Plan Review Details - Permit 04021355
Plan Review Stops For Permit 04021355
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-04-22 Cont ID  
Sent By rmcdouga Date 2005-04-22 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2005-04-22 Time 07:10 Sent To  
Notes
2005-04-22 00:00:00REVISED ROOF SHINGLES TO CERTAINTEED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2005-03-08 Cont ID  
Sent By rmcdouga Date 2005-03-08 Time 15:19 Rev Time 0.00
Received By rmcdouga Date 2005-03-08 Time 15:19 Sent To  
Notes
2005-03-08 00:00:00SLAB AND FILLED CELL COMPRESSION TESTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 18:06 Rev Time 2.00
Received By rmcdouga Date 2004-09-22 Time 18:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-29 Cont ID  
Sent By csiegber Date 2004-09-14 Time 15:27 Rev Time 2.00
Received By jwitmer Date 2004-06-29 Time 12:51 Sent To  
Notes
2004-06-29 00:00:00BUILDING PLAN REVIEW
 PERMIT:04021355
 ADD: 1770 MISSION COURT
 CONT: WCI
 TEL: (561)951-2226
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) RE-RECORD NOC WITH THE CORRECT PCN.
  
 2) PROVISO: WILL REQUIRE THE HR. RATING
 INFO FOR THE FIRE REATED GLASS BLOCK.
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By jwitmer Date 2004-03-23 Time 08:18 Rev Time 5.50
Received By jwitmer Date 2004-03-23 Time 08:18 Sent To  
Notes
2004-03-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021355
 ADD: 1770MISSION COURT
 CONT: WCI COMMUNITIES
 TEL: (561)775-2120
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST PERMIT REVIEW
 PLAN REVIEW: 04010005
  
 ACTION: DENIED
  
 NOTE: A SIGNED & SEALED LETTER FROM THE
 ARCHITECT OF RECORD INDICATING THE PLANS
 SUBMITTED ARE OCCUPANCY TYPE: (R2).
 WITH THE PLANS STATING "TOWNHOUSE" AS
 PART OF THE NAME IT IS TO BE MADE CLEAR
 THAT ALL DOCUMENTS INCLUDING THE SOILS
 REPORTS SHOULD NOT STATE TOWNHOMES.
 FOR THESE UNITS TO BE SOLD AS CONDOMIN
 IUMS A RECORDED DECLARATION OF CONDOMIN-
 IUM SHALL BE REQUIRED BEFORE A CERTIFI-
 CATE OF OCCUPANCY WILL BE ISSUED.
  
 1) 105.3 CITY ADMINISTRATIVE CODE,
 RESIDENT INSPECTOR TO BE REQUIRED.
 CONTACT HAROLD PISKURA)@ 805-6711 FOR
 MORE INFORMATION AS TO THE REQUIREMENTS
 OF COMPLETED UNITS VS CONSTRUCTION AREAS
 REQUIRED STRUCTURAL INSPECTIONS AND
 PHASING.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 2ND REQUEST!!!!!!!!!!!!!!!!!
 A SITE PLAN INDICATING ALL SITE AMENIT-
 IES WITH DIMENSIONS BETWEEN BUILDINGS
 INDICATING THE ASSUMED PROPERTY LINE
 BETWEEN BUILDINGS, TO CALCULATE ALLOW-
 ABLE OPENING SIZES TABLE 600. UNABLE TO
 VARIFY COMPLIANCE WITH TABLE 600.
 " 2ND REQUEST". HIGHLIGHT WHICH BUILDING
 IS PERMITTED UNDER THIS PERMIT!
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 2ND REQUEST, THE SOILS REPORT
 PROVIDED IS NOT THE ORIGINAL RAISED SEAL
 WITH ORIGINAL SIGNATURE.
  
 4)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 5) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 2ND REQUEST!!!!!!!!
  
 6)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) FAIR HOUSING, 1. ACCESSIBLE ROUTE,
 INDICATE ON THE SITE PLAN, THE ACCESS-
 IBLE ROUTE TO ALL ELEMENTS, INCLUDING
 THE CLUBHOUSE,GAZEBOES,DUMPSTER, POOLS,
 PARKING AND PATH OF TRAVEL TO PUBLIC
 TRANSPORTATION.
  
