Plan Review Details - Permit 04021037
Plan Review Stops For Permit 04021037
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-07 Cont ID  
Sent By jwitmer Date 2004-04-07 Time 13:14 Rev Time 1.33
Received By jwitmer Date 2004-04-07 Time 12:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-19 Cont ID  
Sent By jwitmer Date 2004-03-19 Time 12:43 Rev Time 3.00
Received By jwitmer Date 2004-03-19 Time 12:43 Sent To PC
Notes
2004-03-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021037
 ADD: 326 FERN ST# 301
 CONT: CATALFUMO
 TEL: (561)307-4836
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE OCCUPANCY IS CORRECT AS BUSINESS
 BUT THE CONFRENCE ROOM IS CONSIDERED TO
 BE ASSEMBLY AS FAR AS OCCUPANT LOAD.
 CONFERENCE ROOMS USE 15 NET, THE OCCU-
 PANT LOAD FOR THIS ROOM IS 71.DOOR 317 &
 318 NEED TO HAVE THE DOOR SWING REVERSED
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE, DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS.
  
 2) THIS SAME ISSUE WILL ALSO HOLD TRUE
 FOR THE MOVED DOORS#300 & 306,
 REVERSE SWING IN THE DIRECTION OF
 TRAVEL.
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-14 Cont ID  
Sent By dpalmer Date 2004-04-14 Time 11:37 Rev Time 1.00
Received By dpalmer Date 2004-04-14 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 16:05 Rev Time 1.00
Received By dpalmer Date 2004-03-05 Time 15:26 Sent To  
Notes
2004-03-05 00:00:00******** UNSAT ************
  
 1)NOTE: CIRCUITS FOR RECEPTS ARE
 SHOWN 3OR SO PER GROUP. PLEASE PROVIDE
 NOTE, TO MAX AMOUNT PER CIRCUIT.
  
 2)NOTE: PLEASE SEE ELECTRICAL PLANS,
 PLANS DO NOT INDICATE/SHOW ELECTRICAL
 PANEL/TRANSFORMER LOCATION. PLEASE
 SHOW LOCATION OF ELECTRICAL ROOM.
 IS THIS LOCATION ACCROSS HALL AS SHOWN
 ON ARCH? PLEASE SHOW EQUIPMENT ON LAYOUT
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC.
  
 PLEASE VERIFY LOAD ON EXSITNG SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-03-26 Cont ID  
Sent By mcarsill Date 2004-03-26 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2004-03-26 Time 16:14 Sent To  
Notes
2004-03-26 00:00:00OKAY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-02-25 Cont ID  
Sent By nmccray Date 2004-02-25 Time 12:18 Rev Time 0.00
Received By nmccray Date 2004-02-25 Time 12:18 Sent To  
Notes
2004-02-25 00:00:00********DENIED**************************
 1) THE TWO EXIT DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL.
  
 2) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS REMODEL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 14:34 Sent To  
Notes
2004-03-25 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-19 Cont ID  
Sent By jwitmer Date 2004-03-19 Time 13:12 Rev Time 0.00
Received By jwitmer Date 2004-02-25 Time 10:27 Sent To PC
Notes
2004-02-25 00:00:00TO COMM BD#22

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-09 Cont ID  
Sent By pkrauss Date 2004-03-09 Time 10:04 Rev Time 0.45
Received By pkrauss Date 2004-03-09 Time 09:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-06 Cont ID  
Sent By kstevens Date 2004-03-06 Time 06:06 Rev Time 0.33
Received By kstevens Date 2004-03-06 Time 06:05 Sent To  
Notes
2004-03-06 00:00:00PASSED/PROVISO
  
 LOCATE WATER HAMMER ARRESTOR NEAR THE
 FIXTURE. PDI-WH 201 & MANUF. INSTALL.
 INSTRUCTIONS.