Plan Review Details - Permit 04021148
Plan Review Stops For Permit 04021148
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-12-08 Cont ID  
Sent By jwitmer Date 2004-12-08 Time 07:40 Rev Time 0.75
Received By jwitmer Date 2004-12-08 Time 07:40 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-07-14 Cont ID  
Sent By alange Date 2004-07-14 Time 14:11 Rev Time 1.00
Received By alange Date 2004-07-14 Time 14:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-06-19 Cont ID  
Sent By jwitmer Date 2004-06-19 Time 15:28 Rev Time 0.75
Received By jwitmer Date 2004-06-19 Time 15:28 Sent To PC
Notes
2004-06-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021148
 ADD: 2421 OKEECHOBEE BLVD
 CONT: SOUTHEAST CONSTRUCTION
 TEL: (561)282-7610
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 3RD REVIEW
 ACTION: DENIED
  
 PLANS ARE FOUND TO BE CODE COMPLIANT:
 ****************************************
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-13 Cont ID  
Sent By jwitmer Date 2004-05-13 Time 11:20 Rev Time 0.99
Received By jwitmer Date 2004-05-13 Time 11:20 Sent To  
Notes
2004-05-13 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021148
 ADD: 2421 OKEECHOBEE BLVD
 CONT: SOUTHEAST CONSTRUCTION
 TEL: (561)282-7610
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-02 Cont ID  
Sent By jwitmer Date 2004-04-02 Time 15:38 Rev Time 3.33
Received By jwitmer Date 2004-04-02 Time 15:38 Sent To  
Notes
2004-04-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021148
 ADD: 2421 OKEECHOBEE BLVD
 CONT: SOUTHEAST CONSTRUCTION
 TEL: (813)251-6802
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 4) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PROVIDE THE MINIMUM BUILDING TYPE:
  
 6) BUILDING IS LOCATED IN THE "FIRE
 DISTRICT", SEE REQUIREMENTS FOR "FIRE
 DISTRICT", NO TYPE VI BUILDINGS ALLOWED,
 EXTERIOR WALLS NOT TO COMBUSTIBLE, SEE
 PLYWOOD SHEATHING.
  
 7) ADD INFO PLANS INDICATE THE USE OF
 6" 16 GA STEEL STUDS BUT THE CONNENCTION
 OF THE TOP AND BOTTOM PLATES TO VARIOUS
 MATERIALS IS NOT GIVEN , SEE A3 DETAIL
 # 2, SHEET# 3A DETAIL 1 ALSO.
  
 8) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED WINDOWS
 B) MULLIONS, HORIZONTAL/ VERTICAL
 C) SWING DOOR
 D) ROOFING ASSEMBLIES
 E) STORM PANELS
 **************IMPORTANT**************
 9)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 11) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 12) CHECK WINDOW AND DOOR PRESSURES TO
 TABLE 1606.2B, BOTH POSITIVE & NEGITIVE
 PRESSURES ARE LOW.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2004-11-18 Cont ID  
Sent By dpalmer Date 2004-11-18 Time 18:03 Rev Time 0.20
Received By dpalmer Date 2004-11-18 Time 18:03 Sent To  
Notes
2004-11-18 00:00:00NO ELECTRICAL COULD BE LOCATED ON PLANS
 SUBMITTED.
 REV COVER SHEET WAS CHECKED OFF FOR AN
 ELECTRICAL REVIEW??

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-09 Cont ID  
Sent By dpalmer Date 2004-03-09 Time 09:04 Rev Time 1.00
Received By dpalmer Date 2004-03-09 Time 07:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-04 Cont ID  
Sent By mcarsill Date 2004-05-04 Time 11:04 Rev Time 0.00
Received By mcarsill Date 2004-05-04 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-03-02 Cont ID  
Sent By mcarsill Date 2004-03-02 Time 13:04 Rev Time 0.00
Received By mcarsill Date 2004-03-02 Time 13:04 Sent To  
Notes
2004-03-02 00:00:001) PLEASE INDICATE ANY AND ALL
 SAFEGUARDS THAT WILL BE TAKEN FOR
 SAFETY. WILL THE EXISTING RESTAURANT
 REMAIN OPEN OR CLOSED DURING THE
 RENOVATIONS. PLEASE ADVISE.
  
 2) PLEASE INDICATE NEW OCCUPANT LOAD
 BASED ON NEW SEATS PLANNED FOR THE
 ADDITION.
  
 3) PANIC HARDWARE REQUIRED ON EXIT DOORS
 IF DOORS ARE SUBJECT TO 100 OR MORE
 PERSONS.
  
 4) PLEASE INDICATE SEATING LOCATIONS
 FOR THE HANDICAPPED IN THE EXISTING
 OR NEW CONSTRUCTION AREAS.
  
 5) ALL CONSTRUCTION, DEMOLITITON, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 13:19 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 13:19 Sent To E
Notes
2004-11-16 00:00:00SENT TO COMM BD#9

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 16:41 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 16:41 Sent To  
Notes
2004-06-03 00:00:00TO COMM BD#19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 16:31 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 16:31 Sent To  
Notes
2004-04-30 00:00:00TO COMM BD#17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-25 Time 15:54 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 15:53 Sent To  
Notes
2004-02-25 00:00:00TO COMM BD#36

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-06-10 Cont ID  
Sent By pkrauss Date 2004-06-10 Time 07:21 Rev Time 0.35
Received By pkrauss Date 2004-06-10 Time 07:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-05-05 Cont ID  
Sent By pkrauss Date 2004-05-05 Time 07:19 Rev Time 0.40
Received By pkrauss Date 2004-05-05 Time 06:50 Sent To  
Notes
2004-05-05 00:00:00DENIED:
 RESPONSE TO COMMENT #1 FROM REVIEW
 DATED 3-24-04:
 CONDENSATE FROM THE ROOFTOP UNIT IS TO
 DISCHARAGE ONTO ROOF.
  
