Plan Review Details - Permit 04021143
Plan Review Stops For Permit 04021143
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-28 Cont ID  
Sent By dpalmer Date 2004-05-07 Time 15:16 Rev Time 1.25
Received By alange Date 2004-04-28 Time 12:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 06:07 Rev Time 2.00
Received By alange Date 2004-04-06 Time 14:52 Sent To  
Notes
2004-04-06 00:00:00DENIED
 1.PRODUCT APPROVAL FOR ENTRY DOOR
 MISSING.SUBMIT 2 COPIES.
 APPICATIONS FOR LOCAL AND OR STATE
 SITE SPECIFIC PRODUCT APPROVAL NOT
 REQUIRED IF THE PRODUCT IS LISTED ON
 THEFBC PRODUCT APPROVAL SITE.ALL
 PRODUCT APPROVALS SUBMITTED ARE ON THE
 FBC SITE.PLEASE REMOVE APPLICATIONS.
  
 2.VALUATION OF $166,800 IS TO LOW
 BASED UPON SBCCI BUILDING VALUATION
 DATA.BUILDING VALUE HAS BEEN CHANGED
 TO $233,750.ADDITIONAL PERMIT FEES
 OF $676.20 AREW DUE BEFORE A PERMIT MAY
 BE ISSUED.
  
 3.WINDOW BUCKS SHALL COMPLY WITH
 FBC 1707.4.4.2 BUCKS SHALL EXTEND
 BEYOND THE INTERIOR FACE OF THE WINDOW
 OR DOOR FRAME SUCH THAT FULL SUPPORT OF
 THE FRAME IS PROVIDED.
 SHOW ON DETAIL.
  
 4.BALISTERS ON GUARD RAILS AND STAIR
 RAILINGS SHALL BE SPACED THAT A 4"
 DIAMETER SHERE CANNOT PASS THROUGH.
 FBC 1015.3SHOW ON DETAIL.
  
 5.SUBMIT A SECOND COPY OF ENERGY CALCS
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-01-10 Cont ID  
Sent By btrobaug Date 2005-01-10 Time 11:07 Rev Time 0.50
Received By btrobaug Date 2005-01-10 Time 10:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-05-07 Cont ID  
Sent By dpalmer Date 2004-05-07 Time 15:15 Rev Time 0.33
Received By dpalmer Date 2004-05-07 Time 15:14 Sent To B
Notes
2004-05-07 00:00:00PLANS SENT TO BLDG FOR PROCESSING.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-05-04 Cont ID  
Sent By dpalmer Date 2004-05-04 Time 18:05 Rev Time 0.25
Received By dpalmer Date 2004-05-04 Time 18:05 Sent To  
Notes
2004-05-04 00:00:00*********** RESPONSE **************
  
 THIS IS IN RESPONSE FROM STUART BRENNER
 DATED 4/28/04
 WE HAVE BEEN INSTRUCTED BY THE STATE
 DBPR, FBPE'S THAT A LEGAL SIGNATURE
 IS REQ'D AS PER FS 481.221, 471.025,
 FAC 61G1-16.004, 61G15-23.002
 WE DO NOT HAVE THE AUTHORITY TO AUTHO-
 -RIZE INITIALS AS AN ALTERNATIVE.
 DBPR AND FBPE'S HAS MENTIONED, LEGAL
 SIGNATURE MAY NOT BE ADJUSTED DUE TO
 TIME IT MAY OR MAY NOT TAKE TO SIGN
 PLANS.
 ANY VARIATION IN LEAGAL SIGNATURE MUST
 BE REVIEWED AND ACCEPTED BY DBPR/ BOARD
 OF ARCHS.
  
 IF DESIRED, PLANS CAN BE SENT OFF FOR
 VERIFICATION OF THIS. THIS WOULD UNFORT-
 -UNATELY DELAY THE PERMIT FOR CONSTRUCT-
 -ION.
 WE ARE IN THE PROCESS OF HAVING FILES
 AND LETTERS BEING SENT TO THE STATE FOR
 REVIEW OF MANY OF THESE ITEMS, NOT ONLY
 SIGNATURE ISSUES.
  
