| 2004-04-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT D-1 ALL DEMO'D AND ABANDONED PIPE |
| | SHALL BE INSPECTED PRIOR TO COVERING. |
| | 2) DEAD ENDS SHALL BE PROHIBITED WHEN |
| | REMOVING ANY PART OF A DRAINAGE SYSTEM. |
| | SECTION 704.5 |
| | 3) SHT P-1 SANITARY RISER DIAGRAM DOES |
| | NOT MEET CODE REQUIREMENTS. |
| | A) FIRST FLOOR KITCHEN SINKS SHALL NOT |
| | CONNECT TO THE WET VENTED HORIZONTAL |
| | BRANCH DRAIN FOR THE POWDER ROOM. FIX- |
| | TURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. SECTION 909.1. |
| | B) SECOND FLOOR WASH MACHINE SHALL NOT |
| | CONNECT TO THE WET VENTED HORIZONTAL |
| | BRANCH DRAIN FOR THE MASTER BATHROOM. |
| | FIXTURES SHALL DISCHARGE DOWNSTREAM OF |
| | THE WET VENT. SECTION 909.1. |
| | C) A FIXTURE SHALL NOT BE DOUBLE TRAPP- |
| | ED. WATER CLOSETS HAVE AN INTEGRAL TRAP |
| | AND DO NOT REQUIRE A TRAP ON THE RISER |
| | DIAGRAM. SECTION 1002.1 |
| | D) WASH MACHINE REQUIRES A STANDPIPE & |
| | A CLEANOUT 4' ABOVE THE FLOOR PER SECT- |
| | IONS 1002.1, 802.4, AND 708.10. |
| | 4) THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PERMIT. SEPARATE GAS PERMIT IS |
| | REQUIRED. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED). |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER FBC-2001 FUEL GAS CODE SECTION |
| | 304. - FOR BOTH THE WATER HEATER ROOM |
| | AND THE DRYER ROOM. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAS CODE |
| | SECS. 502 THRU 506. |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 5) SEAL FOR ARCHITECT SHALL MAKE AN IM- |
| | PRESSION ON THE SURFACE OF THE PRINTS OR |
| | DRAWINGS. NO INFORMATION IS SHOWN ON THE |
| | SEALED PLANS. FAC 61G1-16.001 |
| | 6) LICENSE AA0003566 SHOWS ARCHITECT |
| | BUSINESS NUMBER FOR TEKTONICA DESIGN INC |
| | NOT BORGLUND TYSON, LLC AS SHOWN ON THE |
| | TITLE BLOCK. FIRM NAME SHALL BE ON TITLE |
| | BLOCK PER 61G1-16.004(1). |
| | 7) A CERTIFICATE OF AUTHORIZATION IS RE- |
| | QUIRED PER FS 481.219(2) & (3). SHOW THE |
| | CERTIFICATE OF AUTHORIZATION ON TITLE |
| | BLOCK OF EACH SHEET. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |