| Plan Review Stops For Permit 04021037 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-04-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-04-07 |
Time |
13:14 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2004-04-07 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-03-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-03-19 |
Time |
12:43 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2004-03-19 |
Time |
12:43 |
Sent To |
PC |
|
| Notes |
| 2004-03-19 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04021037 | | | ADD: 326 FERN ST# 301 | | | CONT: CATALFUMO | | | TEL: (561)307-4836 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) THE OCCUPANCY IS CORRECT AS BUSINESS | | | BUT THE CONFRENCE ROOM IS CONSIDERED TO | | | BE ASSEMBLY AS FAR AS OCCUPANT LOAD. | | | CONFERENCE ROOMS USE 15 NET, THE OCCU- | | | PANT LOAD FOR THIS ROOM IS 71.DOOR 317 & | | | 318 NEED TO HAVE THE DOOR SWING REVERSED | | | 1012.1.2 EGRESS DOORS SHALL BE SIDE | | | SWINGING TYPE, DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS. | | | | | | 2) THIS SAME ISSUE WILL ALSO HOLD TRUE | | | FOR THE MOVED DOORS#300 & 306, | | | REVERSE SWING IN THE DIRECTION OF | | | TRAVEL. | | | | | | 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-04-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-14 |
Time |
11:37 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-04-14 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-03-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-03-05 |
Time |
16:05 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2004-03-05 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2004-03-05 00:00:00 | ******** UNSAT ************ | | | | | | 1)NOTE: CIRCUITS FOR RECEPTS ARE | | | SHOWN 3OR SO PER GROUP. PLEASE PROVIDE | | | NOTE, TO MAX AMOUNT PER CIRCUIT. | | | | | | 2)NOTE: PLEASE SEE ELECTRICAL PLANS, | | | PLANS DO NOT INDICATE/SHOW ELECTRICAL | | | PANEL/TRANSFORMER LOCATION. PLEASE | | | SHOW LOCATION OF ELECTRICAL ROOM. | | | IS THIS LOCATION ACCROSS HALL AS SHOWN | | | ON ARCH? PLEASE SHOW EQUIPMENT ON LAYOUT | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3,230.42 ETC. | | | | | | PLEASE VERIFY LOAD ON EXSITNG SERVICE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-03-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-03-26 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-03-26 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2004-03-26 00:00:00 | OKAY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-02-25 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-02-25 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-02-25 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2004-02-25 00:00:00 | ********DENIED************************** | | | 1) THE TWO EXIT DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS TRAVEL. | | | | | | 2) SEPARATE PLANS AND PERMITS ARE | | | REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM SYSTEMS REMODEL. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-03-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-25 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-25 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2004-03-25 00:00:00 | TO COMM BD#54 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-03-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-03-19 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2004-02-25 |
Time |
10:27 |
Sent To |
PC |
|
| Notes |
| 2004-02-25 00:00:00 | TO COMM BD#22 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-03-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-03-09 |
Time |
10:04 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2004-03-09 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-03-06 |
Time |
06:06 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-03-06 |
Time |
06:05 |
Sent To |
|
|
| Notes |
| 2004-03-06 00:00:00 | PASSED/PROVISO | | | | | | LOCATE WATER HAMMER ARRESTOR NEAR THE | | | FIXTURE. PDI-WH 201 & MANUF. INSTALL. | | | INSTRUCTIONS. |
|
|