Plan Review Details - Permit 04021071
Plan Review Stops For Permit 04021071
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 15:00 Rev Time 1.25
Received By alange Date 2004-04-28 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-09 Cont ID  
Sent By csiegber Date 2004-04-27 Time 15:21 Rev Time 2.50
Received By alange Date 2004-04-09 Time 11:55 Sent To  
Notes
2004-04-09 00:00:00DENIED
 1.FBC 1707.4.4.2 WINDOW BUCKS SHALL
 EXTEND BEYOND THE INTERIOR FACE OF THE
 WINDOW FRAME SUCH THAT FULL SUPPORT OF
 THE FRAME IS PROVIDED.
 SHOW THIS DETAIL ON PLAN.
  
 2.BUILDING PERMIT VALUE TOO LOW BASED
 UPON SBCCI BUILDING VALUATION DATA.
 PERMIT VALUE HAS BEEN ADJUSTED TO
 $280,729.ADDITIONAL PERMIT FEES OF
 $848.89 ARE DUE.
  
 3.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 MANY OF THE PRODUCT APPROVALS SUBMITTED
 ARE APPROVED AND THEY ONLY REQUIRE THE
 COVER SHEET.LOCAL AND SITE SPECIFIC
 APPLICATIONS ARE NOTE REQUIRED IF THESE
 PRODUCT APPROVALS ARE LISTED.
 SEE SAMPLE COVER PAGE ATTACHED.PLEASE
 REMOVE APPLICATIONS FOR SITE SPECIFIC
 PRODUCT APPROVAL IF ITS NOT REQUIRED.
  
 ANY QUESTIONS FEEL FREE TO CALL.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-01-10 Cont ID  
Sent By btrobaug Date 2005-01-10 Time 10:18 Rev Time 0.50
Received By btrobaug Date 2005-01-10 Time 09:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-12-10 Cont ID  
Sent By btrobaug Date 2004-12-10 Time 14:32 Rev Time 0.50
Received By btrobaug Date 2004-12-10 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-05-28 Cont ID  
Sent By btrobaug Date 2004-05-28 Time 10:51 Rev Time 0.50
Received By btrobaug Date 2004-05-27 Time 16:48 Sent To B
Notes
2004-05-28 00:00:00 
 TO ARTS IN BOX./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-05-27 Time 15:46 Rev Time 0.75
Received By btrobaug Date 2004-03-09 Time 13:44 Sent To M
Notes
2004-03-09 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5. SUBMIT SAME FOR REVIEW
 PRIOR TO CALLING ANY ELECTRICAL
 INSPECTIONS. ALSO PLEASE NOTE THESE MAY
 NOT BE REVIEWED IMMEDIATLY UPON
 SUBMITTING. ALLOW 2 TO 3 DAYS. SUBMIT
 THESE AS SOON AS POSSIBLE TO AVOID
 DELAYS WHEN INSPECTIONS ARE NEEDED.
 THIS INFORMATION MUST BE SUBMITTED BY
 THE DESIGN PROFESIONAL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 14:27 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 14:27 Sent To Z
Notes
2005-01-07 00:00:00TO "BT" DESK./REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-12-06 Cont ID  
Sent By mjacobs Date 2004-12-06 Time 07:53 Rev Time 0.00
Received By mjacobs Date 2004-12-06 Time 07:53 Sent To E
Notes
2004-12-06 00:00:00SENT TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-05-28 Cont ID  
Sent By csiegber Date 2004-05-28 Time 15:00 Rev Time 0.00
Received By csiegber Date 2004-05-28 Time 15:00 Sent To B
Notes
2004-05-28 00:00:00TOOK OFF AL'S DESK PASSED TO LS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-05-27 Time 15:45 Rev Time 0.00
Received By csiegber Date 2004-05-27 Time 15:45 Sent To E
Notes
2004-05-27 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-20 Cont ID  
Sent By csiegber Date 2004-05-20 Time 16:23 Rev Time 0.00
Received By csiegber Date 2004-05-20 Time 16:23 Sent To Z
Notes
2004-05-20 00:00:00REVISION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 15:21 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 15:21 Sent To B
Notes
2004-04-27 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-09 Cont ID  
Sent By mmclean Date 2004-02-25 Time 13:28 Rev Time 0.00
Received By csiegber Date 2004-02-25 Time 11:07 Sent To  
Notes
2004-03-05 00:00:003/5/04 SUBMITTALS PUT IN PACK
2004-02-26 00:00:00TO SFD RACK/E
2004-02-25 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-09 Cont ID  
Sent By btrobaug Date 2004-03-09 Time 14:26 Rev Time 0.33
Received By pkrauss Date 2004-03-09 Time 14:54 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-13 Cont ID  
Sent By pkrauss Date 2004-03-09 Time 15:17 Rev Time 0.33
Received By jleech Date 2004-03-13 Time 07:54 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-05-20 Time 16:23 Rev Time 0.00
Received By mmclean Date 2004-02-25 Time 13:28 Sent To I
Notes
***NONE***