Plan Review Details - Permit 04021360
Plan Review Stops For Permit 04021360
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-10-06 Cont ID  
Sent By rmcdouga Date 2005-10-06 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2005-10-06 Time 07:22 Sent To  
Notes
2005-10-06 00:00:00REVISED SHEET A-13.1 IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-05-24 Cont ID  
Sent By rmcdouga Date 2005-05-24 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2005-05-24 Time 14:16 Sent To  
Notes
2005-05-24 00:00:00REVISED ROOF SHINGLES TO CERTAINTEED

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-24 Cont ID  
Sent By rmcdouga Date 2005-03-24 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2005-03-24 Time 09:18 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-03-18 Cont ID  
Sent By rmcdouga Date 2005-03-18 Time 16:38 Rev Time 0.00
Received By rmcdouga Date 2005-03-18 Time 16:38 Sent To  
Notes
2005-03-18 00:00:00DENIED
  
 1) THE SURVEY INCORRECTLY SPECIFIES THE
 STRUCTURE AS TWO STORY.
  
 2) THE ENERGY CALC. FORM IS NOT SIGNED
 BY THE OWNER/AGENT.
  
 3) THERE IS AN ADDITIONAL ENERGY CALC.
 FORM LISTING A 4TON UNIT FOR THE 2215
 SQFT MID UNIT THAT WAS NOT SUBMITTED
 WITH THE MASTER.
  
 4) SHEETS A6, A7 AND A8 HAVE BEEN
 REVISED AND DO NOT MATCH THE MASTER
 PLAN. THE STEP IN THE ROOF HAS BEEN
 CHANGED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-08-03 Cont ID  
Sent By rmcdouga Date 2004-07-29 Time 16:31 Rev Time 0.00
Received By rmcdouga Date 2004-07-29 Time 16:31 Sent To  
Notes
2004-07-29 00:00:00NOTE: BEFORE THE CERTIFICATE OF
 OCCUPANCY IS ISSUED THE RECORDED
 DECLARATION OF CONDOMINIUM WILL BE
 REQUIRED.
  
 1) ENERGY CALCS. ARE REQUIRED FOR EACH
 UNIT TYPE AND LOCATION (EXTERIOR AND
 INTERIOR). THE CONDITIONED SPACE ON THE
 FORMS DIFFERS FROM THE ONES LISTED ON
 THE PLANS. PLEASE CORRECT.
  
 2) MASTERED PLANS ARE NOT ALLOWED TO BE
 REDLINED. SEE SHEETS A10, S7 AND S5.
 PLEASE CORRECT SEPIAS.
  
 3) DETAIL 4 ON S1 IS INCORRECT. IT
 SHOULD BE A SECTION OF THE EXTERIOR WALL
 AND FOOTING.
  
 4) THE FOUNDATION NOTES #3,4,& 5 ON S1
 REFER TO SHEETS S3 AND S4 FOR DETAILS.
 HOWEVER, THERE ARE NO FOUNDATION NOTES
 ON S3 OR S4. PLEASE CORRECT.
  
 5) ON SHEET A12, DETAIL #2 IS MISSING
 THE FIRESTOP BETWEEN THE VERTICAL AND
 HORIZONTAL AREAS. WALL SHEATHING SHOULD
 EXTEND TO BOTTOM OF FLOOR TRUSSES.
 PLEASE CORRECT.
  
 6) FIRESTOP IS ALSO MISSING AT CONCEALED
 SPACES WHERE HORIZONTAL AND VERTICAL
 SPACES INTERSECT AT SECTIONS 11 AND 13
 ON S7. SEE FBC 2305.1.4.
  
 7) SHEET S2 HAS AN ID MARK FOR A DETAIL
 #17 ON S7. THERE IS NO SUCH DETAIL.
 PLEASE CORRECT.
  
 8) THE PRODUCT APPROVAL SUBMITTED FOR
 THE FRONT DOOR INDICATES THAT THE DOOR
 IS NOT RATED FOR IMPACT AND IS REQUIRED
 TO BE SHUTTERED. PLANS SPECIFY THIS DOOR
 IS REQUIRED FOR EGRESS AND IS NOT TO BE
 SHUTTERED. PLEASE CORRECT.
  