 8) SHEET A-11 TYP 2 STORY DETAIL AT THE
 GARAGE MISSING FLOOR INSULATION OVER THE
 GARAGE. SEPERATION OF A/C VS NON.
 2ND REQUEST!!!!!!!!
  
 9) SHEET A-11 SECTION 3 & 4 INDICATE THE
 USE OF WIRE LATH ON THE SOFFIT, ADD INFO
 REQUIRED FOR INSTALLATION. I PROVIDED
 THE CODE ARTICLE FOR THE FASTENING TO
 HORIZONTAL FRAMING MEMBERS( 2504.2.2)
 FOR A REFRENCE ONLY PLEASE INDICATE
 FASTENING ON PLAN.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 10) FLORIDA STATEWIDE PRODUCT APPROVALS:
 A COVERSHEET FOR EACH PRODUCT APPROVAL
 SUBMITTED WAS PULLED FROM THE WEBSITE,
 COPY AND PROVIDE WITH EVERY PRODUCT
 APRROVAL SUBMITTED!!!!!!!!!!!!!!!!!!!
  
 11) PRODUCT APPROVALS SUBMITTED:
 AMARR GARAGE DOORS, SEE TABLE 1606.2B
 COMPONENTS & CLADDING WIND LOADS FOR A
 BUILDING WITH A MEAN ROOF HEIGHT OF <
 30' LOCATED IN EXPOSURE "B"
  
 BOTH THE 9' & 16' DOORS OK FOR 2STORY
 USE!!!!!!! LOW PRESSURE FOR 3 STORY USE
 WITH 1.09 MULTIPLIER 1606.2 D & E.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2ND REQUEST FOR PRODUCT TESTING REPORTS
 FOR THE (G) STRUCTURAL COMPONENTS-
 WOOD CONNECTORS!!!!!!!!!!!!!!!
  
 13) 2ND REQUEST!!!!PROVIDE THE TRUSS
 ENGINEERING SHEETS WITH ALL LOADING
 CASES, VERTICAL, HORIZONTAL & GRAVITY
 LOADS. PLANS DO NOT INDICATE LOADING,
 ONLY THE ALLOWABLE VALUES FOR THE ANCHOR
  
 14) 2ND REQUEST: NOT ADDRESSED,
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 15) 2ND REQUEST: GARAGE SWING DOOR,
 NOT LISTED ON DOOR SCHEDULE, A 3/4 HR
 RATING IS REQUIRED 411.2.6, 705.1.3.5,
 DOOR SHALL BE EQUIPPED WITH AN APPROVED
 CLOSER.
 A) THE FLORIDA BUILDING CODE UNDER
 THE ABOVE CODE ARTICLES DOES NOT INDI-
 CATE A "C" LABELED DOOR, IT IS A 45 MIN
 DOOR.
 B) PROVIDE THE CLOSER INFORMATION
 REQUIRED.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-24 Cont ID  
Sent By dpalmer Date 2005-03-24 Time 10:32 Rev Time 0.25
Received By dpalmer Date 2005-03-24 Time 10:32 Sent To  
Notes
2005-03-24 00:00:00FEEDERS REVISED TO SHOW SE CABLE,
 HOWEVER PLANS/RISER STILLS SHOWS BEING
 INSTALLED IN CONDUIT. CALLED ELECTRICAL
 ENGINEER,CONDUIT IS NOT BEING USED. THIS
 IS A MISPRINT ON PLANS.
 CONDUIT CROSSED OUT ON PLANS PER
 ENGINEER'S REQUEST.
  
  
 WASHER VA REDLINED, SHOULD BE 1500VA
 220.16
  
 IF PLANS ARE REVISED FOR ANY FUTURE
 ITEMS, PLEASE ADJUST THE ABOVE AT THAT
 TIME.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 18:07 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2004-09-22 00:00:00PASSED UNDER MASTER# 04010005

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-14 Cont ID  
Sent By btrobaug Date 2004-07-14 Time 09:40 Rev Time 0.50
Received By btrobaug Date 2004-07-09 Time 07:00 Sent To  
Notes
2004-07-14 00:00:00 
 PLEASE SEE PERMIT # 04021345 FOR COMMENT
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 17:57 Rev Time 1.00
Received By btrobaug Date 2004-04-05 Time 17:39 Sent To  
Notes
2004-04-05 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER SHOWS A MAIN DISCONNECT,
 THE DRAWING SHOWS METERS AND
 DICONNECTS. PLEASE CORRELATE.
  
