Plan Review Details - Permit 04021359
Plan Review Stops For Permit 04021359
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-04-22 Cont ID  
Sent By rmcdouga Date 2005-04-22 Time 08:41 Rev Time 0.00
Received By rmcdouga Date 2005-04-22 Time 08:41 Sent To  
Notes
2005-04-22 00:00:00REVISED ROOF SHINGLES TO CERTAINTEED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2005-03-18 Cont ID  
Sent By rmcdouga Date 2005-03-18 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2005-03-18 Time 06:57 Sent To  
Notes
2005-03-18 00:00:00REVISION TO CHANGE FROM AN "A" ELEVATION
 TO A "B" ELEVATION IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-08 Cont ID  
Sent By rmcdouga Date 2005-03-08 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2005-03-08 Time 15:30 Sent To  
Notes
2005-03-08 00:00:00SLAB AND WALL COMPRESSION TESTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2004-11-29 Cont ID  
Sent By rmcdouga Date 2004-11-29 Time 15:12 Rev Time 0.00
Received By rmcdouga Date 2004-11-29 Time 15:12 Sent To  
Notes
2004-11-29 00:00:00TIE IN SURVEY REVIEWED AND PUT IN FILE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 17:17 Rev Time 0.00
Received By rmcdouga Date 2004-09-22 Time 17:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-09-14 Time 15:27 Rev Time 1.77
Received By jwitmer Date 2004-06-29 Time 13:04 Sent To  
Notes
2004-06-29 00:00:00 
  
 BUILDING PLAN REVIEW
 PERMIT: 04021359
 ADD: 899 MARINA DEL RAY LA
 CONT: WCI
 TEL: (561)951-2226
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) CORRECT AND RERECORD NOC
  
 2) GLASS BLOCK: PROVIDE INFO FOR THE
 FIRE RATING OF THE GLASS BLOCK
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By jwitmer Date 2004-03-23 Time 11:11 Rev Time 1.20
Received By jwitmer Date 2004-03-23 Time 11:11 Sent To  
Notes
2004-03-23 00:00:003/23/04SEE MASTER 04021355 FOR COMMENTS

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 17:18 Rev Time 0.00
Received By rmcdouga Date 2004-09-22 Time 17:18 Sent To  
Notes
2004-09-22 00:00:00PASSED UNDER MASTER# 04010005

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-14 Cont ID  
Sent By btrobaug Date 2004-07-14 Time 09:44 Rev Time 0.50
Received By btrobaug Date 2004-07-14 Time 09:44 Sent To  
Notes
2004-07-14 00:00:00 
 SEE COMMENTS ON PERMIT #04021345.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 06:56 Rev Time 0.50
Received By btrobaug Date 2004-04-06 Time 06:56 Sent To  
Notes
2004-04-06 00:00:00 
 PLEASE SEE COMMENTS, REVIEW#04021355
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-12 Cont ID  
Sent By mamini Date 2004-04-12 Time 14:33 Rev Time 1.00
Received By mamini Date 2004-04-12 Time 14:33 Sent To  
Notes
2004-04-12 00:00:00PASSED :
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By mamini Date 2004-03-09 Time 08:05 Rev Time 0.50
Received By mamini Date 2004-03-09 Time 08:05 Sent To  
Notes
2004-03-09 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS FOR
 PERMITTING, NOTE THAT CIVIL PLANS WERE
 REVIEWED UNDER # 03101412 (PLAN REVIEW),
 AT YOUR OPTION UNDERGROUND UTILITIES &
 SITE WORK COULD BE UNDER SEPARATE PERMIT
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 17:19 Rev Time 0.00
Received By rmcdouga Date 2004-09-22 Time 17:19 Sent To  
Notes
2004-09-22 00:00:00PASSED UNDER MASTER# 04010005

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-20 Cont ID  
Sent By nmccray Date 2004-07-20 Time 11:24 Rev Time 0.00
Received By nmccray Date 2004-07-20 Time 11:24 Sent To  
Notes
2004-07-20 00:00:00DENIED**********************************
 PLEASE SEE COMMENTS ON PERMIT 04021355
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 13:10 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 13:10 Sent To M
Notes
2005-05-13 00:00:00TO "PKRAUSS" DESK