 9) REVISE THE UPLIFT VALUE LISTED IN THE
 SCHEDULE ON S4 FOR THE SIMPSON HETAL 20.
 THE MAXIMUM UPLIFT VALUE IS 1810# IN THE
 2004 SIMPSON CATALOG, WHICH DOES NOT
 INCLUDE A ONE-THIRD INCREASE IN THE
 STEEL CALCULATIONS.
  
 10) REVIEW THE TRUSS DRAWINGS AND REVISE
 THE CONNECTORS SPECIFIED FOR TRUSSES
 THAT EXCEED THE UPLIFT VALUES GIVEN IN
 SCHEDULE FOR THE SPECIFIED CONNECTOR.
 MARK (F) AN H10 IS NOT ADEQUATE FOR
 TRUSSES T4B, T4, T3, T2, T1, H2, AND H1.
 MARK (H) AN H3 AND MARK (A) A HETAL 12
 ARE ALSO INADEQUATE FOR SOME OF THE
 TRUSS UPLIFTS FOR WHICH THEY ARE
 SPECIFIED. PLEASE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-31 Cont ID  
Sent By jwitmer Date 2004-03-31 Time 15:47 Rev Time 0.00
Received By rmcdouga Date 2004-07-29 Time 16:30 Sent To  
Notes
2004-03-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021360
 ADD: 960 MILLBRAE COURT
 CONT:WCI
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
  
 ACTION: DENIED
  
 NOTE: A SIGNED & SEALED LETTER FROM THE
 ARCHITECT OF RECORD INDICATING THE PLANS
 SUBMITTED ARE OCCUPANCY TYPE: (R2).
 WITH THE VARIOUS PLANS AND GEO REPORTS
 STATING TOWNHOMES AS PART OF THE NAME,
 IT IS TO BE MADE CLEAR THAT THE REVIEWS
 AND PERMITS WILL BE ISSUED "R2" FOR
 CONDOMINIUM. BEFORE THE CERTIFICATE OF
 OCCUPANCY IS ISSUED THE RECORDED
 DECLARATION OF CONDOMINIUM WILL BE
 REQUIRED.
  
 1) 105.3 CITY ADMINISTRATIVE CODE,
 RESIDENT INSPECTOR TO BE REQUIRED.
 CONTACT HAROLD PISKURA @ 805-6711, FOR
 MORE INFORMATION AS TO COMPLETED UNITS
 VS CONSTRUCTION AREAS, REQUIRED STRUC-
 TURAL INSPECTORS AND PHASING.
  
 2) SITE PLAN INDICATING ALL SITE AMENIT-
 ITIES WITH DIMENSIONS BETWEEN BUILDINGS
 INDICATING THE ASSUMED PROPERTY LINE
 BETWEEN BUILDINGS, TO CALCULATE ALLOW-
 ABLE OPENING SIZES, VERIFY WITH TABLE
 600.
  
 3) SOILS REPORT:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) WHEN THE ENERGY FORMS ARE FILLED OUT
 BY THE ENGINEER OF RECORD THIS IS FOR
 PUBLIC RECORD, MUST BE SIGNED& SEALED.
  
 6) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) FAIR HOUSING FOR THE COMMON AREAS,
 PROVIDE A SITE PLAN INDICATING THE
 ACCESSIBLE ROUTE TO ALL ELEMENTS, INCLUD
 ING THE CLUBHOUSE, GAZEBOES,DUMPSTERS,
 POOLS, PARKING AND THE PATH OF TRAVEL
 TO PUBLIC TRANSPORTATION.
  
