Plan Review Details - Permit 04021300
Plan Review Stops For Permit 04021300
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-05-24 Cont ID  
Sent By jwitmer Date 2004-05-24 Time 15:03 Rev Time 5.00
Received By jwitmer Date 2004-05-24 Time 15:03 Sent To  
Notes
2004-05-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021300
 ADD: N. CONGRESSBLDG# 1
 CONT:CONTEUVEST CONST
 TEL: (407)509-9707
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 PLANS ARE INCOMPLETE TO DO A THROUGH
 REVIEW. THE PLANS DO NOT INDICATE THE
 4 HR FIREWALL SEPERATING BUILDINGS
 LARGER THAN ALLOWED BY TABLE 500. THIS
 PLAN ALSO IS OVER THE ALLOWABLE HEIGHT
 IN TABLE 500. THE PHASING OF THE BUILD-
 ING # 1 IS MISSING STAIRWELLS FOR 1/3RD
 THE DIAGONAL. PLANS ARE MISSING ENCLOSUR
 ES ON VARIOUS STAIRWELLS. STRUCTURAL
 PLANS DO NOT GIVE STRUCTURAL DIMENSIONS.
  
  
 FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-05-04 Cont ID  
Sent By dpalmer Date 2004-05-04 Time 19:56 Rev Time 2.00
Received By dpalmer Date 2004-05-04 Time 19:53 Sent To  
Notes
2004-05-04 00:00:00*** IN FOR REVIEW ***
 SEE NOTES TO FOLLOW.
 PLANS SUBMITTED 2/26
 ************ UNSAT ****************
  
 1)NOTE: PLEASE PROVIDE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH WITH THE
 SUBMITTED PANEL SCHEDULES FOR UNITS.
 PLEASE SHOW ALL MIN CIRCUITS PER 2002
 NEC. UNABLE TO VERIFY AT THIS TIME.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING EM LTS. CLUBHOUSE?
  
 3)NOTE: PLEASE SEE BLDG ONE.
 MAINS TO BE GROUPED, 230.72
  
 4)NOTE: PLEASE SEE OTHER BLDGS, SOME
 SHOW ELECTRICAL ROOMS, OTHERS DO NOT.
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING FOR
 BLDG/HOUSE POWER. PLANS ALSO NOT
 COMPLETED FOR REVIEW OF CODE COMPLIANCE.
  
 6)NOTE: PLEASE CORRELATE OCP FOR APT
 UNIT FEEDERS. ALL SHOWN AT 125A'S YET
 SOME FEEDERS ARE ONLY RATED FOR 100A'S?
  
 7)NOTE: PLEASE SEE RISER, NOTHING IS
 SHOWN FOR FIRE PUMP WHICH IS SHOWN FOR
 BLDG ONE??? PLEASE SEE 695.4B1
 230.72,230.70,230.76,230.79 ETC
 PLEASE SUBMIT SPECS FOR FIRE PUMP,
 FIRE PUMP CONTROLLER. WILL THERE BE A
 GENERATOR?
  
 8)NOTE: PLEASE SEE 250.50 FOR ALL REQ'D
 ATTACHMENTS FOR GE SYSTEM.
 FOOTER STEEL.
  
 9)NOTE: PLEASE SEE ONLY 3 PERMITS WERE
 APPLIED FOR AND PLANS SHOWS 5 BLDGS AND
 CLUBHOUSE??
  
 10)NOTE: PLEASE SEE NOTE ON E16.26,
 MENTIONS ARC FAULT PROETCTION FOR
 BEDROOM RECEPTS. PLEASE SEE 2002 NEC
 THIS IS REQ'D FOR ALL OUTLETS, INCLUDING
 LTS/ SD'S.
  
