Plan Review Details - Permit 04021011
Plan Review Stops For Permit 04021011
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-06-21 Cont ID  
Sent By rmcdouga Date 2004-06-03 Time 14:41 Rev Time 1.00
Received By rmcdouga Date 2004-06-03 Time 14:41 Sent To  
Notes
2004-06-03 00:00:00DENIED
  
 1) THE DIMENSIONS ON THE SITE SPECIFIC
 DRAWINGS DO NOT CORRESPOND WITH THE
 PLANS.
  
 2) THE ARCHITECTURAL PLANS DO NOT
 SPECIFY A BUTT GLASS ASSEMBLY AT THE
 LIVING ROOM WINDOW. PLANS WILL NEED TO
 BE REVISED.
  
 3) BUTT GLASS ASSEMBLIES ARE LARGER THAN
 TESTED UNIT. SUBMIT SIGNED AND SEALED
 CALCULATIONS. SUBMIT SIGNED AND SEALED
 TEST REPORTS. SITE SPECIFIC UNITS ARE
 REQUIRED TO BE INSPECTED BY THE ENGINEER
 WHEN THEY ARE INSTALLED. SUBMIT A SIGNED
 AND SEALED LETTER FROM THE ENGINEER
 STATING THAT HE WILL INSPECT THE
 INSTALLATION OF THE BUTT GLASS WINDOWS.
 A SIGNED AND SEALED LETTER FROM THE
 ENGINEER STATING THAT THE BUTT GLASS
 WINDOW ASSEMBLIES HAVE BEEN INSTALLED TO
 HIS SPECIFICATIONS WILL BE REQUIRED
 BEFORE THE CO IS ISSUED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-06-03 Cont ID  
Sent By rmcdouga Date 2004-06-03 Time 14:28 Rev Time 1.00
Received By rmcdouga Date 2004-06-03 Time 14:28 Sent To  
Notes
2004-06-03 00:00:00DENIED
  
 1) SUBMIT (2) STATE PRODUCT APPROVALS
 FOR THE IMPACT RATED DOOR AT PLAYROOM.
  
 REVISIONS TO SHEETS A2 AND A4 NEED TO BE
 SUBMITTED AS A REVISION TO PERMIT NUMBER
 04021011 AND PAY REVISION FEE OF $50.00
 PLUS $10.00 PER PAGE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-05-05 Cont ID  
Sent By rmcdouga Date 2004-05-05 Time 15:50 Rev Time 4.00
Received By rmcdouga Date 2004-05-05 Time 15:50 Sent To  
Notes
2004-05-05 00:00:00BUILDING PROVISO
  
 1) SUBMIT SITE SPECIFIC ENGINEERING FOR
 THE BUTT GLASS WINDOW UNDER SEPARATE
 PERMIT WITH ADDITIONAL FEES.
  
 2) SUBMIT REVISED PLAN INDICATING THE
 EXTERIOR DOOR THAT WILL BE IMPACT RATED
 AS REQUIRED FOR EMERGENCY EGRESS WHEN
 STRUCTURE IS SHUTTERED PER FBC 1005.4.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2004-04-21 Cont ID  
Sent By csiegber Date 2004-04-30 Time 15:04 Rev Time 1.00
Received By rmcdouga Date 2004-04-21 Time 10:08 Sent To  
Notes
2004-04-21 00:00:00SUBMITTALS FOR BUTT GLASS AND MULLION
  
 BUTT GLASS:
 1) RULE 9B-72 REQUIRES LOCAL OR STATE
 PRODUCT APPROVAL FOR BUTT GLASS.
 2) USE APPROPRIATE SITE SPECIFIC LOCAL
 PRODUCT APPROVAL FORM. (ATTACHED) FOR
 EACH ITEM.
 3) DIMENSIONS ON DRAWING DO NOT MATCH
 PLANS.
 4) SUBMIT SIGNED AND SEALED CALCULATIONS
 TEST REPORTS ETC.
 5) LIST ALL LIMITATIONS. (DESIGN
 PRESSURES, SHUTTERS REQUIRED, ETC.)
 6) THIRD PARTY QUALITY ASSURANCE IS
 REQUIRED. WINDOW WILL HAVE TO BE
 INSPECTED AND APPROVED BY THE ENGINEER
 AFTER IT IS INSTALLED.
 7) SUBMIT PRODUCT APPROVALS FOR THE
 ARCH ALUMINMUM FRAME.
 8) SUBMIT THE SPECIFICATIONS FOR THE GE
 1200 SILICONE.
 9) SEE FAC RULE 9B-72 FOR ADDITIONAL
 REQUIREMENTS FOR LOCAL PRODUCT APPROVALS
  
