Plan Review Details - Permit 04021075
Plan Review Stops For Permit 04021075
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By shill Date 2004-04-06 Time 07:33 Rev Time 4.00
Received By shill Date 2004-04-02 Time 10:06 Sent To  
Notes
2004-04-06 00:00:00****CORRECTIONS****
 ****PAID PLAN REVIEW****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE CA NUMBER FROM FBPE IS TO BE
 ON EACH SHEET, FAC61G15-23.002.THE
 PRINTED NAME AND LICENSE NUMBER OF THE
 PERSON SEALING THE DOCUMENT IS TO BE ON
 EACH SHEET.
  
 2.)A SIGNATURE, NOT INITIALS, REQUIRED
 AS PER BUILDING OFFICIAL.
  
 3.)SEPARATE PERMIT REQUIRED FOR SIGNS.
  
 4.)SUBMIT THREE COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING:
 4X4 SKYLIGHT
 STOREFRONT GLASS
 KNOCKOUT PANELS
 3X3 INTAKE LOUVER
 OVERHEAD DOOR
 WINDOWS
 DOORS
 LOUVERED DOORS
 IMPACT PROTECTION
 ANY OTHER ITEMS REQUIRED
  
 FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC REQUIRED IN ADDITION TO TEST
 REPORT.WWW.FLORIDABUILDING.ORG
  
 5.)PROVIDE A SURVEY FOR THIS
 PROPERTY.
  
 6.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND A RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 7.)IT IS DIFFICULT TO DETERMINE THE
 FLOOD ZONE FROM THE EXHIBIT PROVIDED.
  
 8.)PROVIDE AN ORIGINAL SEALED SOILS
 REPORT (COPIES WERE SUBMITTED).
  
 9.)RESIDENT INSPECTOR REQUIRED, CALL
 HAROLD PISKURA, 805-6711.
  
 10.) THREE SETS OF PLANS REQUIRED.
  
 11.) PROVIDE A FINISHED FLOOR ELEVATION
 ON THE FOUNDATION PLAN.
  
 12.) GUARDRAILS ARE TO COMPLY WITH
 FBC1608.2.2.
  
 13.) 4-A9 REFERS TO A10 FOR THE STAIR
 AND RAMP DETAIL, NOT ON THAT PAGE.
  
 14.) M01, THE RUSKIN LOUVER DETAIL IS
 ILLEGIBLE.
  
 15.) INDICATE WHERE THE HURRICANE
 SHUTTERS WILL BE STORED AND HOW THEY
 WILL BE STORED.IF THEY ARE NOT STORED
 HORIZONTALLY, PROVIDE A RACK DETAIL.
 PROVIDE A HURRICANE SHUTTER INSTALLATION
 SCHEDULE, SEE ATTACHED.
  
 16.) FBC13-101.1.6, SHELL BUILDING ARE
 TO COMPLY WITH METHOD B OF SUB-CHAPTER
 13-4.
  
 17.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 18.) PLEASE NOTE THAT THE ADDRESS ON
 THE PERMIT APPLICATION IS INCORRECT.
  
 19.) PROVIDE A LIFE SAFETY PLAN.SHOW
 COMPLIANCE WITH FBC CHAPTER 10.
  
 20.) PROVIDE A CODE ANALYSIS FOR THIS
 BUILDING (DECLARE A BUILDING TYPE,
 OCCUPANT LOAD, SPRINKLER AND PROTECTION
 INFORMATION, ETC.)
  
 21.) SHOW HOW YOU ARE COMPLYING WITH
 FBC CHAPTER 5.
  
 22.) PROVIDE A FIRE SPRINKLER PLAN,
 FBC104.3.1.1(5), FBC503.
  
 23.) PROVIDE A COPY OF THE UNITY OF
 TITLE.
  
 24.) WHEN RESUBMITTING, INCLUDE A
 TRANSMITTAL LETTER INCLUDING HOW EACH
 ITEM WAS ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-10 Cont ID  
Sent By dpalmer Date 2004-03-10 Time 10:23 Rev Time 2.00
Received By dpalmer Date 2004-03-10 Time 07:43 Sent To  
Notes
2004-03-10 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE SEE FIRE REVIEW NOTES,
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS. (PUMP RM EM LTS.)
  
 2)NOTE: PLEASE SEE FEEDERS FROM MAIN TO
 "1HP", SHOWS #3'S ON 200A OCP. PLEASE
 SEE 310.16 FOR MIN SIZE OF CONDUCTORS.
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC.
  
 4)NOTE: PLEASE SEE THAT IT DOES APPEAR
 TO HAVE SERVICE EQUIPMENT FOR FIRE PUMP
 SHOWN ON ELECTRICAL RM PLANS.?
 RISER IS SHOWN BUT WHERE IS MAIN ETC?
 PLEASE SEE 230.72,230.76,230.79 FOR
 LOCATION OF DISC.MEANS.
 PLEASE ALSO SEE CODE REFERENCED FOR
 OCP OF FIRE PUMP. APPEARS TO BE A MIS-
 -PRINT FOR CODE #.
 PLEASE SUBMIT SPECS FOR FIRE PUMP FOR
 FIRE REVIEW.
  
 5)NOTE: PLEASE SHOW GROUNDING FOR TRANS-
 -FORMER. 250.30
  
 6)NOTE: PLEASE SEE LOCAL AMENDMENT FOR
 COLOR CODING OF 277/480V SYSTEMS.
 BR/PURP/YELLOW. PLANS SHOW DIFF ORDER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-02-27 Cont ID  
Sent By mamini Date 2004-02-27 Time 10:39 Rev Time 0.50
Received By mamini Date 2004-02-27 Time 10:39 Sent To  
Notes
2004-02-27 00:00:00PASSED:
 1. SEE PERMIT # 04021080 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-02-27 Cont ID  
Sent By mcarsill Date 2004-02-27 Time 13:30 Rev Time 0.00
Received By mcarsill Date 2004-02-27 Time 13:30 Sent To  
Notes
2004-02-27 00:00:001) WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESS REQUIRED. SIX HIGH
 NUMBERS REQUIRED.
  
 3) KNOX-BOX REQUIRED.
  
 4) ELECTRONIC SWITCHES REQUIRED ON
 FIRE LINE BACKFLOW DEVICE.
  
 5) FDC'S SHALL BE WITHIN 150 FEET OF
 A FIRE HYDRANT.
  
 6) SUITABLE ROADS ARE REQUIRED FOR
 FIRE AND PARAMEDICAL EQUIPMENT.
  
 7) NO FIRE SPRINKLER PLANS PROVIDED
 WITH DRAWINGS.
  
 8) NEW FIRE ALARM SYSTEMS SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 9) NOTES # 17 AND 19 ARE INCORRECT.
 PLEASE REVISE PLANS AS NECESSARY.
  
 10) FIRE PUMP ROOM REQUIRED EMERGENCY
 LIGHTING.
  
 11) PLEASE EXPLAIN EXITING RATIONALE
 DIRECTLY BEHIND DUMPSTER ENCLOSURE.
  
 12) PLEASE EXPLAIN SECURITY BAR NOTE
 # 3 ON PAGE M2.2.
  
 13) EXTERIOR STAIRS SHALL BE SLIP
 RESISTANT.
  
 14) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ALL TENANT IMPROVEMENT PLANS.
  
 15) PLEASE EXPLAIN PUMP ROOM AND
 STORAGE ROOM DOORS THAT OPEN ONTO
 EXIT DISCHARGE. ALSO HANDRAILS ARE
 REQUIRED ON BOT SIDES OF STAIRS.
  
 16) PLEASE PROVIDE CODE DATA BOX.
  
 17) PLEASE INDICATE FIRE EXTINGUISHER
 LOCATIONS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By shill Date 2004-04-06 Time 07:33 Rev Time 0.00
Received By shill Date 2004-02-25 Time 13:46 Sent To  
Notes
2004-02-25 00:00:00COMM BD#63

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-03-11 Cont ID  
Sent By pkrauss Date 2004-03-11 Time 09:15 Rev Time 0.40
Received By pkrauss Date 2004-03-11 Time 07:49 Sent To  
Notes
2004-03-11 00:00:00PERMIT APPLICATION INDICATES "SHELL"
 PERMIT ONLY.PLEASE PROVIDE MECHANICAL
 PLANS AND INFORMATION WITH MECHANICAL
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-06 Cont ID  
Sent By kstevens Date 2004-03-06 Time 07:23 Rev Time 1.00
Received By kstevens Date 2004-03-06 Time 07:23 Sent To  
Notes
2004-03-06 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SHTS A-6, A-8 & A-18. A-6 SHOW OVER-
 FLOW SCUPPERS 12"X20" (TYP), A-8 SHOWS
 OVERFLOW SCUPPERS 12"X12" (TYP), AND
 SHT A-18 DETAIL 3/18 SHOWS OVERFLOW
 SCUPPERS 12"X20". PLEASE CLAIRFY. -
 WILL THE SCUPPERS ON THE LOWER ROOFS BE
 SIZED AS TYPICAL?
 2) PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) FS 471.025
  
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
  
 INITIALS ARE NOT ACCEPTABLE PER A RULING
 BY THE FBPE. A COPY OF THE PLUMBING
 SHEET WILL BE PLACED ON FILE FOR REVIEW
 BY FBPE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2004-04-01 Cont ID  
Sent By mmclean Date 2004-04-01 Time 09:35 Rev Time 0.00
Received By mmclean Date 2004-04-01 Time 09:35 Sent To  
Notes
2004-04-01 00:00:00FAILED, PER DAVID KANNING PLANNER.
 1. NEED TO SUBMIT THE SITE PLAN WITH
 REVISIONS DATED 5/15/03 APPROVED BY
 RESOLUTION 276-03
 2. SUBMIT A LANDSCAPING AND PARKING PLAN
 FOR BUILDING 2
 3. SUBMIT A TRAFFIC ANALYLSIS. REFER TO
 CONDITIONS IN SECTION 1 OF RESOLUTION
 276-03.
 4. PROVIDE A UNITY OF TITLE FOR ALL
 PARCELS.
 5. PROVIDE A 12" WIDE ROADWAY EASEMENT
 ALONG THE SOUTH PROPERTY LINE ON SITE
 PLAN FOR FUTURE POSSIBLE RIGHT OF WAY
 DEDICATION.RELOCATE ANY UTILITIES IN
 NEW EASEMENT.
 6. NEED TO PROVIDE MASTER DRAINAGE PLAN,
 FINAL REVISION 3/20/03 FOR BUILDING #2
 7. NEED TO PROVIDE PLANTING PLAN FOR
 BUILDING #2 (LANDSCAPE PLAN), FINAL
 REVISION 5/15/03