 11)NOTE: PLEASE VERIFY IF SD'S WILL BE
 INSTALLED INSIDE SLEEPING ROOMS OR DOES
 BLDGS MEET THE EXCEPTIONS SET FORTH IN
 NFPA-72, LS 101
  
 ***PLEASE SUBMIT COMPLETED PLANS FOR
 REVIEW FOR CODE COMPLIANCE TO 2002 NEC.
 THERE MAY BE OTHER COMMETS DUE TO PLANS
 NOT BEING COMPLETE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-03-04 Cont ID  
Sent By mamini Date 2004-03-04 Time 14:58 Rev Time 1.00
Received By mamini Date 2004-03-04 Time 14:58 Sent To  
Notes
2004-03-04 00:00:00FAILED:
 1. SEE PERMIT # 04021308 FOR UNDERGROUND
 UTILITIES AND SITE REVIEW COMMENTS.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-05-05 Cont ID  
Sent By mcarsill Date 2004-05-05 Time 12:11 Rev Time 0.00
Received By mcarsill Date 2004-05-05 Time 12:10 Sent To  
Notes
2004-05-05 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) STAIRS ARE REQUIRED TO BE KEPT UP
 WITH CONSTRUCTION.
  
 3) TEMPORARY STANDPIPE SYSTEMS ARE
 REQUIRED WHEN THE BUILDING REACH
 THREE STORIES OR THIRTY FEET IN HEIGHT.
  
 4) TACTILE SIGNAGE REQUIRED AT EXITS.
  
 5) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH
 NFPA 241.
  
 6) THE PHASING PLAN NOTES ARE NOT
 CORRECT. ALL LIFE SAFETY EQUIPMENT AND
 DEVICES MUST BE INSPECTED, TESTED AND
 APPROVED PRIOR TO ANY OCCUPANCY
 BEING PERMITTED IN THE BUILDING. NO
 ELECTRICAL POWER WILL BE GRANTED
 UNTIL THE FIRE SPRINKLER SYSTEM AND
 THE FIRE ALARM SYSTEMS ARE READY.
 THE CITY HAS A POLICY WITH REGARDS TO
 RELEASE OF POWER. PLEASE REVIEW
 POLICY.
  
 7) ELEVATORS MUST BE PRESENT TO BE
 UTILIZED BY RESIDENTS.
  
 8) KNOX-BOXES WILL BE REQUIRED ON
 THE OUTSIDE OF THE BUILDINGS.
  
 9) KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED ON ALL FIRE DEPARTMENT
 CONNECTIONS.
  
 10) PLEASE CLEARLY IDENTIFY ALL
 EXIT STAIRS THAT LEAD DIRECTLY TO
 THE EXTERIOR. ALL EXIT STAIRS CANNOT
 TERMINATE WITHIN THE BUILDING.(S)
  
 11) IF THE BUILDINGS ARE GOING TO
 BE CONSIDERED SEPARATE, THEN ALL FIRE
 SPRINKLER, FIRE ALARM, AND MECHANICAL,
 ELECTRICAL, AND PLUMBING SYSTEMS SHALL
 BE SEPARATE.
  
 12) STAIR # 10 APPEAR TO BE OPEN.
 PLEASE EXPLAIN RATIONALE.
  
 13) TRAVEL DISTANCE NOTES IS INCORRECT.
 THE MAXIMUM TRAVEL DISTANCE IN A
 SPRINKLERED BUILDING FROM AN APARTMENT
 TO AN EXIT SHALL NOT EXCEED 200 FEET.
 OTHER AREAS OF THE BUILDING CAN BE
 MEET 250 FEET. PLEASE ADVISE OR
 REVISE.
  
 14) EXIT SIGN PLACEMENT CANNOT EXCEED
 100 FEET.
  
 15) THERE ARE STAIRS THAT ARE NOT
 SEPARATED.
  
 16) ON PAGE A2.01 IT SAYS "THE LOFTS
 AT CITY PLACE PROPOSED DEVELOPMENT".
 CLEARLY THIS INFORMATION IS NOT
 CORRECT. ALSO AN ELEVATION APPEARS
 IMPOSED ON THE DRAWING.
  
 17) SITE PLAN DOES NOT DISPAY ANY
 FIRE HYDRANT LOCATIONS.
  
 18) DOORS 1.005 AND 1.006 ON PAGE
 AP A5.01 OPPOSE ONE ANOTHER.
  
 19) DOORS MISSING FROM STAIRWAYS.
  
 20) THE FIRE ALARM SYSTEMS SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 21) THE FIRE PROTECTION SITE PLAN
 DISPLAYS A FIRE MAIN WITH NO
 TERMINATION POINT OR CONNECTION
 POINT.
  
 22) THERE APPEARS THAT MORE DOORS
 ON THE DOOR SCHEDULE SHOULD BE FIRE
 RATED.
  
 23) ELEVATORS WARNING SIGNS ARE
 REQUIRED.
  
 24) BUILDING ADDRESSES REQUIRED ON
 PROPER ELEVATIONS.
  
 25) CLUBHOUSE DOORS 208 AND 203
 WHEN OPENED TOGETHER WILL BLOCK
 THE HALLWAY.
  
 26) PLEASE EXPLAIN WHERE CLUBHOUSE
 DOOR 201 TERMINATES TO.
  
 27) A TWO HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN PARKING AREAS AND
 OTHER AREAS OF THE BUILDING.
  
 28) ELECTRONIC SWITCHES WILL BE
 REQUIRED ON THE FIRE LINE BACKFLOW
 DEVICES.
  
 29) ANOTHER FIRE HYDRANT APPEARS
 TO BE NEEDED NEAR THE ENTRANCE TO THE
 SITE.
  
 30) SUITABLE ROADS ARE TO BE PROVIDED
 FOR FIRE AND PARAMEDICAL EQUIPMENT.
  
 31) PLANS NEED TO BE BETTER ORGANIZED.
 THEY APPEAR VERY CONFUSING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-06-01 Cont ID  
Sent By kstevens Date 2004-06-01 Time 18:47 Rev Time 0.00
Received By kstevens Date 2004-03-02 Time 08:16 Sent To  
Notes
2004-03-02 00:00:00TO COMM BD#44/ON RACK/3 LG ROLLS-2 SM
 ROLLS & BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-05-10 Cont ID  
Sent By pkrauss Date 2004-05-10 Time 08:59 Rev Time 1.50
Received By pkrauss Date 2004-05-10 Time 08:58 Sent To  
Notes
2004-05-10 00:00:00DENIED:
 PLEASE NOTES, PLANS APPEAR TO BE
 INCOMPLETE.
  
 1.PERMIT APPLICATION INDICATES A 4
 STORY OVER PARKING GARAGE. PLEASE SUBMIT
 PLANS ON VENTILATION FOR THE GARAGE.
 INDICATE OPEN OR CLOSED GARAGE.PROVIDE
 CALCULATIONS PER 2001 FBC 411.3.2 OR
 411.4.2.
  
 2.PLAN SHEETS M15.01 THROUGH M15.03,
 RETURN AIR TRANSFER FROM MASTER
 BEDROOMS SHALL BE SIZED PER THE REVISED
 2001 FBC(M) 601.4 EXCEPTION #2 &3; 50 SQ
 INCHES OF CLEAR SPACE PER 100 CFM OF
 SUPPLY AIR.ALL SUPPLY AIR INTO THE
 MASTER SUITE IS TO BE INCLUDED FOR THE
 "TOTAL" AIR INTO THAT SPACE.
  
 3.PLAN SHEET M15.12 DETAIL FOR THE
 RETURN AIR TRANSFER.SHOW COMPLIANCE
 WITH 2001 FBC(M) 603.8 & CHAPTER 13 SUB
 SUB-CHAPTER 610.1.ABC.3.6 OF THE FBC.
  
 4.PLEASE PROVIDE A FLOOR PLAN FOR THE
 CORRIDORS.INDICATE VENTILATION &
 EQUIPMENT THAT WILL SERVE THE COMMON
 AREA.
  
 5.INDICATE WHERE THE TRASH & FIRE PUMP
 ROOM ARE LOCATED (GARAGE, ROOF, ETC.).
  
 6.PLAN SHEET M15.12 AHU MOUNTING
 DETAIL #3, INDICATES DUCT SUPPORTED ON
 THE BOTTOM CHORD.PROVIDE
 DOCUMENTATION THAT THE BOTTOM CHORD IS
 DESIGNED TO SUPPORT EQUIPMENT FROM THE
 BOTTOM OF THE TRUSS.
  
 7.PLAN SHEET M15.12 AHU MOUNTING
 DETAIL, PER 2001 FBC(M) 603.1.3, A
 MINIMUM OF 4" CLEARANCE AROUND THE AHU
 SHALL BE PROVIDED.
  
 8.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC
 307.2.3.
  
 9.CONDENSING UNIT STANDS LOCATED ON
 THE ROOF SHALL COMPLY WITH 2001 FBC
 1511.7 FOR HEIGHT REQUIREMENT BETWEEN
 THE FINISHED ROOF & THE BOTTOM OF THE
 SUPPORT RAIL.
  
 10. PROVIDE OUTSIDE AIR CALUCALTIONS FOR
 THE RESIDENCE AS WELL AS COMMON AREAS
 PER 2001 FBC(M) 403.3.SHOULD 402.2 BE
 USED, PROVIDE RESULTS FROM TESTING
 AGENCY SHOWING THE ACTUAL FILTRATION
 RATE FOR EACH WINDOW AND DOOR.PLEASE
 INDICATE CALCULATION ON THE PLAN
 SHOWINGCOMPLIANCE WITH 2001 FBC(M)
 402.2.
  
 11.PROVIDE INFORMATION FOR THE
 CONDENSATE.
  
 12.PLEASE NOTE DRYER EXHAUST DUCT
 SHALL NOT EXCEED 25' WITH A 5' REDUCTION
 FOR EACH 90 DEGREE EL & 2 1/2' FOR EACH
 45 DEGREE EL.2001 FBC(M) 504.6
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-06-04 Cont ID  
Sent By kstevens Date 2004-06-01 Time 17:48 Rev Time 3.00
Received By kstevens Date 2004-06-01 Time 17:48 Sent To  
Notes
2004-06-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 FHA-98 AMEND. DESIGN MANUAL
  