 2} INDICATE THE SIZE OF THE EQ. GND WITH
 THE FEEDERS ON THE RISER.
  
 3} THE LAUNDRY CIRCUIT CALCULATION MUST
 COMPLY WITH 220.116(B).(1500 VA).
  
 4} PLEASE LABEL THE ROOMS ON THE ELECTR
 ICAL PLANS TO CORRESPOND TO THE ARCHITEC
 TURAL PLANS.
  
 5} THE PANEL SCHEDULE REFERS TO "LIVING/
 BREAKFAST" ROOM.THE "BREAKFAST" ROOM
 MUST COMPLY WITH 210.52(B),20 AMP CIRC.
  
 6} PLEASE NOTE SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 7} THE CALCULATION FOR "OUTLETS 1X.....)
 IS ONLY USED FOR OFFICE BUILDINGS AND
 BANKS. SEE "B"NOTE AT BOTTOM OF TABLE.
  
 10} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE
 STAMPS ARE NOT ACCEPTABLE PER F.B.P.E.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-12 Cont ID  
Sent By mamini Date 2004-04-12 Time 14:44 Rev Time 1.00
Received By mamini Date 2004-04-12 Time 14:44 Sent To  
Notes
2004-04-12 00:00:00PASSED :
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-08 Cont ID  
Sent By mamini Date 2004-03-08 Time 16:11 Rev Time 0.50
Received By mamini Date 2004-03-08 Time 16:11 Sent To  
Notes
2004-03-08 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS FOR
 PERMITTING, NOTE THAT CIVIL PLANS WERE
 REVIEWED UNDER #03101412 (PLAN REVIEW),
 AT YOUR OPTION UNDERGROUND UTILITIES &
 SITE WORK COULD BE UNDER SEPARATE PERMIT
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-08-23 Cont ID  
Sent By nmccray Date 2004-08-23 Time 14:15 Rev Time 0.00
Received By nmccray Date 2004-08-23 Time 14:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2004-07-20 Cont ID  
Sent By nmccray Date 2004-07-20 Time 09:42 Rev Time 0.00
Received By nmccray Date 2004-07-20 Time 09:42 Sent To  
Notes
2004-07-20 00:00:00*************DENIED*********************
 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE AND ACCESSIBLE ROADS ARE
 REQUIRED FOR FIRE AND PARAMEDICAL
 EQUIPMENT.
  
 THESE NOTES AND COMMENTS ARE ALSO FOR
 PERMITS: 04021353, 04021345, 04021359
 04021357, 04021368
  
 NATE MCCRAY, CAPTAIN
 561-835-2910 OR 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-04-07 Cont ID  
Sent By mcarsill Date 2004-04-07 Time 13:54 Rev Time 0.00
Received By mcarsill Date 2004-04-07 Time 13:54 Sent To  
Notes
2004-04-07 00:00:00PLEASE SEE PREVIOUS PLAN REVIEW
 COMMENTS FOR THE OTHER BUILDINGS
 PLANNED FOR THE SITE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-13 Cont ID  
Sent By adarroug Date 2005-05-13 Time 13:07 Rev Time 0.00
Received By adarroug Date 2005-05-13 Time 13:07 Sent To M
Notes
2005-05-13 00:00:00TO "PKRAUSS" BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-13 Cont ID  
Sent By adarroug Date 2005-04-13 Time 10:16 Rev Time 0.00
Received By adarroug Date 2005-04-13 Time 10:16 Sent To B
Notes
2005-04-13 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 13:47 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 13:47 Sent To  
Notes
2005-03-11 00:00:00TO "COMM" BD#24/PLANS ON SFR

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 15:27 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 15:27 Sent To B
Notes
2004-09-14 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 11:32 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 11:31 Sent To  
Notes
2004-06-15 00:00:00TO COMM BD #28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-07 Cont ID  
Sent By csiegber Date 2004-06-07 Time 16:39 Rev Time 0.00
Received By csiegber Date 2004-06-07 Time 16:39 Sent To  
Notes
2004-06-07 00:00:00TO COMM BD#28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-05-10 Time 10:07 Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 10:36 Sent To  
Notes
2004-03-03 00:00:00TO COMM BD#48/ROLLS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2005-03-26 Time   Rev Time 0.00
Received By hmoser Date 2005-03-26 Time 12:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-02 Cont ID  
Sent By pkrauss Date 2004-07-02 Time 14:55 Rev Time 0.35
Received By pkrauss Date 2004-07-02 Time 14:09 Sent To  
Notes
2004-07-02 00:00:00MASTER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2004-05-14 Cont ID  
Sent By pkrauss Date 2004-05-14 Time 16:49 Rev Time 0.15
Received By pkrauss Date 2004-05-14 Time 16:49 Sent To  
Notes
2004-05-14 00:00:00PER MTG 5-14-04 COMMENTS ADDRESSED
 PLANS OKAY