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-13 Cont ID  
Sent By adarroug Date 2005-04-13 Time 10:19 Rev Time 0.00
Received By adarroug Date 2005-04-13 Time 10:19 Sent To B
Notes
2005-04-13 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 13:57 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 13:57 Sent To  
Notes
2005-03-11 00:00:00TO "COMM" BD#24/SFR

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-23 Cont ID  
Sent By mjacobs Date 2004-11-23 Time 12:33 Rev Time 0.00
Received By mjacobs Date 2004-11-23 Time 12:33 Sent To B
Notes
2004-11-23 00:00:00SENT TO DON NEELY DESK.APPLICATION WAS
 RETURNED TO MY DESK BY HARROLD PISKURA
 APPLICATION WAS GIVEN TO LUIS MARTINEZ.
 11-24-04 SENT TO ROB MCDOUGAL DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 15:27 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 15:27 Sent To B
Notes
2004-09-14 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 11:29 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 11:29 Sent To  
Notes
2004-06-15 00:00:00TO COMM BD #28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 10:38 Sent To  
Notes
2004-03-03 00:00:00TO COMM BD#48/ROLLS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2004-09-22 Time 17:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By pkrauss Date 2004-03-29 Time 12:32 Rev Time 0.40
Received By pkrauss Date 2004-03-29 Time 12:32 Sent To  
Notes
2004-03-29 00:00:00DENIED:
 1.PLANS SHALL BE SIGNED WITH ENGINEERS
 ORIGINAL SIGNATURE AND NOT STAMPED PER
 FS 471.025.
  
 2.FIRE DAMPERS INDICATED ON PLAN SHEET
 M-1 UNIT A, RATING APPEARS TO BE AT THE
 WALL AND CEILING, THE WALL DOES NOT
 CONTINUE ABOVE THE CEILING.FIRE DAMPER
 NOT REQUIRED.
  
 3.PLAN SHEET A-21 INDICATES THE
 FLOOR/CEILING AS A 1HR FIRE RATED
 ASSEMBLY.UL LISTING FOR L528 DOES NOT
 INDICATE PENETRATIONS THROUGH RATED
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR PENETRATIONS (DUCT).INDICATE IF
 RADIATION CEILING DAMPERS ARE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-06-04 Cont ID  
Sent By jleech Date 2005-06-04 Time 08:50 Rev Time 0.33
Received By jleech Date 2005-06-04 Time 08:50 Sent To  
Notes
2005-06-04 00:00:00REVISION;
 ADD WATER METER TO PLAN

