| 2004-05-19 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04021048 |
| | ADD: 3031 OKEECHOBEE BLVD |
| | CONT: POPPER & ASSOCIATES |
| | TEL: (561)719-7133 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMMENT# 1 FROM PREVIOUS REVIEW: |
| | ADDITIONAL INFO ON THE WAYNE DAWSON |
| | ROLL UP DOOR. |
| | THE INFORMATION PROVIDED HAS DESCREPAN- |
| | CIES, THE FIRST SUBITTAL IS FOR OVERHEAD |
| | GARAGE DOOR(FIRE RATED) SERIES 640 OR |
| | 641. THE SECOND IS A MIAMI-DADE NOA FOR |
| | A EXTERIOR GARGE DOOR SERIES 610/620, |
| | THE THIRD IS FOR WAYNE DALSON SERIES |
| | AKBAR 89. NONE OF THESE SUBMITTALS ACT- |
| | UALLY SPELL OUT WHAT RATING IS TO BE |
| | USED. THE COVERSHEET INDICATES A SEPERAT |
| | ION FROM THE SHOWROOMWITH THE PARTS |
| | STORAGE. FOR S2 STORAGE A 2 HR WALL AND |
| | 1 1/2 HR OPENING PROTECTIVES REQUIRED. |
| | SUBMIT THE ACTUAL UNIT TO BE INSTALLED! |
| | |
| | THE SECOND ISSUE WITH THIS ISSUE IS THE |
| | DETAIL-1, THE ROLL DOWN DOOR ASSUMED TO |
| | BE 1 1/2 HR RATED IS TO SEAL AGAINST THE |
| | NEW COUNTERTOP, WHICH IS (2) LAYERS OF |
| | PLYWOOD SEE 709.6.2A,5/8" PLYWOOD IS ASS |
| | IGNED A TIME OF 15 MIN. EVEN IF WE WENT |
| | WITH 20 MIN FOR 3/4" TWO LAYERS STILL IS |
| | GOOD FOR 40 MINUTES? |
| | |
| | 2) COMMENT "F" FROM PREVIOUS REVIEW DEAL |
| | S WITH THE EXITING OF THE 2ND FLOOR. |
| | THE ANSWER WAS , EXITING NOT AFFECTED BY |
| | THE GOING THROUGH THE FLOOR. |
| | THE XEROX SUBMITTAL ARE NOT FOR THE |
| | 2ND FLOOR BUT THE FIRST FLOOR. THE AREA |
| | WHERE THE FLOOR IS CUT AWAY MAY AFFECT |
| | TRAVEL DISTANCES TO EXITING FOR THE |
| | SECOND FLOOR THIS IS WHY THE REQUEST WAS |
| | MADE AND STILL REMAINS A UNANSWERED QUES |
| | TION? |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |