION 104.2.1.3
 4C) SEE ATTACHED SHEET IN REFERENCE TO
 FS 553.80(2)(B). FOUT TIMES THE FEE FOR
 THE PLAN REVIEW PORTION OF THE PERMIT
 SHALL BE IMPOSED IF THE SAME COMMENTS
 ARE NOT ADDRESSED PER FLA. STATUTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-03-15 Time 16:10 Rev Time 0.50
Received By kstevens Date 2004-03-15 Time 16:10 Sent To  
Notes
2004-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A WATER RISER DIAGRAM IS REQUIRED FOR
 ALL UNIT TYPES. SECTION 104.3.1.1
 2) SHTS P-1, P-2 & P-3 SIGNATURE REQD ON
 SEAL, SIGNATURE STAMP NOT ACCEPTABLE.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-07-21 Cont ID  
Sent By mmclean Date 2004-07-21 Time 16:48 Rev Time 0.00
Received By mmclean Date 2004-07-21 Time 16:48 Sent To  
Notes
2004-07-21 00:00:00APPROVED BY ERIC SCHNEIDER, SENIOR
 PLANNING, 659-8031

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By sgraham Date 2004-03-22 Time 09:00 Rev Time 0.00
Received By sgraham Date 2004-03-22 Time 09:00 Sent To  
Notes
2004-03-22 00:00:001. NO SITE & LANDSCAPE PLANS INCLUDED
 2.MUST SHOW BUILDINGS HEIGHT MEETS
 CODE REQUIRESMENTS ON ELEVATIONS
 SHEETS A-9,A-10, A-11, A-12


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved