Plan Review Details - Permit 04021066
Plan Review Stops For Permit 04021066
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-07-26 Cont ID  
Sent By alange Date 2004-07-26 Time 16:24 Rev Time 0.66
Received By alange Date 2004-07-26 Time 16:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-07-23 Cont ID  
Sent By csiegber Date 2004-07-26 Time 15:57 Rev Time 1.00
Received By alange Date 2004-07-23 Time 15:55 Sent To  
Notes
2004-07-23 00:00:00DENIED
 SAME COMMENT 5TH REVIEW:
  
 PRODUCT APPROVAL FOR TOWN AND COUNTRY
 SHUTTERS STILL MISSING STATE APPROVAL
 COVER SHEET.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-22 Time 12:46 Rev Time 0.75
Received By alange Date 2004-07-21 Time 11:32 Sent To  
Notes
2004-07-21 00:00:00DENIED
 THIS IS THE 5TH REPETITIVE COMMENT
 FOR PRODUCT APPROVALS.
 I SORTED THROUGH THE STATE APPROVALS YOU
 SUBMITTED AND ATTACHED THEM TO THE
 PRODUCT APPROVALS.
 I AM STILL MISSING 8 COMPLETED SETS WITH
 STATE APPROVALS AND AM MISSING ALL
 APPROVALS FOR SIMPSON FASTENERS USED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-19 Time 17:07 Rev Time 0.66
Received By alange Date 2004-07-16 Time 12:50 Sent To  
Notes
2004-07-21 00:00:00DENIED
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
2004-07-16 00:00:00DENIED
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-15 Cont ID  
Sent By alange Date 2004-07-15 Time 08:35 Rev Time 1.00
Received By alange Date 2004-07-15 Time 08:35 Sent To  
Notes
2004-07-15 00:00:00DENIED
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.PRODUCT APPROVALS:ONE COPY OF
 ROOFING PRODUCT APPROVALS MISSING.
 SUBMIT TWO COPIES OF TRUSS CONNECTOR
 PRODUCT APPROVALS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 4.ADDITIONAL PERMIT FEES ARE STILL DUE
 $124.54.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-17 Cont ID  
Sent By btrobaug Date 2004-07-14 Time 15:00 Rev Time 1.75
Received By alange Date 2004-06-17 Time 10:27 Sent To  
Notes
2004-06-17 00:00:00DENIED
 COMMENTS NOT ADDRESSED FROM FIRST REVIEW
  
 1. BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2. PROVIDE AT LEAST ONE BATHROOM WITH
 A DOOR THAT HAS A 29 INCH CLEAR OPENING
 AS REQUIRED.A 32" WIDE DOOR IS NEEDED.
  
 3.PRODUCT APPROVALS:
 1 COPY OF ROOF PRODUCT APPROVALS MISSING
 GARAGE OVERHEAD DOOR PRODUCT APPROVAL
 MISSING.NO TRUSS CONNECTOR PRODUCT
 APPROVAL SUBMITTED.
 BUTT GLASS PRODUCT APPROVAL SUBMITTED
 BUT NOT SHOWN ON PLAN.
  
 4. BASED ON SBCCI BUILDING VALUATION
 DATA THE REVISED VALUE IS $287,331
 ADDITIONAL PERMIT FEES OF $124.54 ARE
 DUE.
  
 5.SUBMIT SIGNED AND SEALED COPY OF
 SOIL REPORT.
  
 6. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-31 Cont ID  
Sent By btrobaug Date 2004-06-14 Time 09:03 Rev Time 3.00
Received By lsmith Date 2004-03-31 Time 15:05 Sent To  
Notes
2004-03-31 00:00:00BUILDING PLANS REVIEW: FAILED
  
 1. BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALMBEACH COUNTY.THE ACTUAL PERMIT
 PLANS
 MUST BE STAMPED BY THAT OFFICE, AND A
 COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.PLEASE CALL
 (561) 233-5025 FOR MORE INFORMATION.
  
 2. PROVIDE AT LEAST ONE BATHROOM WITH
 DOOR THAT HAS A 29 INCH CLEAR OPENING,
 AS REQUIRED BY THE 1997 FLORIDA
 BUILDING CODE CHAPTER 11. A 32" WIDE
 DOOR IS NEEDED.
  
 3. TWO PRODUCT APPROVALS FOR THE ROOF
 TILE WAS SUBMITTED. PLEASE CLARIFY
 WHICH ONE IS BEING USED.ALSO NEED
 FLORIDA PRODUCT APPROVAL FOR ROOF TILE.
  
 4. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 ATWWW.FLORIDABUILDING.ORG. PRODUCTS
 WITHSTATEWIDE APPROVAL ARE REQUIRED TO
 BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG. SUBMIT PRODUCT
 APPROVAL FOR THE FOLLOWING:
 GLASS BLOCK
 SINGLE HUNG WINDOWS
 FIXED WINDOWS
 ARCHED TOP WINDOWS, TRANSOM, ETC.
 MULLIONS
 OVERHEAD GARAGE DOORS
 DOUBLE INSWING ENTRY DOOR
 SINGLE OUTSWING PANEL DOOR
 SLIDING GLASS DOORS
 TRUSS CONNECTORS
 HURRICANE PANELS.
 THE APPROPRIATE DADE COUNTY OR SBCCI
 APPROVALS MUST ACCOMPANY THE FLORIDA
 APPROVALS.
  
 5. SUBMIT KEY PLAN AND INSTALLATION
 SCHEDULES FOR HURRICANE PANELS.
 SPECIFY THE MOUNT TYPE, FASTENER TYPE
 AND SPACING.
  
 6. SUBMIT INFORMATION FOR GAS BBQ. MFGR
 SPECS.
  
 7. THE VALUE OF THE HOUSE IS
 UNDERSTATED ACCORDING TO SBCCI BUIDING
 VALUATION THE NEW VALUE IS:$287,331.
  
 8. SUBMIT THE MEASUREMENTS FOR THE
 GLASSBLOCK SHOWN ON THE RIGHT ELEVATION.
  
 9. SUBMIT A SIGNED & SEALED COPY OF THE
 SOILREPORT.
  
 10. A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE ROOF.
  
 11. SUBMITALS FOR A BUTT GLASS BAY
 WINDOW WAS INCLUDED BUT PLANS DO NOT
 SHOW A BAY WINDOW IN THIS HOUSE.
  
 12. A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE FILED AT THE
 COUNTY CLERKS OFFICE AND A COPY
 SUBMITTED BEFORE A PERMIT CAN BE ISSUED.
  
 13. THE WINDOW IN BATH #3 IS WITHIN 3'
 OF SHOWER AND MUST HAVE SAFETY GLAZING
 PER FBC 2405.2.
  
 14. THE WINDOWS IN THE TUB/SHOWER BATH
 AND THE MASTER BATH MUST HAVE SAFETY
 GLAZING.
  
 15. SHOW SIZE OF ATTIC ACCESS ON PLANS.
  
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-06-08 Cont ID  
Sent By btrobaug Date 2005-06-08 Time 17:17 Rev Time 0.50
Received By btrobaug Date 2005-06-08 Time 16:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-05-06 Cont ID  
Sent By btrobaug Date 2005-05-06 Time 07:41 Rev Time 0.50
Received By btrobaug Date 2005-05-06 Time 07:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-07-14 Cont ID  
Sent By btrobaug Date 2004-07-14 Time 15:00 Rev Time 0.50
Received By btrobaug Date 2004-07-14 Time 14:42 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-14 Cont ID  
Sent By jleech Date 2004-07-13 Time 17:28 Rev Time 0.75
Received By btrobaug Date 2004-06-14 Time 07:11 Sent To B
Notes
2004-06-14 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} BEDROOM #2 NEEDS A RECEPTACLE TO
 COMPLY WITH 210.52(A)(2).
  
 2} A SMOKE DETECTOR IS REQUIRED OUTSIDE
 BEDROOM #3 PER 8-1.4.1.6.2(1) NFPA-72.
  
 3} THE DISCONNECT LOCATION FOR CU #2
 STILL WILL NOT COMPLY WITH 110.26
 CLEARANCE DUE TO THE WALL LOCATION
 ENCLOSING THE UNITS.
  
 4} THE ARCHITECTS AA NUMBER IN THE TITLE
 BLOCK IS NOT LISTED WITH THE DBPR.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-06-08 Time 15:20 Rev Time 0.50
Received By btrobaug Date 2004-03-01 Time 09:51 Sent To P
Notes
2004-03-01 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER DIAGRAM INDICATES #3/0
 FEEDERS TO THE 100 AMP PANEL(MARKED
 "A"ON THE RISER) AND #3'S ON THE PANEL
 SCHEDULE, PLEASE CORRELATE.
  
 2} THE "BREAKFAST" AND "BEDROOM #3 NEED
 RECEPTACLES ADDED TO COMPLY WITH
 210.52(A)(2).
  
 3} THE KITCHEN COUNTERTOP NEEDS A
 RECEPTACLE TO COMPLY WITH 210.52(C)(1).
  
 4} THE GUEST BEDROOM(LABLED BEDROOM#3
 ON ELECTRICAL PLAN) NEEDS A SMOKE
 DETECTOR IN THE HALLWAY OUTSIDE IN THE
 "IMMIDIATE VICINITY" TO COMPLY WITH
 8-1.4.1.6.2 NFPA-72.
  
 5} THE A/C DISCONNECT LOCATIONS DO NOT
 COMPLY WITH 110.26.
  
 6} PLEASE SEE 210.12 WHICH INDICATES
 THAT THE SMOKE DETECTORS MUST ALSO BE
 ARC FAULT PROTECTED.SEE THE DEFINITION
 OF "OUTLET" IN ARTICLE 100,NEC.
  
 ALL OF THE ABOVE CORRECTIONS ARE MARKED
 ON ONE SET OF REVIEWED PLANS FOR
 REFERENCE. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 PLEASE NOTE THAT THE ARCHITECTS
 SIGNATURE IS REQUIRED ON HIS/HER SEAL
 PER 61G116.003.INITIALS ARE NOT
 ACCEPTABLE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 10:20 Rev Time 0.00
Received By shill Date 2005-06-08 Time 10:20 Sent To E
Notes
2005-06-08 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 08:20 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 08:20 Sent To P
Notes
2005-06-01 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-05-25 Cont ID  
Sent By adarroug Date 2005-05-25 Time 14:00 Rev Time 0.00
Received By adarroug Date 2005-05-25 Time 14:00 Sent To P
Notes
2005-05-25 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-04-29 Cont ID  
Sent By adarroug Date 2005-04-29 Time 11:22 Rev Time 0.00
Received By adarroug Date 2005-04-29 Time 11:22 Sent To E
Notes
2005-04-29 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 15:57 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 15:57 Sent To B
Notes
2004-07-26 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-07-22 Cont ID  
Sent By csiegber Date 2004-07-22 Time 12:45 Rev Time 0.00
Received By csiegber Date 2004-07-22 Time 12:45 Sent To B
Notes
2004-07-22 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-07-19 Cont ID  
Sent By csiegber Date 2004-07-19 Time 17:07 Rev Time 0.00
Received By csiegber Date 2004-07-19 Time 17:07 Sent To B
Notes
2004-07-19 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-16 Cont ID  
Sent By ptjomsto Date 2004-07-16 Time 12:03 Rev Time 0.00
Received By ptjomsto Date 2004-07-16 Time 12:03 Sent To  
Notes
2004-07-16 00:00:003RD RESUB GIVEN TO ART LANGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-25 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:53 Rev Time 0.00
Received By csiegber Date 2004-06-25 Time 12:53 Sent To M
Notes
2004-06-25 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-08 Cont ID  
Sent By csiegber Date 2004-06-08 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-06-08 Time 15:20 Sent To E
Notes
2004-06-08 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-07 Cont ID  
Sent By mmclean Date 2004-06-08 Time 12:46 Rev Time 0.00
Received By csiegber Date 2004-06-07 Time 09:55 Sent To Z
Notes
2004-06-07 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-31 Cont ID  
Sent By csiegber Date 2004-05-06 Time 16:47 Rev Time 0.00
Received By csiegber Date 2004-02-24 Time 11:54 Sent To  
Notes
2004-02-25 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-06-30 Cont ID  
Sent By pkrauss Date 2004-06-30 Time 15:03 Rev Time 0.30
Received By pkrauss Date 2004-06-30 Time 15:03 Sent To P
Notes
2004-06-30 00:00:00PROVISO:
 1. RETURN AIR REQUIRED FROM THE DEN
 AREA PER 2001 FBC(M) 601.4.
  
 2. AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2004-02-28 Cont ID  
Sent By csiegber Date 2004-06-25 Time 12:53 Rev Time 0.25
Received By hmoser Date 2004-02-28 Time 13:13 Sent To E
Notes
2004-02-28 00:00:00MECHANICAL CONTRACTOR MUST SUBMIT
 ENERGY CALCELATIONS,MANUAL (J) AND PLANS
 WHEN THEY SUBMIT APPLICATION
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2005-06-13 Cont ID  
Sent By jleech Date 2005-06-13 Time 13:07 Rev Time 0.33
Received By jleech Date 2005-06-13 Time 13:07 Sent To  
Notes
2005-06-13 00:00:00PLUMBING REVISION OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-07-13 Cont ID  
Sent By jleech Date 2004-07-13 Time 17:27 Rev Time 0.33
Received By jleech Date 2004-07-13 Time 17:27 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-03-13 Cont ID  
Sent By pkrauss Date 2004-06-30 Time 15:04 Rev Time 0.50
Received By jleech Date 2004-03-13 Time 07:37 Sent To B
Notes
2004-03-13 00:00:00DENIED;
 1.ARCHITECTS SIGNATURE REQUIRED.
 2.PLUMBING CODE VIOLATIONS SEE PLUMBING
 DRAWINGS. VIOLATIONS MARKED IN RED.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2004-06-08 Cont ID  
Sent By mmclean Date 2004-06-08 Time 12:43 Rev Time 0.00
Received By mmclean Date 2004-06-08 Time 12:43 Sent To I
Notes
2004-06-08 00:00:00APPROVED BY GRACE JOYCE, PLANNER
 659-8031

Review Stop Z ZONING
Rev No 1 Status F Date 2004-02-24 Cont ID  
Sent By csiegber Date 2004-06-07 Time 09:55 Rev Time 0.00
Received By mmclean Date 2004-02-24 Time 13:05 Sent To I
Notes
2004-02-24 00:00:00DENIED, SIDE LOAD GARAGE SHOULD BE 15FT
 CALLED PETER (PERMIT RUNNER)