Plan Review Details - Permit 04021354
Plan Review Stops For Permit 04021354
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-05-05 Cont ID  
Sent By rmcdouga Date 2005-05-05 Time 14:12 Rev Time 0.00
Received By prafter Date 2005-05-16 Time 08:43 Sent To  
Notes
2005-05-05 00:00:00REVISED ROOF SHINGLES TO CERTAINTEED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-02-10 Cont ID  
Sent By rmcdouga Date 2005-02-10 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2005-02-10 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-31 Cont ID  
Sent By jwitmer Date 2004-03-31 Time 14:50 Rev Time 1.00
Received By jwitmer Date 2004-03-31 Time 14:50 Sent To  
Notes
2004-03-31 00:00:00SEE 04021372 FOR COMMENTS

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-02-10 Cont ID  
Sent By rmcdouga Date 2005-02-10 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2005-02-10 Time 10:59 Sent To  
Notes
2005-02-10 00:00:00PASSED UNDER MASTER # 04010007

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-07-15 Cont ID  
Sent By btrobaug Date 2004-07-15 Time 10:04 Rev Time 0.50
Received By btrobaug Date 2004-07-15 Time 10:04 Sent To  
Notes
2004-07-15 00:00:00 
 SEE COMMENTS FOR #04021350.
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By btrobaug Date 2004-04-05 Time 13:22 Rev Time 0.50
Received By btrobaug Date 2004-04-05 Time 13:22 Sent To  
Notes
2004-04-05 00:00:00 
 PLEASE SEE COMMENTS PERMIT #04021372.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-12 Cont ID  
Sent By mamini Date 2004-04-12 Time 14:07 Rev Time 1.00
Received By mamini Date 2004-04-12 Time 14:07 Sent To  
Notes
2004-04-12 00:00:00PASSED :
 1. SEE # 03101412 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By mamini Date 2004-03-09 Time 08:55 Rev Time 0.50
Received By mamini Date 2004-03-09 Time 08:55 Sent To  
Notes
2004-03-09 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL PLANS FOR
 PERMITTING, NOTE THAT CIVIL PLANS WERE
 REVIEWED UNDER #03101412 (PLAN REVIEW),
 AT YOUR OPTION UNDERGROUND UTILITIES &
 SITE WORK COULD BE UNDER SEPARATE PERMIT
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-02-10 Cont ID  
Sent By rmcdouga Date 2005-02-10 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2005-02-10 Time 10:58 Sent To  
Notes
2005-02-10 00:00:00PASSED UNDER MASTER #04010007

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-07-20 Cont ID  
Sent By nmccray Date 2004-07-20 Time 16:31 Rev Time 0.00
Received By nmccray Date 2004-07-20 Time 16:31 Sent To  
Notes
2004-07-20 00:00:00SEE COMMENTS ON PERMIT 04021372
 SEE COMMENTS ON PERMIT 04021372
  
 NATE MCCRAY
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-05-27 Cont ID  
Sent By adarroug Date 2005-05-27 Time 11:26 Rev Time 0.00
Received By adarroug Date 2005-05-27 Time 11:25 Sent To P
Notes
2005-05-27 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 13:09 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 13:09 Sent To M
Notes
2005-05-03 00:00:00TO "PKRAUSS" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-04-22 Cont ID  
Sent By adarroug Date 2005-04-22 Time 16:18 Rev Time 0.00
Received By adarroug Date 2005-04-22 Time 16:18 Sent To B
Notes
2005-04-22 00:00:00TO "RMCDOUGAL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-03-11 Cont ID  
Sent By adarroug Date 2005-03-11 Time 13:17 Rev Time 0.00
Received By adarroug Date 2005-03-11 Time 13:17 Sent To P
Notes
2005-03-11 00:00:00TO "KSTEVENS" BOX(SFR)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-15 Cont ID  
Sent By mjacobs Date 2004-06-15 Time 11:06 Rev Time 0.00
Received By mjacobs Date 2004-06-15 Time 11:05 Sent To  
Notes
2004-06-15 00:00:00TO COMM BD #28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-02-10 Cont ID  
Sent By rmcdouga Date 2004-03-31 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2004-03-03 Time 10:42 Sent To  
Notes
2004-03-03 00:00:00TO COMM BD#48/ROLLS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-05-13 Cont ID  
Sent By prafter Date 2005-05-13 Time 10:51 Rev Time 0.50
Received By prafter Date 2005-05-13 Time 10:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-02-10 Cont ID  
Sent By rmcdouga Date 2005-02-10 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2005-02-10 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By pkrauss Date 2004-03-29 Time 08:58 Rev Time 0.40
Received By pkrauss Date 2004-03-29 Time 08:58 Sent To  
Notes
2004-03-29 00:00:00DENIED:
 1.PLAN SHEET A-21 DETAIL 2, INDICATES
 A 1HR FIRE RATED FLOOR/CEILING ASSEMBLY.
 PLEASE PROVIDE UL LISTING FOR
 PENETRATIONS THROUGH THE MEMBRANE AT
 EACH GRILLE.PLEASE CLARIFY.
  