 1.PLEASE CLARIFY, WILL CONDENSATE BE
 PIPED FROM THE UNIT TO THE GENERAL
 VICINITY OF THE SCUPPER OR IS IT THE
 INTENT TO JUST LET IT RUN DOWN THE ROOF
 & GRAVITY TO DIRECT WATER TO SCUPPER?
 PLEASE NOTE, PER 2001 FBC(M) 307.2.1.#3,
 DISCHARGE SHALL NOT CAUSE A NUISANCE.
  
 2.WHERE DOES THE SCUPPER TERMINATE?
 PLAN SHEET A0 INDICATES A SIDEWALK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-24 Cont ID  
Sent By pkrauss Date 2004-03-24 Time 12:25 Rev Time 0.55
Received By pkrauss Date 2004-03-24 Time 12:00 Sent To  
Notes
2004-03-24 00:00:00DENIED:
 1.PROVIDE ADDITIONAL INFORMATION ON
 THE CONDENSATE.PER CITY CODE SEC.
 90-125 (5), CONDENSATE SHALL TERMINATE
 INTO THE STORM DRAIN.PER 2001 FBC(M)
 307.2.1. #1, UNITS LARGER THAN 6 TON,
 CONDENSATE SHALL TERMINATE INTO STORM
 DRAIN OR AN APPROVED DRY WELL.
  
 2.PLEASE PROVIDE ENERGY CALCULATIONS
 PER 2001 FBC CHAPTER 13 SUB-CHAPTER 400.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status N Date 2004-06-18 Cont ID  
Sent By kstevens Date 2004-06-18 Time 16:49 Rev Time 1.00
Received By kstevens Date 2004-06-18 Time 16:49 Sent To  
Notes
2004-06-18 00:00:00NO PLUMBING PLANS SUBMITTED - ALL ROOF
 COMMENTS ADDRESSED EXCEPT PROVISO ON
 SLOPE OF GUTTER. GUTTER SHALL SLOPE @
 1/4" PER FT. KSTEVENS

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-05-15 Cont ID  
Sent By kstevens Date 2004-05-15 Time 17:41 Rev Time 1.00
Received By kstevens Date 2004-05-15 Time 17:41 Sent To  
Notes
2004-05-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) CALCULATIONS FOR UPPER ROOF DO NOT
 SHOW 1/2 AREA OF VERITCAL WALLS AS REQ-
 QUESTED. THE ROOF AREA AS SCALED OUT IS
 THE SAME AS INDICATED ON CALCULATIONS
 WITH VERTICAL WALLS, (PARAPETS), ADDED.
 SHOW DIMENSIONS OF ROOF AREA AND SHOW
 HEIGHT OF PARAPETS TO CONFIRM CALCULAT-
 IONS.
 2) SUBMIT THE SAME INFORMATION FOR LOW-
 ER ROOF. SUBMIT A DETAIL FOR LOWER ROOF
 SHOWING GUTTER AND DOWNSPOUT INDICATED
 IN CALCULATIONS ON SHT A4. 5" GUTTER IS
 NOT SUFFICIENT FOR THE ROOF AREA TO BE
 DRAINED PER TABLE 1106.6. SHOW SLOPE OF
 GUTTER AND SHOW HIGH POINT OF GUTTER AND
 LOCATION OF DOWNSPOUT. INDICATE SLOPE OF
 GUTTER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-06 Cont ID  
Sent By kstevens Date 2004-03-06 Time 08:24 Rev Time 1.00
Received By kstevens Date 2004-03-06 Time 08:24 Sent To  
Notes
2004-03-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
  
 1) ROUTE PLANS TO THE DEPT. OF BUSINESS
 REGULATION HOTEL AND RESTAURANT DIVISION
 FOR REVIEW. 201 W BROWARD BLVD. SUITE
 104 FT. LAUDERDALE FLA. (954) 958-5520
 SECTION 104.1.7
 2) SHT A1A IF BEVERAGE BAR HAS WATER
 SUPPLY, A WATER RISER DIAGRAM SHALL BE
 REQUIRED PER SECTION 104.3.1.1
 3) SHT A4 ROOF PLAN, SUBMIT CALCULATIONS
 FOR UPPER ROOF PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106 & 1107
 AND ALL SUBSECTIONS. SHOW SQUARE FEET OF
 ROOF & 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS.
 4) SHT A4 ROOF PLAN, SUBMIT CALCULATIONS
 FOR LOWER ROOF. SHOW LOCATION AND SIZE
 OF PRIMARY AND SECONDARY ROOF DRAINS.
 SHOW SQUARE FEET OF LOWER ROOF AND SHOW
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS. SHOW SQUARE FEET OF UPPER ROOF
 BEING ADDED TO LOWER ROOF. SHOW SIZE OF
 ALL RWL PIPING AND OR DOWNSPOUTS FOR
 EXISTING ROOF. IF LOWER ROOF IS SLOPED,
 INDICATE SLOPE ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-05 Cont ID  
Sent By mmclean Date 2004-04-05 Time 11:57 Rev Time 0.00
Received By mmclean Date 2004-04-05 Time 11:57 Sent To  
Notes
2004-04-05 00:00:00APPROVED BY JOSH LONG PLANNER 659-8031 M
 M