| 2004-03-05 00:00:00 | *************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S |
| | ON TITLE BLOCK AS REQ'D UNDER FS 481.219 |
| | AND FAC 61G1-16.004 |
| | |
| | 2)NOTE: PLEASE SEE FIRE REVIEW COMMENTS, |
| | PANEL MAY NOT BE LOCATED ON EXIT/EGRESS |
| | STAIRWELL. |
| | |
| | 3)NOTE: PLANS DO NOT INCLUDE "SECOND" |
| | FLOOR FOR REVIEW. |
| | PLANS NOT COMPLETE FOR SUFFICENT REVIEW |
| | |
| | 4)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPTS. |
| | |
| | 5)NOTE: PLEASE SEE 210.52E FOR MISSING |
| | FRONT/REAR RECEPTS. |
| | |
| | 6)NOTE: PLEASE SEE NO INFORMATION SUBMIT |
| | -TED FOR HOUSE PANEL FOR LAUNDRY EQUIP- |
| | -MENT. |
| | NO COMMON BRANCH CIRCUITS FROM APT |
| | PANELS PERMITTED IN COMMON AREA. |
| | |
| | 7)NOTE: PLEASE SEE MISSING EGRESS LIGHT- |
| | ING PER LS 101 5-8 , 210.70 NEC |
| | |
| | 8)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 9) NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 10)NOTE: PLEASE SHOW /CLARIFY METHOD |
| | OF THE EQUIPMENT GROUNDING BETWEEN |
| | MAIN MEANS OF DISC AND PANELS/GUTTERS. |
| | 250.110,250.24 |
| | PLEASE SIZE ALL EQUIPMENT GROUNDING |
| | CONDUCTORS PER 250.122 |
| | EQUIPMENT GROUND IS SHOWN ON LINE SIDE |
| | OF METER>250.6 |
| | |
| | 11)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 12)NOTE: PLEASE SEE 210.11C1, 220.16 FOR |
| | MIN SMALL APPL. |
| | |
| | 13)NOTE: PLEASE SUBMIT COMPLETED LOAD |
| | CALCS FOR ALL ELECTRICAL SHOWN. |
| | NEED MORE INFORMATION. |
| | |
| | 14)NOTE: PLEASE SHOW LOCATION OF SERVICE |
| | AND MAINS. MAINS TO BE GROUPED PER |
| | 230.72. |
| | RISER SHOWS A MAIN DISC AND MCB PANEL?? |
| | IF MCB IS SHOWN, THEN IT WILL BE REQ'D |
| | TO BE INSTALLED. |
| | |
| | FYI, NO LOW VOLTAGE SHOWN FOR PHONE/TV |
| | ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |