Plan Review Details - Permit 04021070
Plan Review Stops For Permit 04021070
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-06-29 Cont ID  
Sent By alange Date 2004-06-29 Time 13:28 Rev Time 0.50
Received By alange Date 2004-06-29 Time 13:28 Sent To  
Notes
2004-06-29 00:00:00DENIED
 SEE TABLE 600 FBC NO OPENINGS PERMITTED
 FOR ZERO LOT SIDE.UNDER 3 FT. FROM
 PROPERTY LINE.
  
 SUBMIT PRODUCT APPROVAL.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:51 Rev Time 0.25
Received By alange Date 2004-06-17 Time 13:53 Sent To  
Notes
2004-06-17 00:00:00REVISION OK ONLY

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-05-18 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:49 Rev Time 2.00
Received By lsmith Date 2004-05-18 Time 07:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-05-04 Cont ID  
Sent By hmoser Date 2004-05-17 Time 17:08 Rev Time 2.50
Received By lsmith Date 2004-05-04 Time 10:05 Sent To  
Notes
2004-05-04 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 A COPY OF THE PAID RECEIIPT SUBMITTED
 TO THE CITY BEFORE A PERMIT CAN BE
 ISSUED.
  
 2. A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3. SUBMIT A SIGNED & SEALED COPY OF THE
 SOIL REPORT INCLUDING THE BORING LOG.
  
 4. HIGHLIGHT THE GLASS BLOCK BEING USED
 TO SHOW THICKNESS AND FIRE RATING.
  
 5.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT STATE PRODUCT APPROVALS AS
 REQUESTED IN FIRST REVIEW NOTES.
  
 6. BUTT GLASS SUBMITTALS STILL INCLUDED
 BUT NO BUTT GLASS SHOWN ON PLANS.
  
 7. SUBMIT MANUFACTURER'S SPECIFICATIONS
 ON GAS HOOD FOR BBQ.
  
 8. SUBMIT A SURVEY WITH THE PROPOSED
 HOUSE SHOWN AND FLOOD ZONE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-01 Cont ID  
Sent By jleech Date 2004-03-13 Time 07:13 Rev Time 3.00
Received By lsmith Date 2004-04-01 Time 13:00 Sent To  
Notes
2004-04-01 00:00:00BUILDING PLAN REVIEW FAILED:
  
 1. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 A COPY OF THE PAID RECEIPT SUBMITTED TO
 THE CITY BEFORE A PERMIT CAN BE ISSUED.
  
 2. A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3. SUBMIT A SIGNED & SEALED COPY OF THE
 SOIL REPORT INCLUDING THE BORING LOG.
  
 4. THE GLASS BLOCK IN THE EXTERIORWALL
 THAT IS WITHIN 3 FEET OF THE PROPERTY
 LINE IS REQUIRED TOHAVE
 A ONE HOUR FIRE RATING PER FBC TABLE
 600. SPECIFY ON PLANS.
  
 5. THE GLASS BLOCK AT THE TUBS IN THE
 MASTER BATH & BATH #2 IS REQUIRED TO
 HAVE A MINIMUM UNIFORM FACE THICKNESS
 OF 0.25. SEE FBC 2405.2.2 (5)
  
 6. THE WINDOW IN BATH #3 IS WITHIN 3'
 OF SHOWER IS REQUIRED TO HAVE SAFETY
 GLAZING PER 2405.2.
  
 7.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 ATWWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 SUBMIT STATE OR LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING:
 ROOF TILE
 DOUBLE INSWING ENTRY DOORS
 DOUBLE OUTSWING GLAZED DOORS WITH AND
 WITHOUT SIDELIGHTS.
 SINGLE OUTSWING PANEL DOORS
 SINGLE HUNG WINDOWS
 FIXED GLASS WINDOWS (CIRCULAR, ARCHED,
 ETC.
 GLASS BLOCK ( FIRE RATED)
 STRUCTURAL MULLIONS
 OVERHEAD GARAGE DOORS
 STORM PANELS
 TRUSS ANCHORS & CONNECTORS.
  
 8. SUBMIT MANUFACTURER'S INSTALLATION
 SPECIFICATIONS AND LISTING FOR ONE HOUR
 GLASS BLOCK ASSEMBLY.
  
 9. SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS.SPECIFY
 THE MOUNT TYPE, ANCHOR TYPE AND SPACING
 ON THE INSTALLATION DRAWINGS.
  
 10. 2 DIFFERENT PRODUCT APPROVALS (DADE
 COUNTY) WERE SUBMITTED FOR THE ROOF.
 PLEASE REMOVE ONE. A SEPARATE
 PERMIT WILL BE REQUIRED FOR THE ROOF.
  