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By pkrauss Date 2004-03-29 Time 11:26 Rev Time 0.55
Received By pkrauss Date 2004-03-29 Time 11:01 Sent To  
Notes
2004-03-29 00:00:00DENIED:
 1.PLANS SHALL BE SIGNED WITH ENGINEERS
 ORIGINAL SIGNATURE AND NOT STAMPED
 PER FS 471.025.
  
 2.FIRE DAMPERS INDICATED ON PLAN SHEET
 M-1 UNIT A, RATING APPEARS TO BE AT THE
 WALL AND CEILING, THE WALL DOES NOT
 CONTINUE ABOVE THE CEILING.FIRE DAMPER
 NOT REQUIRED.
  
 3.PLAN SHEET A-21 INDICATES THE
 FLOOR/CEILING AS A 1HR FIRE RATED
 ASSEMBLY.UL LISTING FOR L528 DOES NOT
 INDICATE PENETRATIONS THROUGH RATED
 ASSEMBLY.PLEASE PROVIDE UL LISTING
 FOR PENETRATIONS.PLEASE INDICATE IF
 RADIATION/CEILING DAMPERS ARE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-06-04 Cont ID  
Sent By jleech Date 2005-06-04 Time 07:57 Rev Time 0.33
Received By jleech Date 2005-06-04 Time 07:57 Sent To  
Notes
2005-06-04 00:00:00REVISION;
 ADD WATER METER TO PLANS

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-03-26 Cont ID  
Sent By jleech Date 2005-03-26 Time 13:14 Rev Time 0.33
Received By jleech Date 2005-03-26 Time 13:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-09-22 Cont ID  
Sent By rmcdouga Date 2004-09-22 Time 18:08 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-08-19 Cont ID  
Sent By kstevens Date 2004-08-19 Time 08:51 Rev Time 2.50
Received By kstevens Date 2004-08-19 Time 08:51 Sent To  
Notes
2004-08-19 00:00:00DENIED
 REFERRENCE: FBC-2001 PLUMBING
  
