Plan Review Details - Permit 04021067
Plan Review Stops For Permit 04021067
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-12 Cont ID  
Sent By rmcdouga Date 2004-05-12 Time 16:27 Rev Time 0.00
Received By rmcdouga Date 2004-05-12 Time 16:27 Sent To  
Notes
2004-05-12 00:00:00BUILDING PROVISO
  
 1) SUBMIT STATE/LOCAL PRODUCT APPROVAL
 FOR HORIZONTAL SLIDING WINDOW WITH
 HEIGHT OF 72".
  
 2) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE STORM PANELS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-27 Time 15:17 Rev Time 2.00
Received By rmcdouga Date 2004-04-06 Time 12:53 Sent To  
Notes
2004-04-06 00:00:00DENIED
  
 1) THE HORIZONTAL SLIDING WINDOWS IN THE
 BREAKFAST AREA EXCEED THE MAXIMUM HEIGHT
 LISTED IN THE PRODUCT APPROVAL THAT WAS
 SUBMITTED. SUBMIT APPROPRIATE PRODUCT
 APPROVALS.
  
 2) THE LAWSON PRODUCTS HAVE STATE
 PRODUCT APPROVALS WITH APPROVED STATUS.
 SITE SPECIFIC PRODUCT APPROVALS ARE NO
 LONGER NECESSARY FOR THEM. PLEASE SUBMIT
 THE APPROPRIATE STATE PRODUCT APPROVAL
 COVER SHEET AND CORRESPONDING NOA.
  
 NOTE: THE SITE SPECIFIC PRODUCT APPROVAL
 FORM HAS BEEN REVISED. THE PROJECT
 LOCATION IS REQUIRED. THE CATEGORY OF
 PRODUCT AND APPROVAL METHOD IS REQUIRED
 ON THE FORM.
  
 3) THE PITTSBURG GLASS BLOCK ALSO HAS
 APPROVED STATE PRODUCT APPROVAL. SUBMIT
 STATE PRODUCT APPROVAL COVER AND NOA.
  
 4) SUBMIT THE PROPER APPLICATION FOR
 LOCAL PRODUCT APPROVAL FOR THE A&P
 CUSTOM FIXED WINDOWS. IF THE SITE
 SPECIFIC FORM IS USED THE PROJECT
 LOCATION IS REQUIRED TO BE LISTED ON THE
 FORM. SEE NEW FORMS ATTACHED.
  
 5) STORM PANELS WILL REQUIRE A SEPARATE
 PERMIT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-01-10 Cont ID  
Sent By btrobaug Date 2005-01-10 Time 09:05 Rev Time 0.50
Received By btrobaug Date 2005-01-10 Time 08:16 Sent To  
Notes
2005-01-10 00:00:00 
 THE PLANS SUBMITTED FOR REVIEW DO NOT
 MATCH THE APPROVED SET OF PLANS ON FILE
 FOR RECORD.
  
 PLEASE CHECK YOUR RECORDS AND SUBMIT THE
 CORRECT SE FOR REVIEW.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-12 Cont ID  
Sent By btrobaug Date 2004-10-12 Time 17:52 Rev Time 0.50
Received By btrobaug Date 2004-10-12 Time 17:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-09 Cont ID  
Sent By csiegber Date 2004-10-06 Time 09:55 Rev Time 0.50
Received By btrobaug Date 2004-03-09 Time 13:41 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-01-07 Cont ID  
Sent By mjacobs Date 2005-01-07 Time 14:25 Rev Time 0.00
Received By mjacobs Date 2005-01-07 Time 14:25 Sent To E
Notes
2005-01-07 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-10-06 Cont ID  
Sent By csiegber Date 2004-10-06 Time 09:55 Rev Time 0.00
Received By csiegber Date 2004-10-06 Time 09:55 Sent To E
Notes
2004-10-06 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-04-27 Time 15:17 Rev Time 0.00
Received By csiegber Date 2004-04-27 Time 15:17 Sent To B
Notes
2004-04-27 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-02-25 Time 13:22 Rev Time 0.00
Received By rmcdouga Date 2004-02-25 Time 11:06 Sent To  
Notes
2004-02-26 00:00:00TO SFD RACK/E
2004-02-25 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-29 Cont ID  
Sent By pkrauss Date 2004-03-29 Time 14:33 Rev Time 0.20
Received By pkrauss Date 2004-03-29 Time 14:33 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By btrobaug Date 2004-03-09 Time 13:41 Rev Time 0.33
Received By pkrauss Date 2004-03-09 Time 15:31 Sent To P
Notes
2004-03-09 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER SUITE
 IS NOT SIZED PROPERLY.ALL AIR INTO THE
 MASTER SUITE (BATHROOM, CLOSET, ETC) TO
 BE INCLUDED FOR THE "TOTAL" SUPPLY AIR
 INTO THE SUITE.PLEASE REVISE RETURN
 AIR JUMPER TO REFLECT THIS CALCUALTION.
 SEE THE ATTACHED SCHEDULE FOR PROPER
 SIZING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-13 Cont ID  
Sent By pkrauss Date 2004-03-09 Time 15:41 Rev Time 0.33
Received By jleech Date 2004-03-13 Time 08:54 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-25 Cont ID  
Sent By mmclean Date 2004-02-25 Time 13:22 Rev Time 0.00
Received By mmclean Date 2004-02-25 Time 13:22 Sent To I
Notes
***NONE***