 2.PLEASE NOTE, A SHAFT ENCLOSURE IS
 NOT REQUIRED PER 2001 FBC 705.2.2,
 FIRE DAMPER NOT REQUIRED.
  
 3.PLAN SHEET M-1 UNIT C, O.A. APPEARS
 TO BE LOCATED IN THE GARAGE.FRESH AIR
 INTAKES SHALL BE LOCATED AS NOT TO
 CIRCULATE CARBON MONOXIDE INTO HVAC
 SYSTEM.PLEASE ADVISE.
  
 4.PLAN SHEET M-2 UNIT 2L & 2R RETURN
 AIR JUMPER NOT SIZED PROPERLY(MASTR BRM)
 RETURN SHALL BE A MINIMUM OF 14".THE
 TOTAL SUPPLY AIR INTO MASTER SUITE SHALL
 BE USED WHEN SIZING THE RETURN FOR THE
 MASTER SUITE.REVISED 2001 FBC(M)
 601.4 EXCEPTION #1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-06-13 Cont ID  
Sent By jleech Date 2005-06-13 Time 14:35 Rev Time 0.33
Received By jleech Date 2005-06-13 Time 14:35 Sent To  
Notes
2005-06-13 00:00:00WATER METERS ADDED TO EACH UNIT

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-10 Cont ID  
Sent By rmcdouga Date 2005-02-10 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2005-02-10 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-07-19 Cont ID  
Sent By kstevens Date 2004-07-19 Time 17:56 Rev Time 0.25
Received By kstevens Date 2004-07-19 Time 17:56 Sent To  
Notes
2004-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A) COMMENTS FROM PREVIOUS REVIEWS HAVE
 NOT BEEN ADDRESSED PROPERLY. COMMENT
 NUMBER TO STAY THE SAME TO AVOID CONFUS-
 ION.
 8)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS SHALL LEGIBLY INDICATE THEIR NAME
 AND LICENSE NUMBER, AS WELL AS, THE NAME
 ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY
 THIS REQUIREMENT. FAC 61G15-23.002(2)
 AND FS 471.025.
 ***************NEW COMMENTS*************
 1C) SHT P-1 DOMESTIC WATER SUPPLY DETAIL
 SHOWS THE WATER SUPPLY UNDER THE SLAB &
 SHOWS AN ADAPTOR FROM PVC TO COPPER.
 SUBMIT A DETAIL SHOWING TYPE OF FITTING
 AND MANUF. SPECIFICATION SHOWING APPROV-
 AL FOR UNDER SLAB INSTALLATION FOR THE
 ADAPTOR. SECTION 104.2.1
 2C) SHP P-1 SHOWS MAIN SHUTOFF VALVE IN-
 SIDE THE GARAGE, BUT PLUMBING GENERAL
 NOTES #13 INDICATES THAT VALVE SHALL BE
 LOCATED OUTSIDE OF THE BUILDING. PLEASE
 CLARIFY AND CORRELATE PLANS AND NOTES.
 SECTION 104.2.1
 3C) SHT P-1 PLUMBING GENERAL NOTES #19
 HAS BEEN DELETED WITH WHITE-OUT. THIS IS
 NOT APPROVED. PLEASE DELETE NOTE ON PLAN
 PROPERLY. SECTION 104.2.1.3
 4C) SEE ATTACHED SHEET IN REFERENCE TO
 FS 553.80(2)(B). FOUR TIMES THE FEE FOR
 THE PLAN REVIEW PORTION OF THE PERMIT
 SHALL BE IMPOSED IF THE SAME COMMENTS
 ARE NOT ADDRESSED PER FLA. STATUTE.
 ***WITH COMMENTS ATTACHED TO #04021372**
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By kstevens Date 2004-03-15 Time 15:55 Rev Time 0.50
Received By kstevens Date 2004-03-15 Time 15:55 Sent To  
Notes
2004-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A WATER RISER DIAGRAM IS REQUIRED FOR
 ALL UNIT TYPES. SECTION 104.3.1.1
 2) SHTS P-1, P-2 & P-3 SIGNATURE REQD ON
 SEAL, SIGNATURE STAMP NOT ACCEPTABLE.
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-07-21 Cont ID  
Sent By mmclean Date 2004-07-21 Time 16:53 Rev Time 0.00
Received By mmclean Date 2004-07-21 Time 16:53 Sent To  
Notes
2004-07-21 00:00:00APPROVED BY ERIC SCHNEIDER, SENIOR
 PLANNER 659-8031

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By sgraham Date 2004-03-22 Time 09:08 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2004-03-22 00:00:001. NO SITE & LANDSCAPE PLANS INCLUDED.
 2. MUST SHOW BUILDING HEIGHT MEETS CODE
 REQUIREMENTS ON ELEVATIONS SHEETS
 A-9,A-10,A-11,A-12