 1) PER FHA DESIGN MANUAL REQUIREMENT 7B
 SPECIFICATION "A" OR "B" TO BE INDICATED
 FOR EACH UNIT TYPE.
 2) SHOW HEIGHT OF LAVS PER FHA DESIGN
 MANUAL PAGE 7.52. (34" MAX).
 3) SHOW DETAIL FOR BACKING AT SIDE WALL
 OF WATER CLOSET PER PAGE 6.4 OF THE FHA
 DESIGN MANUAL.
 4) SHT AP A5.04 ROOF PLAN KEY NOTES 4 &
 5 ARE NOT SHOWN. PLEASE CLARIFY. SECTION
 104.2.1- SHTS AP A5.12, A5.25, A5.32,
 AND A5.42 ALSO.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW SQUARE FOOT-
 AGE FOR EACH AREA. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO SF OF ROOF. SHOW AREAS OF ROOF DRAIN-
 ING ONTO ROOF FROM ABOVE. SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS.
 6) SUBMIT A DETAIL FOR SECONDARY ROOF
 DRAINS. SECTION 1O4.2.1.
 7) SHOW LOCATIONS FOR ALL SECONDARY ROOF
 DRAINS. SECTION 104.2.1.
 8) SHT AP A5.70 SUBMIT DETAILS FOR SECT-
 IONS 11-4.15, 11-4.16, 11-4.19, 11-4.22
 AND ALL SUBSECTIONS.
 9) SHT AP A5.71 SUBMIT A DETAIL FOR THE
 SMOOTHIE BAR & THEATER/CONF. ROOM SINKS
 PER 11-4.24 AND ALL SUBSECTIONS.
 10) SUBMIT A DETAIL FOR THE TRASH CHUTE
 WASH DOWN. SHOW WATER SUPPLY SIZE AND
 SHOW REQUIRED BACKFLOW. SECTION 104.2.1
 11) SHTS P14.02 UNITS B3 & B4 AND RISER
 S/5. MAXIMUM 4 FIXTURE UNITS ALLOWED ON
 2" WET VENT. TABLE 909.3 (MASTER BATH)
 12) SHT P14.04 2ND FLOOR CLUBHOUSE PLUMB
 ING PLAN. KITCHEN SINK SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT FOR THE TOIL-
 ET ROOM. - ALSO SEE SANT. RISER S/9.
 13) SUBMIT A SANITARY BLDG DRAIN ISOMET-
 RIC RISER DIAGRAM. SHOW PIPE SIZE, AND
 DFU'S AS THEY ACCUMULATE IN THE SYSTEM.
 INDICATE TOTAL FIXTURE UNITS FOR EACH
 SANITARY RISER. SECTION 104.3.1.1
 14) AN RPZ BACKFLOW IS REQURED AT EACH
 BUILDING. SECTION 608.13.2
 15) SHT AP 14.27 THERMAL EXPANSION CON-
 TROL IS REQUIRED PER SECTION 607.3.2
 SUBMIT DETAIL.
 16) SHT AP 14.27 WATER HEATER DETAIL,
 DIELECTRIC UNIONS ARE NOT APPROVED FOR
 USE IN THE WATER SYSTEM. DELETE FROM DE-
 TAIL.
 17) SUBMIT WATER RISER DIAGRAMS. SHOW
 PIPE SIZE. SECTION 104.3.1.1 - SHOW
 WATER HAMMER ARRESTORS REQUIRED BY SECT-
 ION 604.9 AND LOCATED PER PDI-WH 201.
 18) SUBMIT A BLDG STORM DRAIN ISOMETRIC
 AND STORM RISER DIAGRAMS. SHOW PIPE SIZE
 AND INDICATE SQUARE FOOTAGE AS I ACCUMU-
 LATES IN THE BLDG STORM DRAIN. SECTION
 104.3.1.1
 19) SUBMIT A CONDENSATE RISER DIAGRAM.
 SHOW ALL PIPE SIZES. SECTION 104.3.1.1.
 20) SUBMIT BLDG DRAIN ISOMETRIC FOR THE
 PAN DRAIN LINES. MINIMUM DRAIN LINE UN-
 DERGROUND IS 2". SECTION 710.3
 21) APPLICATIONS ARE FOR BLDGS 1, 2, & 3
 BUT PLANS SHOW BLDGS. 4 & 5. PLEASE
 CLARIFY. SECTION 104.2.1
 22) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025 - PER FBPE'S RULING INITIALS
 ARE NOT ACCEPTABLE. MINIMUM OF FIRST AND
 LAST REQUIRED FOR SIGNATURE ON SEALED
 PLANS.
 23) FLOOR DRAINS SHOWN ON BLDG DRAIN
 SYSTEM ARE NOT APPROVED FOR THE SANITARY
 SYSTEM. THESE ARE AREA DRAINS FOR THE
 PARKING GARAGE AND SHALL CONNECT TO THE
 STORM SYSTEM.
 24) PLANS DO NOT SEEM TO BE COMPLETE AND
 ADDITIONAL COMMENTS MAY BE ADDED NEXT
 REVIEW IF MORE INFORMATION IS AVAILABLE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-06-07 Cont ID  
Sent By mmclean Date 2004-06-07 Time 16:41 Rev Time 0.00
Received By mmclean Date 2004-06-07 Time 16:41 Sent To  
Notes
2004-06-07 00:00:00APPROVED BY JOSH LONG, PLANNER 659-8031