 9) SEE S-5
 CORRECT DOOR AND WINDOW PRESSURE SCHED-
 ULE, WALL AREAS INTERIOR ZONES SHOULD BE
 REPRESENTED BY ZONE (4) NOT ZONE(1),AND
 THE END ZONES SHOULD BE REPRESENTED BY
 ZONE(5) NOT (2).
 B) ROOF NAILING ZONES,ZONE (3) NOTE DIF
 FICULT TO UNDERSTAND, IT CAN BE PRECEVED
 THAT THE ZONE (3) MAY BE NAILED THE
 SAME AS ZONE# 2.
 C) ROOF NAILING CHART IS ONLY GOOD TO
 35' ABOVE GRADE. THE TRUE HEIGHT OF THE
 BUILDING IS > 35', THE ENGINEER OF
 RECORD SHALL PROVIDE THE ADDITIONAL
 INFORMATION REQUIRED FOR THE NAILING
 REQUIREMENTS FOR THE EFFECTED NAILING
 ZONES.
  
 10) AMARR GARAGE DOORS DO NOT MEET THE
 NEGITIVE PRESSURES FOR A BUILDING >35'
 TALL WITH THE ADJUSTMENT COEFFICIENT
 OF 1.09 SEE 1606.2D & 1606.2E.
  
 11) SHEET A-12 DETAIL# 2, IS MISSING THE
 FIRE STOP BETWEEN THE VERTICAL & HORIZON
 TAL AREAS 2ND & 3RD FLOOR WALL SHEATHING
 CUT SHORT, ALSO MISSING FOR THE WALL
 DIAPHRAM.
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 2ND REQUEST:
 FOR THE PRODUCT TESTING REPORTS FOR THE
 STRUCTURAL COMPONENTS- TRUSS ANCHORS,
 CONCRETE TO WOOD, WOOD TO WOOD.
  
 13) SHEET M-1, M-2 :
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 14) 2ND REQUEST, PROVIDE TRUSS ENGINEER-
 ING SHEETS WITH ALL LOADING CASES, VER-
 TICAL, HORIZONTAL AND GRAVITY LOADS. THE
 PLANS DO NOT INDICATE THE LOADING, ONLY
 THE ALLOWABLE VALUES FOR ANCHORS.
  
 15) GARAGE TO LIVING QUARTERS, THE
 GARAGE DOOR IS NOT LISTED ON THE DOOR
 SCHEDULE. A 3/4HR RATED DOOR IS REQUIRED
 4.1.2.6/ 705.1.3.5, THS DOOR SHALL ALSO
 BE EQUIPED WITH AN APPROVED CLOSER.
  
 16) SHEET S-2 MASONARY WALLS, ARE DESIGN
 EDAS MW-1, S-5 MASONARY WALL SCHEDULE IS
 #5@48" O.C., NO MENTION ABOUT REINFORC-
 ING AT WINDOWS NOR CORNERS.
  
 17) GARAGE BEAMS AT OVERHEAD DOORS, NO
 INFORMATION IN THEBEAM SCHEDULE NOR IS A
 LENTAL SCHEDULE PROVIDED WITH THE SAFE
 ALLOWABLE LOADS.
  
 18) S-3 VS S-7 DETAIL# 8 INDICATES THIS
 IS TO BE A 2X6 WALL NO DETAILS FOR FAST-
 ENING THE WALL TO THE STRUCTURE BELOW.
 VERSES THE SHEET S-3 INDICATING A BLOCK
 WALL NO BEAM INFORMATION ?
  
 19) S-7 DETAIL 11:
 A) THIS DETAIL IS MISSING STRAPING FOR
 THE WALL TO FLOOR TRUSSES.
 B) MISSING LEDGER ON THE LOWER WALL
 FOR NAILING OF THE DRYWALL CEILING.
 C) MISSING FIRESTOP LOWER WALL WHERE
 THE MISSING LEDGER IS LOCATED.
  
 20) S-7 DETAIL 13:
 A) MISSING FIRESTOP VERTICAL TO HORIZON-
 TAL LOCATIONS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-03-24 Cont ID  
Sent By rmcdouga Date 2005-03-24 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2005-03-24 Time 09:21 Sent To  
Notes
2005-03-24 00:00:00PASSED UNDER MASTER # 04071171

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-08 Cont ID  
Sent By btrobaug Date 2004-07-08 Time 14:03 Rev Time 0.75
Received By btrobaug Date 2004-07-06 Time 07:03 Sent To  
Notes
2004-07-08 00:00:00 
 PLEASE INCLUDE THE ENGINEERING FIRMS
 AUTHORIZATION NUMBER ON THE TITLE BLOCK
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
 PER 61G15-23.002 FAC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-01 Cont ID  
Sent By btrobaug Date 2004-04-01 Time 18:14 Rev Time 2.00
Received By btrobaug Date 2004-04-01 Time 17:08 Sent To  
Notes
2004-04-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE EQUIPMENT GND CONDUCTOR
 SIZE ON THE RISER DIAGRAM PER 250.122.
  
