Plan Review Details - Permit 04021186
Plan Review Stops For Permit 04021186
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-04-16 Cont ID  
Sent By lmartine Date 2004-04-16 Time 13:00 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
2004-04-16 00:00:00 
 PROVISO
  
 SUBMIT PRODUCT APPROVAL FOR ANY NEW
 WINDOWS, SHUTTERS AND EXTERIOR DOORS TO
 BE INSTALLED.
  
  
  
  
  
 L. MARTINEZ
 805-6710

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 05:52 Rev Time 0.75
Received By dpalmer Date 2004-03-05 Time 05:46 Sent To  
Notes
2004-03-05 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S
 ON TITLE BLOCK AS REQ'D UNDER FS 481.219
 AND FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS,
 PANEL MAY NOT BE LOCATED ON EXIT/EGRESS
 STAIRWELL.
  
 3)NOTE: PLANS DO NOT INCLUDE "SECOND"
 FLOOR FOR REVIEW.
 PLANS NOT COMPLETE FOR SUFFICENT REVIEW
  
 4)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS.
  
 5)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT/REAR RECEPTS.
  
 6)NOTE: PLEASE SEE NO INFORMATION SUBMIT
 -TED FOR HOUSE PANEL FOR LAUNDRY EQUIP-
 -MENT.
 NO COMMON BRANCH CIRCUITS FROM APT
 PANELS PERMITTED IN COMMON AREA.
  
 7)NOTE: PLEASE SEE MISSING EGRESS LIGHT-
 ING PER LS 101 5-8 , 210.70 NEC
  
 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 9) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 10)NOTE: PLEASE SHOW /CLARIFY METHOD
 OF THE EQUIPMENT GROUNDING BETWEEN
 MAIN MEANS OF DISC AND PANELS/GUTTERS.
 250.110,250.24
 PLEASE SIZE ALL EQUIPMENT GROUNDING
 CONDUCTORS PER 250.122
 EQUIPMENT GROUND IS SHOWN ON LINE SIDE
 OF METER>250.6
  
 11)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 12)NOTE: PLEASE SEE 210.11C1, 220.16 FOR
 MIN SMALL APPL.
  
 13)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCS FOR ALL ELECTRICAL SHOWN.
 NEED MORE INFORMATION.
  
 14)NOTE: PLEASE SHOW LOCATION OF SERVICE
 AND MAINS. MAINS TO BE GROUPED PER
 230.72.
 RISER SHOWS A MAIN DISC AND MCB PANEL??
 IF MCB IS SHOWN, THEN IT WILL BE REQ'D
 TO BE INSTALLED.
  
 FYI, NO LOW VOLTAGE SHOWN FOR PHONE/TV
 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-02-27 Cont ID  
Sent By mcarsill Date 2004-02-27 Time 14:26 Rev Time 0.00
Received By mcarsill Date 2004-02-27 Time 14:26 Sent To  
Notes
2004-02-27 00:00:001) PROVIDE MORE DETAILS ON EGRESS
 WINDOWS. PLEASE PROVIDE DETAILS
 ON MAXIMUM SILL HEIGHTS, MAXIMUM
 OPENING SIZE, AND LATCHING ARRANGEMENT.
  
 2) ELECTRICAL PANEL # 1 SHOWN IN
 STAIRWELL BASEMENT.
  
 3)NO MENTION ABOUT EXISTING OR NEW
 FIRE EXTINGUISHERS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 15:02 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 15:02 Sent To  
Notes
2004-02-25 00:00:00TO COMM BD#58

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-03-06 Cont ID  
Sent By kstevens Date 2004-03-06 Time 09:18 Rev Time 0.25
Received By kstevens Date 2004-03-06 Time 09:18 Sent To  
Notes
2004-03-06 00:00:00NO PLUMBING PLANS SUBMITTED - FIXTURE
 REPLACEMENT - SEE ELECTRICAL REVIEW
 CONCERNING ENGINEERS LICENSE'S REQUIRE-
 MENTS.