 11. SUBMITTALS FOR BUTT GLASS WAS
 SUBMITTED.PLANS DO NOT SHOW ANY BUTT
 GLASS WINDOWS IN THIS HOUSE.
  
 12. SUBMIT 2 COPIES OF THE
 MANUFACTURER'S SPECIFICATIONS AND UL
 LISTING FOR THE GAS BBQ AND HOOD.A
 SEPARATE GAS PERMIT WILL BE REQUIRED.
  
 13. KITCHEN WINDOW DIMENSIONS NOT SHOWN
 ON PLANS. (ONLY TRANSOM SHOWN)
  
 14. THE FBC TABLE 600 CALCULATIONS FOR
 THE EXTERIOR WALL AT THE DINING ROOM AND
 DEN/STUDY ARE INCORRECT. ONLY 20% OF
 THE WALL AREA IS ALLOWED AS OPENINGS.
 PLEASE CORRECT.
  
 15. SPECIFY THE FOOTING DETAIL FOR THE
 5' WALL IN THE GARDEN COURT.
  
 16. THE STATEDVALUE OF THE HOUSE IS
 UNDERSTATED.VALUE HAS BEEN ADJUSTED
 TO $290,601. PER SBCCI BUILDING
 VALUATION DATA.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-02-23 Cont ID  
Sent By dpalmer Date 2005-02-23 Time 10:24 Rev Time 0.50
Received By dpalmer Date 2005-02-23 Time 10:24 Sent To  
Notes
2005-02-23 00:00:00REDLINED CONDUCTORS FOR SUB PANEL.
 REDLINED 2-P BRKR INSTEAD OF 1-P SHOWN.
 STAMPED OK FOR PARTIAL FINAL.
 NEED TO BRING IN REPRINTED CORRECTED
 SHEET BEFORE CO.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-02-17 Cont ID  
Sent By dpalmer Date 2005-02-17 Time 07:18 Rev Time 0.30
Received By dpalmer Date 2005-02-17 Time 07:07 Sent To  
Notes
2005-02-17 00:00:00*********UNSAT *************
  
 1)NOTE: PLEASE SEE RISER INDICATES BOTH
 PANELS AS MLO AND NO MAIN IS SHOWN?
 PLEASE SEE PLANS SHOWS A SEPARATE MAIN?
 PLEASE CORRELATE. MAIN REQUIRED
 225.31,225.32,240.4 ETC
  
 2)NOTE: PLEASE SEE RISER SHOWS SUB PANEL
 AS 60A'S YET PANEL SHOWS @ 100A'S.
 PLEASE ALSO SEE PANEL "A" SHOWS A SINGLE
 POLE 15A BRKR FEEDING PANEL "B".
 PLEASE ALSO SEE RISER INDICATES A 100A
 BRKR FEEDING THE 60A PANEL?
 PLEASE ADJUST.
  
 3)NOTE: PLEASE PANEL"A" INDICATES FOUR
 10KW AHU'S. NO COND UNITS SHOWN?
 PLEASE VERIFY AND CORRECT.
  
 4)NOTE: PLEASE SEE GFI RECEPT SPACING IN
 KITCHEN TO BE PER 210.52C1. MISSING ON
 MORE THAN ONE COUNTERSPACE.
  
 5)NOTE: PLEASE SEE 210.52D FOR GFI
 RECEPTS TO BE W/IN 3' OF BATH RM SINKS
 EDGE.
  
 6)NOTE: PLEASE SEE PLANS DO NOT INDICATE
 LOACTION OF PANEL "B".
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE SEE MISSING HALLWAY
 RECEPT PER 210.52H
  
 9)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM TO INCLUDE FOOTER STEEL PER
 250.50.
  
 ** PLEASE SEE ONE COPY OF PLANS ARE
 BEING RETAINED. PLEASE SEE OTHER COPY
 HAS MOST OF THESE ITEMS REDLINED AT
 LOCATIONS FOR ABOVE NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-05-13 Cont ID  
Sent By dpalmer Date 2004-05-13 Time 07:41 Rev Time 0.33
Received By dpalmer Date 2004-05-13 Time 07:41 Sent To M
Notes
2004-05-13 00:00:00*** NOTED ***
 220.3B4

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-04-23 Cont ID  
Sent By csiegber Date 2004-05-12 Time 16:57 Rev Time 0.75
Received By dpalmer Date 2004-04-23 Time 20:32 Sent To P
Notes
2004-04-23 00:00:00************** UNSAT 2ND TIME *********
  
 PLEASE SEE MOST COMMENTS FROM FIRST
 REVIEW HAVE NOT BEEN ADRESSED FOR CODE
 COMPLIANCE.
  
 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 2 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E PLANS SHOW TWO SEPARATE GFI
 RECEPTS FOR A/C COND UNITS??
 MISSING FRONT OF DWELLING.
  
 3 )NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLANS STILL MISSING ONES FROM FIRST
 REVIEW.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 SHOWN FOR SUB PANELS, BUT NOT FOR MAIN.
  
 5)NOTE: PLEASE SEE RISER, PLEASE SEE
 250.6, 250.24. AN EQUIPMENT GROUDING
 CONDUCTOR AS SHOWN SHALL NOT BE INSTALL-
 ED AND MUST BE REMOVED.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULES.
 THERE ARE MANY 220V/2-POLE ITEMS SHOWN
 AS 1-POLE BRKRS? MISPRINT?
  
 7)NOTE: PLEASE SEE PLANS NOW REFERENCE
 THE FBC FOR ARC FAULT PROTECTION.
 210.12 FOR ARC FAULT PROETCTION IS FROM
 THE 2002 NEC.
  
 8 )NOTE: PLEASE CORRELATE RISER DIGRAM(S
 WITH PANEL SCHEDULE(S).
 RISER SHOWS #3 FOR CONDUCTORS TO SUB
 PANEL. PLEASE INDICATE # OF #3'S.
  
 9)NOTE: PLEASE SEE NOTE #9 MENTIONS:
 ALL CONDUCTORS TO BE #12, YET PANEL
 SCHEDULES INDICATE #14'S????
  
 10)NOTE: PLEASE SEE RECEPT IN MASTERBATH
 DOES NOT MEET 210.52D.
  
 11)NOTE: PLEASE SEE FS 481.219 AND
 FAC 61G1-16.004. PLEASE INCLUDE ALL
 LICENSE #'S REQ'D IN TITLE BLOCK.
 PLEASE SEE MISSING CERTIFICATE OF AUTH-
 -ORIZATION #.
  
 12) NOTE: PLEASE SHOW LOAD CALCS AS
 REQ'D UNDER NEC 220. PLEASE SHOW ALL MIN
 CIRCUITS AND LOADS. 215.5
  
 13)NOTE: PLEASE SEE NOTICE IS NOW GIVEN
 FOR FS 553.80(2)(B).
 IF PLANS COME BACK FOR 3RD REVIEW AND
 ANY OF THE SAME COMMENTS FROM THE FIRST
 TWO REVIEWS FOR CODE COMPLIANCE ARE NOT
 ADDRESSED, A 4X FEE WILL BE ACCESSED
 FOR PLAN REVIEW PORTION.
  
 14)NOTE: PLEASE SHOW SUB PANEL "B" ON
 PLANS. ONLY PANEL "A" IS SHOWN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-01 Cont ID  
Sent By alange Date 2004-04-22 Time 14:04 Rev Time 0.75
Received By btrobaug Date 2004-03-01 Time 12:35 Sent To P
Notes
2004-03-01 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDER FROM PANEL "A" TO PANEL
 "B"ON THE RISER DIAGRAM IS 3/0 AND
 #3 ON THE PANEL SCHEDULE.PLEASE
 CORRELATE.
  
 2} PANEL "B"IS MARKED PANEL"A" ON THE
 RISER DIAGRAM.
  
 3} PLEASE NOTE THAT THE SMOKE DETECTORS
 MUST BE ON AN ARC FAULT BREAKER PER
 210.12, SEE DEFINITION OF OUTLETS" IN
 ARTICLE 100 NEC.
  
 4} THE RECEPTACLE IN THE MASTER BATH
 DOES NOT COMPLY WITH 210.52(D),IT'S
 MORE THAN 3' FROM THE BASIN.
  
 5} THERE ARE 2 PLACES ON THE KITCHEN
 COUNTERTOP THAT NEED ANOTHER
 RECEPTACLE PER 210.52(C)(1).
  
 6} THE ISLAND IN THE KITCHEN NEEDS A
 RECEPTACLE PER 210.52(C)(2).
  
 7) THE LOCATION OF THE A/C DISCONNECTS
 DO NOT COMPLY WITH 110.26 FOR CLEARANCE.
  
 8} A RECEPTACLE AT THE FRONT OF THE
 DWELLING MUST BE ADDED PER 210.52(E).
  
 9} PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 ONE SET OF THE PLANS SUBMITTED HAVE BEEN
 REVIEWED AND CODE ARTICLES PER COMMENTS
 ARE MARKED ON THE PLANS. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-02-15 Cont ID  
Sent By adarroug Date 2005-02-15 Time 14:36 Rev Time 0.00
Received By adarroug Date 2005-02-15 Time 14:36 Sent To P
Notes
2005-02-15 00:00:00TO P BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-02-11 Cont ID  
Sent By adarroug Date 2005-02-11 Time 10:45 Rev Time 0.00
Received By adarroug Date 2005-02-11 Time 10:45 Sent To E
Notes
2005-02-11 00:00:00TO DPALMER DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-12-20 Cont ID  
Sent By mjacobs Date 2004-12-20 Time 15:44 Rev Time 0.00
Received By mjacobs Date 2004-12-20 Time 15:44 Sent To G
Notes
2004-12-20 00:00:00SENT TO "GAS" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:51 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 12:51 Sent To B
Notes
2004-06-25 00:00:00TO AL DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 10:49 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 10:49 Sent To B
Notes
2004-06-11 00:00:00TO LS DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-05-12 Cont ID  
Sent By csiegber Date 2004-05-12 Time 16:57 Rev Time 0.00
Received By csiegber Date 2004-05-12 Time 16:57 Sent To E
Notes
2004-05-12 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 14:04 Rev Time 0.00
Received By alange Date 2004-04-22 Time 14:04 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-20 Cont ID  
Sent By mmclean Date 2004-04-21 Time 11:26 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 12:33 Sent To Z
Notes
2004-04-20 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-20 Time 12:27 Rev Time 0.00
Received By csiegber Date 2004-02-24 Time 11:54 Sent To  
Notes
2004-02-25 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-05-17 Cont ID  
Sent By hmoser Date 2004-05-17 Time 17:19 Rev Time 0.50
Received By hmoser Date 2004-05-17 Time 17:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-05-17 Cont ID  
Sent By dpalmer Date 2004-05-13 Time 07:41 Rev Time 0.35
Received By hmoser Date 2004-05-03 Time 16:16 Sent To B
Notes
2004-05-03 00:00:00DENIED:
 2ND REQUEST:
 1.PROVIDE ENERGY AND MANUAL J
 CALCULATIONS PER 2001 FBC CHAPTER 13.
  
 1ST REQUEST:
 1.BEDROOM #2 MISSING RETURN AIR DUCT
 & GRILLE SIZE & LAYOUT.
  
 2.SUPPLY DUCT TO BEDROOM #3 IS NOT
 SIZED.PLEASE REVISE.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2 OR 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-02-28 Cont ID  
Sent By hmoser Date 2004-02-28 Time 13:25 Rev Time 0.25
Received By hmoser Date 2004-02-28 Time 13:24 Sent To E
Notes
2004-02-28 00:00:00MECHANICAL CONTRACTOR MUST SUBMIT
 MANUAL (J) ENERGY CALCULATIONS AND PLANS
 AT TIME OF APPLICATION
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-02-26 Cont ID  
Sent By jleech Date 2005-02-26 Time 08:59 Rev Time 0.50
Received By jleech Date 2005-02-26 Time 08:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-03 Cont ID  
Sent By dpalmer Date 2004-04-23 Time 20:38 Rev Time 1.50
Received By pschmitz Date   Time   Sent To M
Notes
2004-05-03 00:00:00PROVISO: PLUMBING, GAS PLAN REVIEW.
 SHT P-1 SEE RED LINED ITEMS, PLUMBING
 PLAN VIEW.
 SHT P-1 GAS, SEPERATE PLANS & PERMIT,NO
 PIPING SHOWN.
 QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-13 Cont ID  
Sent By btrobaug Date 2004-03-01 Time 14:20 Rev Time 0.50
Received By jleech Date 2004-03-13 Time 07:13 Sent To B
Notes
2004-03-13 00:00:00DENIED;
 ARCHITECTS SIGNITURE IS REQUIRED ON SEAL
 PER 61G116.003.
 PLUMBING DRAWINGS ARE NOT TO CODE. SEE
 SEE RED COMMENTS MARKED ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-21 Cont ID  
Sent By mmclean Date 2004-04-21 Time 11:26 Rev Time 0.00
Received By mmclean Date 2004-04-21 Time 11:26 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-04-20 Time 12:33 Rev Time 0.00
Received By mmclean Date 2004-02-24 Time 13:01 Sent To I
Notes
2004-02-24 00:00:00DENIED, SIDE ENTRY GARAGE SHOULD BE 15FT
 CALLED PETER (PERMIT RUNNER)