 PLEASE SUBMIT PLANS WITH ABOVE.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-05-03 Time 10:25 Rev Time 0.33
Received By dpalmer Date 2004-04-28 Time 06:07 Sent To B
Notes
2004-04-28 00:00:00**** UNSAT ***
  
 1)NOTE: PLEASE HAVE ARCH SIGN PLANS
 WITH COMPLETE SIGNATURE AS SHOWN ON
 LICENSE/RAISED SEAL ERP FS 481.221
 PLEASE SEE PLANS APPEAR TO SHOW INITIALS
 OF SOME SORT?
 PLEASE SUBMIT COPY OF LICENSE TO VERIFY
 LEAGAL "SIGNATURE". THIS SHOULD BE A
 DRIVER'S LICENSE/ ARCH LICENSE.
 PER RECENT CONVERSATION WITH STATE,
 A MIN OF FIRST AND LAST NAME IS REQ'D
 OR AS SHOWN ON ARCH LICENSE.
 THIS IS REQ'D FOR ALL TRADES AND ALL
 SHEETS. FAC 61G1-16.004
 IF PLANS ONLY COME BACK FOR THIS COMMENT
 ARESUB WILL NOT BE DUE,DUE TO LACK
 OF COMMENT ON FIRST REVIEW BY INITIAL
 REVIEWER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-10 Cont ID  
Sent By csiegber Date 2004-04-27 Time 15:19 Rev Time 0.50
Received By btrobaug Date 2004-03-10 Time 07:54 Sent To M
Notes
2004-03-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 2} THE DOWNSTAIR BEDROOM LABLED #3 (SAME
 AS UPSTAIR #3) NEEDS AN ADDED
 RECEPTACLE PER 210.52(A)(1).
  
 3} THE DISCONNECTS AT THE A/C UNITS DO
 NOT COMPLY WITH 110.26 CLEARANCE
 REQUIREMENTS. PLEASE INDICATE, ON THE
 DRAWING, PLACEMENT FOR COMPLIANCE.
  
 4} PLEASE SEE THE MECHANICAL PLANS TO
 INSURE PLACEMENT OF THE SMOKE DETECTORS
 IS IN COMPLIANCE WITH THE CLEARANCE
 REQUIREMENTS OF NFPA-72, 1999 ED., CH
 #8.
  
 5} NOTE #15 REFERENCES THE 1997 SBC.
 THIS PLAN IS BEING REVIEWED UNDER THE
 2001 FLORIDA BUILDING CODE. ALSO IT
 SHOULD BE NOTED THAT SMOKE DETECTORS IN
 BEDROOMS MUST COMPLY WITH 210.12 AND BE
 ARC FAULT PROTECTED.
  
 6} PLEASE INDICATE THE AMPERAGE RATING
 OF THE FUSE OR BREAKER IN THE MAIN
 DISCONNECT, ALSO THE AIC RATING OF SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 14:29 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 14:29 Sent To E
Notes
2005-01-07 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 10:25 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 10:25 Sent To E
Notes
2004-05-03 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 15:19 Sent To E
Notes
2004-04-27 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-02-27 Time 12:45 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 16:01 Sent To  
Notes
2004-03-01 00:00:00TO SFD RACK/E
2004-02-25 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-10 Cont ID  
Sent By btrobaug Date 2004-03-10 Time 10:37 Rev Time 0.35
Received By pkrauss Date 2004-03-10 Time 15:19 Sent To P
Notes
2004-03-10 00:00:00PROVISO:
 PROVIDE CALCULATIONS FOR COMBUSTION AIR
 IN THE LAUNDRY ROOM IN REFERENCE TO THE
 GAS DRYER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-13 Cont ID  
Sent By pkrauss Date 2004-03-10 Time 15:30 Rev Time 0.25
Received By jleech Date 2004-03-13 Time 09:45 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-27 Cont ID  
Sent By mmclean Date 2004-02-27 Time 12:45 Rev Time 0.00
Received By mmclean Date 2004-02-27 Time 12:45 Sent To I
Notes
***NONE***