| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-03-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-25 |
Time |
15:00 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-03-01 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2004-03-01 00:00:00 | PROVISO: | | | 1.PLAN INDICATES A WINDOW (3' X 3'), | | | PER 2001FBC(M) 402.3.1 WINDOWS SHALL | | | HAVE NO LESS THAN 3 SQ FT OF OPEN SPACE | | | OTHERWISE MECHANICAL VENTILATION WILL | | | BE REQUIRED. | | | | | | 2.FAN SHUTDOWN WITH NOTIFICATION TO | | | ALARM/STROBE ON SYSTEMS WITH A DESIGN | | | CAPACITY GREATER THAN 2,000 CFM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|