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-03-26 Cont ID  
Sent By jleech Date 2005-03-26 Time 12:24 Rev Time 0.50
Received By jleech Date 2005-03-26 Time 12:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2004-09-22 Time 17:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-06-29 Cont ID  
Sent By kstevens Date 2004-06-29 Time 13:17 Rev Time 0.50
Received By kstevens Date 2004-06-29 Time 13:17 Sent To  
Notes
2004-06-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEWS HAVE
 NOT BEEN ADDRESSED PROPERLY. COMMENT
 NUMBER TO STAY THE SAME TO AVOID CONFUS-
 ION.
 3) SHT A-15 GRAB BAR BLOCKING DETAILS
 SHALL REFLECT BACKING IN CHAPTER 6 OF
 THE FHA DESIGN MANUAL. - RESPONSE NOTED
 BUT ONLY THE MEASUREMENTS FOR THE GRAB
 BARS ARE SHOWN. NO MEASUREMENTS FOR THE
 BACKING IS SHOWN. PLEASE SEE DESIGN MAN-
 UAL FOR BACKING FOR THE GRAB BARS FOR
 THE W/C'S AND SHOWERS.
 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME
 ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY
 THIS REQUIREMENT. FAC 61G15-23.002(2)
 AND FS 471.025.
 ***************NEW COMMENTS*************
 1C) SHT P-1 DOMESTIC WATER SUPPLY DETAIL
 SHOWS THE WATER SUPPLY UNDER THE SLAB &
 SHOWS AN ADAPTOR FROM PVC TO COPPER.
 SUBMIT A DETAIL SHOWING TYPE OF FITTING
 AND MANUF. SPECIFICATION SHOWING APPROV-
 AL FOR UNDER SLAB INSTALLATION FOR THE
 ADAPTOR. SECTION 104.2.1
 2C) SHP P-1 SHOWS MAIN SHUTOFF VALVE IN-
 SIDE THE GARAGE, BUT PLUMBING GENERAL
 NOTES #13 INDICATES THAT VALVE SHALL BE
 LOCATED OUTSIDE OF THE BUILDING. PLEASE
 CLARIFY AND CORRELATE PLANS AND NOTES.
 SECTION 104.2.1
 3C) SHT P-1 PLUMBING GENERAL NOTES #19
 HAS BEEN DELETED WITH WHITE-OUT. THIS IS
 NOT APPROVED. PLEASE DELETE NOTE ON PLAN
 PROPERLY. SECTION 104.2.1.3
 4C) SEE ATTACHED SHEET IN REFERENCE TO
 FS 553.80(2)(B). FOUT TIMES THE FEE FOR
 THE PLAN REVIEW PORTION OF THE PERMIT
 SHALL BE IMPOSED IF THE SAME COMMENTS
 ARE NOT ADDRESSED PER FLA. STATUTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-03-15 Time 12:46 Rev Time 0.50
Received By kstevens Date 2004-03-15 Time 12:46 Sent To  
Notes
2004-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED. COMMENT NUMBER TO STAY THE
 SAME AS FIRST REVIEW TO AVOID CONFUSION.
 1) INDICATE SPECIFICATION "A" OR "B" AS
 REQUIRED IN FHA DESIGN MANUAL REQUIRE-
 MENT 7B PAGES 7.34 & 7.35. - RESPONSE
 NOTED, BUT SPECIFICATION NOT FOUND ON
 SHEET A-3 AS INDICATED.
 2) SHOW LAV HEIGHT PER FHA DESIGN MANUAL
 PAGE 9512 SECTION "V". RESPONSE NOTED,
 BUT 36" IS INCORRECT. 34" IS MAX. HEIGHT
 3) SHT A-15 GRAB BAR BLOCKING DETAILS
 SHALL REFLECT BACKING IN CHAPTER 6 OF
 THE FHA DESIGN MANUAL. - RESPONSE NOTED,
 BUT SHEET A-19 DETAIL DOES NOT REFLECT
 THE DESIGN MANUAL REQUIREMENTS.
 4) A SANITARY AND A WATER RISER DIAGRAM
 ARE REQURED PER SECTION 104.3.1.1. - RE-
 SPONSE NOTED, BUT NO WATER RISER DIAGRAM
 HAS BEEN SUBMITTED,
 8) PLANS HAVE STAMPED WITH A SIGNATURE
 STAMP. A WET SIGNATURE IS REQUIRED ON
 THE SEAL. NO CERTIFICATE OF AUTHORIZAT-
 ION IS SHOWN ON THE TITLE BLOCK.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 ***************NEW COMMENT**************
 1B) CLEAR FLOOR SPACE SHALL BE APPLIED
 OR SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE RE-
 QUIREMENTS ARE BEING MET. PAGE 7.43 OF
 THE DESIGN MANUAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-07-21 Cont ID  
Sent By mmclean Date 2004-07-21 Time 16:12 Rev Time 0.00
Received By mmclean Date 2004-07-21 Time 16:12 Sent To  
Notes
2004-07-21 00:00:00APPROVED BY ERIC SCHNEIDER, SENIOR
 PLANNER 659-8031

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By sgraham Date 2004-03-22 Time 11:29 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2004-03-22 00:00:001. NEED SITE & LANDSCAPE PLANS
 2. AREA TABULATION INCORRECT
 UNIT#2 TOTAL A/C
 UNIT#3 TOTAL A/C & UNIT TOTAL
 3. BUILDING LARGER THAN ORIGINALLY
 APPROVED-SETBACKS MUIST BE MET ON
 SITE PLAN.
 4. SHEET A-6 INCORRECT SCALE SHOWN.
 5. MUST SHOW BUILDING HEIGHT MEETS CODE
 REQUIREMENT ON ELEVATIONS SHEETS
 A-7,A-8