 2} THE DRAWING SHOWS A MAIN DISCONNECT
 AND 8 "METERS AND DISCONNECTS". THE
 RISER INDICATES A 6GANG METER CENTER
 WITH NO MAIN. PLEASE CORRELATE.
  
 3} THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.16.(1500 VA).
  
 4} PLEASE LABEL ROOMS ON THE ELECTRIC
 PLANS TO CORRESPOND WITH THE
 ARCHITECTURAL PLANS.
  
 5} PLEASE PROVIDE PLANS FOR ALL UNITS,
 INCLUDING REVERSED MODELS.
  
 6} NOTE THAT THE "NOOK" 7 DINING ROOM
 MUST COMPLY WITH 210.52(B).
  
 7} THE DINING ROOMIN UNIT "2203" MUST
 HAVE 2 RECEPTACLES ADDED TO COMPLY WITH
 210.52(A).
  
 8} THE PANEL SCHEDULE REFERS TO
 "LIVING/BREAKFAST" ROOM, THE BREAKFAST
 ROOM
 MUST BE ON A 20 AMP CIRCUIT TO COMPLY
 WITH 210.52(B), HOWEVER THERE IS NO
 ROOM LABLED LIKE THAT ON THE
 ARCHITECTURAL PLANS.
  
 9} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODESTAMPED SIGNATURES ARE NOT
 ACCEPTABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-12 Cont ID  
Sent By mamini Date 2004-04-12 Time 14:57 Rev Time 1.00
Received By mamini Date 2004-04-12 Time 14:57 Sent To  
Notes
2004-04-12 00:00:00PASSED :
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-08 Cont ID  
Sent By mamini Date 2004-03-08 Time 15:43 Rev Time 0.50
Received By mamini Date 2004-03-08 Time 15:43 Sent To  
Notes
2004-03-08 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS FOR
 PERMITTING, NOTE THAT CIVIL PLANS WERE
 REVIEWED UNDER #03101412 (PLAN REVIEW),
 AT YOUR OPTION UNDERGROUND UTILITIES &
 SITE WORK COULD BE UNDER SEPARATE PERMIT
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-03-24 Cont ID  
Sent By rmcdouga Date 2005-03-24 Time 09:20 Rev Time 0.00
Received By rmcdouga Date 2005-03-24 Time 09:19 Sent To  
Notes
2005-03-24 00:00:00PASSED UNDER MASTER # 04071171

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-06-16 Cont ID  
Sent By mcarsill Date 2004-06-16 Time 15:29 Rev Time 0.00
Received By mcarsill Date 2004-06-16 Time 15:29 Sent To  
Notes
2004-06-16 00:00:00870 MARINA DEL RAY
 883 MILLBRAE COURT
 840 MARINA DEL RAY
 845 MILLBRAE COURT
  
 1) PLEASE INDICATE WHAT FIRE HYDRANTS
 WILL BE AVAILABLE WHEN THE BUILDINGS
 ARE UNDER CONSTRUCTION.
  
 2) YOUR PERMIT RESPONSE FOR WALLS AND
 CEILINGS ARE INCORRECT. CLASS A, B,
 OR C NOT PAINTED RESPONSE IS REQUIRED.
  
 3) THE REQUIRED FIRE SPRINKLER
 SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE. "STATION
 LOCATED AT GATEHOUSE DOES NOT MEET
 THIS REQUIREMENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-07 Cont ID  
Sent By mcarsill Date 2004-04-07 Time 13:53 Rev Time 0.00
Received By mcarsill Date 2004-04-07 Time 13:53 Sent To  
Notes
2004-04-07 00:00:00SEE PREVIOUS PLAN REVIEW COMMENTS
 FOR OTHER BUILDINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-10-05 Cont ID  
Sent By pkrauss Date 2005-10-05 Time 10:29 Rev Time 0.00
Received By pkrauss Date 2005-10-05 Time 10:29 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-09-26 Cont ID  
Sent By adarroug Date 2005-09-26 Time 17:40 Rev Time 0.00
Received By adarroug Date 2005-09-26 Time 17:40 Sent To P
Notes
2005-09-26 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status F Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 19:40 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 19:40 Sent To B
Notes
2005-09-21 00:00:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 17:09 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 17:09 Sent To M
Notes
2005-09-15 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 14:42 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 14:42 Sent To P
Notes
2005-05-27 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-18 Cont ID  
Sent By adarroug Date 2005-05-18 Time 16:13 Rev Time 0.00
Received By adarroug Date 2005-05-18 Time 16:13 Sent To B
Notes
2005-05-18 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-22 Cont ID  
Sent By adarroug Date 2005-03-22 Time 12:01 Rev Time 0.00
Received By adarroug Date 2005-03-22 Time 12:01 Sent To B
Notes
2005-03-22 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-15 Cont ID  
Sent By adarroug Date 2005-03-15 Time 10:01 Rev Time 0.00
Received By adarroug Date 2005-03-15 Time 10:01 Sent To Z
Notes
2005-03-15 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 10:01 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 10:01 Sent To  
Notes
2004-06-15 00:00:00TO COMM BD #28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-05-10 Time 10:11 Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 10:34 Sent To  
Notes
2004-03-03 00:00:00TO COMM BD#48/ROLLS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2005-10-05 Cont ID  
Sent By pkrauss Date 2005-10-05 Time 10:30 Rev Time 0.30
Received By pkrauss Date 2005-10-05 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-09-28 Cont ID  
Sent By rregueir Date 2005-09-28 Time 16:34 Rev Time 0.00
Received By rregueir Date 2005-09-28 Time 16:04 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-07-02 Cont ID  
Sent By pkrauss Date 2004-07-02 Time 11:38 Rev Time 0.40
Received By pkrauss Date 2004-07-02 Time 11:17 Sent To  
Notes
2004-07-02 00:00:00MASTER FOR ROWHOUSE 6 UNITS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-26 Cont ID  
Sent By pkrauss Date 2004-03-26 Time 06:56 Rev Time 0.55
Received By pkrauss Date 2004-03-25 Time 16:45 Sent To  
Notes
2004-03-26 00:00:00DENIED:
 1.PLEASE NOTE, DETAIL OF UL DESIGN
 L528, IN THE UL DIRECTORY DOES NOT
 INDICATE ANY PENETRATIONS THROUGH THIS
 ASSEMBLY.PLEASE PROVIDE UL LISITING
 FOR THE PENETRATIONS THROUGH THE RATED
 ASSEMBLY.
  
 2.PLEASE CLARIFY RATING ON PLAN SHEET
 A-10 DETAIL #4, THE 1HR RATING IS AT THE
 PARTITION WALL TO THE UNDERSIDE OF THE
 CEILING CORRECT?IF THIS IS CORRECT,
 THE FIRE DAMPER INDICATED ON PLAN SHEET
 M-1 IS NOT REQUIRED BECAUSE THE WALL
 DOES NOT CONTINUE ABOVE THE CEILING.
  
 3.CLARIFY O.A. DUCT, IT APPEARS TO BE
 ABOVE THE CEILING AND DOES NOT PENETRATE
 AT THE POINT OF ENTRY, FIRE DAMPER IS
 NOT REQUIRED.
  
 4.PER 2001 FBC 705.2.2 EXCEPTION #1,
 A SHAFT ENCLOSURE IS NOT REQUIRED FOR
 OPENINGS TOTALLY WITHIN A DWELLING UNIT
 & CONNECTING FOUR STORIES OR LESS.
  