 1) SHT P-1 DOMESTIC WATER SUPPLY DETAIL
 SHOWS THE WATER SUPPLY UNDER THE SLAB &
 SHOWS AN ADAPTOR FROM PVC TO CPVC. SUB-
 MANUFACTURERS SPECIFICATION FOR ADAPTOR
 SHOWING APPROVAL FOR UNDER SLAB INSTALL-
 ATION. SECTION 605.22.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-06-29 Cont ID  
Sent By kstevens Date 2004-06-29 Time 10:56 Rev Time 1.50
Received By kstevens Date 2004-06-29 Time 10:56 Sent To  
Notes
2004-06-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEWS HAVE
 NOT BEEN ADDRESSED PROPERLY. COMMENT
 NUMBER TO STAY THE SAME TO AVOID CONFUS-
 ION.
 3) SHT A-15 GRAB BAR BLOCKING DETAILS
 SHALL REFLECT BACKING IN CHAPTER 6 OF
 THE FHA DESIGN MANUAL. - RESPONSE NOTED
 BUT ONLY THE MEASUREMENTS FOR THE GRAB
 BARS ARE SHOWN. NO MEASUREMENTS FOR THE
 BACKING IS SHOWN. PLEASE SEE DESIGN MAN-
 UAL FOR BACKING FOR THE GRAB BARS FOR
 THE W/C'S AND SHOWERS.
 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME
 ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY
 THIS REQUIREMENT. FAC 61G15-23.002(2)
 AND FS 471.025.
 ***************NEW COMMENTS*************
 1C) SHT P-1 DOMESTIC WATER SUPPLY DETAIL
 SHOWS THE WATER SUPPLY UNDER THE SLAB &
 SHOWS AN ADAPTOR FROM PVC TO COPPER.
 SUBMIT A DETAIL SHOWING TYPE OF FITTING
 AND MANUF. SPECIFICATION SHOWING APPROV-
 AL FOR UNDER SLAB INSTALLATION FOR THE
 ADAPTOR. SECTION 104.2.1
 2C) SHP P-1 SHOWS MAIN SHUTOFF VALVE IN-
 SIDE THE GARAGE, BUT PLUMBING GENERAL
 NOTES #13 INDICATES THAT VALVE SHALL BE
 LOCATED OUTSIDE OF THE BUILDING. PLEASE
 CLARIFY AND CORRELATE PLANS AND NOTES.
 SECTION 104.2.1
 3C) SHT P-1 PLUMBING GENERAL NOTES #19
 HAS BEEN DELETED WITH WHITE-OUT. THIS IS
 NOT APPROVED. PLEASE DELETE NOTE ON PLAN
 PROPERLY. SECTION 104.2.1.3
 4C) SEE ATTACHED SHEET IN REFERENCE TO
 FS 553.80(2)(B). FOUT TIMES THE FEE FOR
 THE PLAN REVIEW PORTION OF THE PERMIT
 SHALL BE IMPOSED IF THE SAME COMMENTS
 ARE NOT ADDRESSED PER FLA. STATUTE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-03-15 Time 12:33 Rev Time 0.50
Received By kstevens Date 2004-03-15 Time 12:33 Sent To  
Notes
2004-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEW NOT
 ADDRESSED. COMMENT NUMBER TO STAY THE
 SAME AS FIRST REVIEW TO AVOID CONFUSION.
 1) INDICATE SPECIFICATION "A" OR "B" AS
 REQUIRED IN FHA DESIGN MANUAL REQUIRE-
 MENT 7B PAGES 7.34 & 7.35. - RESPONSE
 NOTED, BUT SPECIFICATION NOT FOUND ON
 SHEET A-3 AS INDICATED.
 2) SHOW LAV HEIGHT PER FHA DESIGN MANUAL
 PAGE 9512 SECTION "V". RESPONSE NOTED,
 BUT 36" IS INCORRECT. 34" IS MAX. HEIGHT
 3) SHT A-15 GRAB BAR BLOCKING DETAILS
 SHALL REFLECT BACKING IN CHAPTER 6 OF
 THE FHA DESIGN MANUAL. - RESPONSE NOTED,
 BUT SHEET A-19 DETAIL DOES NOT REFLECT
 THE DESIGN MANUAL REQUIREMENTS.
 4) A SANITARY AND A WATER RISER DIAGRAM
 ARE REQURED PER SECTION 104.3.1.1. - RE-
 SPONSE NOTED, BUT NO WATER RISER DIAGRAM
 HAS BEEN SUBMITTED,
 8) PLANS HAVE STAMPED WITH A SIGNATURE
 STAMP. A WET SIGNATURE IS REQUIRED ON
 THE SEAL. NO CERTIFICATE OF AUTHORIZAT-
 ION IS SHOWN ON THE TITLE BLOCK.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 ****************NEW COMMENTS************
 1B) CLEAR FLOOR SPACE SHALL BE APPLIED
 OR SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE RE_
 QUIREMENTS ARE BEING MET. PAGE 7.43 OF
 THE DESIGN MANUAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-07-21 Cont ID  
Sent By mmclean Date 2004-07-21 Time 16:11 Rev Time 0.00
Received By mmclean Date 2004-07-21 Time 16:11 Sent To  
Notes
2004-07-21 00:00:00APPROVED BY ERIC SCHNEIDER, SENIOR
 PLANNER 659-8031

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By sgraham Date 2004-03-22 Time 10:17 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2004-03-22 00:00:001. NEED SITE & LANDSCAPE PLANS
 2. AREA TABULATION INCORRECT
 UNIT#2 TOTAL A/C
 UNIT#3 TOTAL A/C & UNIT TOTAL
 3. BUILDING LARGER THAN ORIGINALLY
 APPROVED- SETBACKS MUST BE MET ON
 SITE PLAN.
 4. SHEET A-6 INCORRECT SCALE SHOWN.
 5. MUST SHOW BUILDING HEIGHT MEETS CODE
 REQUIREMENTS ON ELEVATIONS SHEETS
 A-7,A-8