Plan Review Details - Permit 04021265
Plan Review Stops For Permit 04021265
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-26 Cont ID  
Sent By kstevens Date 2004-05-26 Time 16:34 Rev Time 1.00
Received By alange Date 2004-05-26 Time 16:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-12 Cont ID  
Sent By pkrauss Date 2004-05-26 Time 11:20 Rev Time 1.50
Received By alange Date 2004-04-12 Time 10:02 Sent To  
Notes
2004-04-12 00:00:00DENIED
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.BASED UPON BUILDING VALUATION DATA
 FROM SBCCI.THE VALUATION OF $50,000
 IS TOO LOW AND HAS BEEN CHANGED TO
 $110,283.ADDITIONAL PERMIT FEES OF
 $623.20 DUE BEFORE A PERMIT CAN BE ISSUE
  
 3.SUBMIT 2 COPIES OF PRODUCT APPROVALS
 FOR HARDIE PLANK SIDING.
  
 4.TWO COMPLETE COPIES OF NOTICE OF
 ACCEPTANCE AND PRODUCT APPROVAL REQUIRED
 SUBMITALS ARE INCOMPLETE.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2004-04-01 Cont ID  
Sent By mmclean Date 2004-03-23 Time 16:52 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-28 Cont ID  
Sent By csiegber Date 2004-10-28 Time 14:23 Rev Time 0.00
Received By csiegber Date 2004-10-28 Time 14:23 Sent To M
Notes
2004-10-28 00:00:00TO PK BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 11:14 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 11:14 Sent To M
Notes
2004-10-04 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-05-11 Time 08:19 Rev Time 0.00
Received By csiegber Date 2004-05-11 Time 08:19 Sent To P
Notes
2004-05-11 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-23 Time 09:47 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 16:32 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-16 Cont ID  
Sent By mmclean Date 2004-03-22 Time 16:28 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 15:38 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2004-11-22 Cont ID  
Sent By pkrauss Date 2004-11-22 Time 16:39 Rev Time 0.40
Received By pkrauss Date 2004-11-22 Time 16:39 Sent To  
Notes
2004-11-22 00:00:00DENIED:
 ONE COPY OF A PLAN SUBMITTED WITH RED
 LINES.PLEASE PROVIDE 2 COPIES AS
 REQUIRED PER 2001 FBC(M) 104.2.1.FEES
 WILL BE OWED FOR REVISIONS.THIS SHOULD
 NOT HAVE BEEN SUBMITTED AS A SUBMITTAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-28 Time 14:23 Rev Time 0.30
Received By pkrauss Date 2004-10-05 Time 07:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-05-26 Cont ID  
Sent By csiegber Date 2004-10-04 Time 11:14 Rev Time 0.40
Received By pkrauss Date 2004-05-26 Time 11:20 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-05-11 Time 08:19 Rev Time 0.40
Received By pkrauss Date 2004-04-05 Time 13:07 Sent To B
Notes
2004-04-05 00:00:00DENIED:
 1.PLAN SHEET M-1, PLEASE CLARIFY
 RETURN AIR DUCT TERMINATING INTO THE
 STORAGE ROOM.IS THIS DUCT TIED INTO
 THE AHU?
  
 2.PLEASE INDICATE IF THE WATER HEATER
 IS GAS OR ELECTRIC.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PLAN SHEET M-2 RETURN AIR DUCT TO
 THE MASTER BEDROOM DOES NOT INDICATE
 DUCT SIZE.PLEASE NOTE WHEN SIZING THE
 RETURN AIR FOR THE MASTER BEDROOM, ALL
 SUPPLY AIR INTO THE MASTER SUITE IS TO
 BE INCLUDED IN THE CALCULATION FOR A
 "TOTAL" OF SUPPLY AIR TO THE SUITE.
 REVISED 2001 FBC(M) 601.4 EXCEPTION #3.
 PLEASE SIZE RETURN AIR TO THE MASTER
 SUITE ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-26 Cont ID  
Sent By kstevens Date 2004-05-26 Time 16:33 Rev Time 1.50
Received By kstevens Date 2004-05-26 Time 16:33 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-04-03 Cont ID  
Sent By csiegber Date 2004-05-18 Time 14:59 Rev Time 1.50
Received By kstevens Date 2004-04-03 Time 13:18 Sent To M
Notes
2004-04-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT D-1 ALL DEMO'D AND ABANDONED PIPE
 SHALL BE INSPECTED PRIOR TO COVERING.
 2) DEAD ENDS SHALL BE PROHIBITED WHEN
 REMOVING ANY PART OF A DRAINAGE SYSTEM.
 SECTION 704.5
 3) SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS.
 A) FIRST FLOOR KITCHEN SINKS SHALL NOT
 CONNECT TO THE WET VENTED HORIZONTAL
 BRANCH DRAIN FOR THE POWDER ROOM. FIX-
 TURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. SECTION 909.1.
 B) SECOND FLOOR WASH MACHINE SHALL NOT
 CONNECT TO THE WET VENTED HORIZONTAL
 BRANCH DRAIN FOR THE MASTER BATHROOM.
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. SECTION 909.1.
 C) A FIXTURE SHALL NOT BE DOUBLE TRAPP-
 ED. WATER CLOSETS HAVE AN INTEGRAL TRAP
 AND DO NOT REQUIRE A TRAP ON THE RISER
 DIAGRAM. SECTION 1002.1
 D) WASH MACHINE REQUIRES A STANDPIPE &
 A CLEANOUT 4' ABOVE THE FLOOR PER SECT-
 IONS 1002.1, 802.4, AND 708.10.
 4) THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT. SEPARATE GAS PERMIT IS
 REQUIRED.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED).
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER FBC-2001 FUEL GAS CODE SECTION
 304. - FOR BOTH THE WATER HEATER ROOM
 AND THE DRYER ROOM.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 5) SEAL FOR ARCHITECT SHALL MAKE AN IM-
 PRESSION ON THE SURFACE OF THE PRINTS OR
 DRAWINGS. NO INFORMATION IS SHOWN ON THE
 SEALED PLANS. FAC 61G1-16.001
 6) LICENSE AA0003566 SHOWS ARCHITECT
 BUSINESS NUMBER FOR TEKTONICA DESIGN INC
 NOT BORGLUND TYSON, LLC AS SHOWN ON THE
 TITLE BLOCK. FIRM NAME SHALL BE ON TITLE
 BLOCK PER 61G1-16.004(1).
 7) A CERTIFICATE OF AUTHORIZATION IS RE-
 QUIRED PER FS 481.219(2) & (3). SHOW THE
 CERTIFICATE OF AUTHORIZATION ON TITLE
 BLOCK OF EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-23 Cont ID  
Sent By mmclean Date 2004-03-23 Time 16:52 Rev Time 0.00
Received By mmclean Date 2004-03-23 Time 16:52 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-16 Time 15:38 Rev Time 0.00
Received By mmclean Date 2004-03-22 Time 16:27 Sent To I
Notes
2004-03-22 00:00:00DENIED, NEED TO SHOW THE LOCATION OF
 THE ADDITION.CALLED OWNER LEFT MSG