 5.PLANS SHALL BE SIGNED BY THE
 ENGINEER NOT STAMPED WITH THEIR
 SIGNATURE PER FS 471.025.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-10-07 Cont ID  
Sent By jleech Date 2005-10-07 Time 14:44 Rev Time 0.00
Received By jleech Date 2005-10-07 Time 14:44 Sent To  
Notes
2005-10-07 00:00:00REVISED PLUMBING PAGES P-1 & P-2 ONLY
 PAGE P-3 NOT CLOUDED.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-14 Cont ID  
Sent By jleech Date 2005-06-14 Time 13:27 Rev Time 0.33
Received By jleech Date 2005-06-14 Time 13:27 Sent To  
Notes
2005-06-14 00:00:00ADDED WATER METER IN EACH UNIT

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-03-24 Cont ID  
Sent By rmcdouga Date 2005-03-24 Time 09:19 Rev Time 0.00
Received By rmcdouga Date 2005-03-24 Time 09:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By kstevens Date 2004-07-20 Time 07:05 Rev Time 0.50
Received By kstevens Date 2004-07-20 Time 07:04 Sent To  
Notes
2004-07-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEWS HAVE
 NOT BEEN ADDRESSED PROPERLY. COMMENT
 NUMBER TO STAY THE SAME TO AVOID CONFUS-
 ION.
 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME
 ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY
 THIS REQUIREMENT. FAC 61G15-23.002(2)
 AND FS 471.025.
 ***************NEW COMMENTS*************
 1C) SHT P-1 PLUMBING GENERAL NOTES #19
 HAS BEEN DELETED WITH WHITE-OUT. THIS IS
 NOT APPROVED. PLEASE DELETE NOTE ON PLAN
 PROPERLY. SECTION 104.2.1.3
 2C) SHT P-1 PLUMBING GENERAL NOTES #16
 WHITE OUT USED ON NOTE TO DELETE INFOR-
 MATION. THIS IS NOT APPROVED. 104.2.3
 3) WATER RISER DIAGRAMS ARE UNCLEAR AND
 HARD TO READ. THE WATER RISER DIAGRAM ON
 SHT P-2 DOES NOT REFLECT THE FLOOR PLAN.
 THE BATHROOM ON THE FIRST FLOOR AND THE
 BATHROOM ON THE SECOND FLOOR SHOWN ON
 THE FLOOR PLAN ARE NOT SHOWN ON THE
 WATER RISER DIAGRAM.
 4)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 5C) SEE ATTACHED SHEET IN REFERENCE TO
 FS 553.80(2)(B). FOUR TIMES THE FEE FOR
 THE PLAN REVIEW PORTION OF THE PERMIT
 SHALL BE IMPOSED IF THE SAME COMMENTS
 ARE NOT ADDRESSED PER FLA. STATUTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-03-15 Time 15:31 Rev Time 0.50
Received By kstevens Date 2004-03-15 Time 15:31 Sent To  
Notes
2004-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A WATER RISER DIAGRAM IS REQUIRED FOR
 ALL UNIT TYPES. SECTION 104.3.1.1
 2) SHTS P-1 & P-2 SIGNATURE REQUIRED ON
 SEAL, SIGNATURE STAMP NOT ACCEPTABLE.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-03-24 Cont ID  
Sent By eschneid Date 2005-03-24 Time 15:42 Rev Time 0.00
Received By eschneid Date 2005-03-24 Time 15:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2005-03-17 Cont ID  
Sent By eschneid Date 2005-03-17 Time 16:52 Rev Time 0.00
Received By eschneid Date 2005-03-17 Time 16:52 Sent To  
Notes
2005-03-17 00:00:001) THE SURVEY DOES NOT MATCH THE
 SUBMITTED PLANS. SURVEY CALLS OUT A 2
 STORY BUILDING, WHILE PLANS ARE FOR A 3
 STORY BUILDING.
 2) SETBACK DISTANCE FROM THE BUILDING TO
 THE EAST PROPERTY LINE SHALL BE SHOWN.
 ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By sgraham Date 2004-03-22 Time 09:18 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2004-03-22 00:00:001. NO SITE & LANDSCAPE PLANS INCLUDED
 2. MUST SHOW BUILDING HEIGHT MEETS CODE
 REQUIREMENT ON ELEVATION SHEETS
 A-7,A-8
 3. FALSE CHIMNEY EXCEEDS HEIGHT
 EXCEPTION.