 STRUCTURAL MULLION:
 1) SUBMIT FOR SITE SPECIFIC LOCAL
 PRODUCT APPROVAL USING THE APPROPRIATE
 FORM.
 2) DIMENSIONS MUST CORRESPOND WITH THE
 PLANS.
 3) SUBMIT CALCULATIONS, TESTING, ETC.
 4) LIST LIMITATIONS.
 5) QUALITY ASSURANCE REQUIRED.
 6) SEE FAC RULE 9B-72 FOR REQUIREMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-21 Cont ID  
Sent By rmcdouga Date 2004-04-21 Time 08:26 Rev Time 2.00
Received By rmcdouga Date 2004-04-21 Time 08:26 Sent To  
Notes
2004-04-21 00:00:00DENIED
  
 1) ON SHEET A5 UNDER STRUCTURAL DESIGN
 CRITERIA THE MEAN ROOF HEIGHT IS LISTED
 AS + OR - 10 FEET. THE MEAN ROOF HEIGHT
 IS THE DISTANCE FROM GRADE TO THE
 AVERAGE HEIGHT OF THE HIGHEST ROOF
 HAVING A PITCH. FOR THIS STRUCTURE IT IS
 MORE THAN 10 FEET. PLEASE CORRECT.
  
 2) SOME OF THE ANCHORS IN THE LEGEND ON
 SHEET A5 HAVE UPLIFT VALUES SPECIFIED
 WHICH INCLUDE THE ONE THIRD STRESS
 INCREASE IN THE STEEL CALCULATIONS,
 WHICH IS NOT ALLOWED BY FBC 1609.3. THE
 UPLIFT VALUES LISTED FOR ID TAG NUMBERS
 (1B) AND (2) FOR THE TA20R CONNECTORS
 ARE INCORRECT. SEE 2004 USP CATALOG FOR
 VALUES THAT DO NOT INCLUDE A STRESS
 INCREASE ON THE STEEL CALCULATIONS.
  
 3) THE UPLIFT AND ANCHOR KEY IN THE
 ANCHOR LEGEND SPECIFIES THE UPLIFT
 VALUES ON THE BOTTOM AND THE ANCHOR ON
 TOP. HOWEVER, ON THE ROOF FRAMING PLAN
 THESE ITEMS ARE REVERSED IN THE ID TAGS.
  
 4) THE STATE PRODUCT APPROVAL FOR THE
 HANSON ROOF TILE IS REQUIRED TO HAVE THE
 SBCCI PST AND ESI REPORTS SUBMITTED
 BECAUSE THEY WERE THE EVALUATION ENTITY
 USED FOR STATE APPROVAL. THE SUBMITTAL
 FOR THE MONIER LIFETILE IS OK. PLEASE
 SELECT THE ONE THAT WILL BE INSTALLED
 AND REMOVE THE OTHER FROM THE SUBMITTAL.
  
 5) SUBMIT STATE PRODUCT APPROVALS FOR
 THE DOUBLE OUTSWING FRENCH DOORS WITH
 SIDELITES. THE PRODUCT APPROVAL FL 1433
 THAT WAS SUBMITTED DOES HAVE THE TESTING
 REPORT (EVALUATION METOD) INDICATING THE
 DESIGN PRESSURES AND LIMITATIONS AND THE
 INSTALLATION INSTRUCTIONS.
  
 6) SUBMIT STATE PRODUCT APPROVALS FOR
 IMPACT RATED ENTRY DOORS, WHICH IS
 REQUIRED FOR EMERGENCY EGRESS PER FBC
 1005.4.5.
  
 7) SUBMIT (2) COPIES OF THE RECORDED
 EASEMENT RELEASE FOR THE 2.5' SHOWN ON
 THE SURVEY IN A DRAINAGE EASEMENT.
  
 8)SUBMIT STATE OR LOCAL PRODUCT APPROVAL
 FOR THE BUTT GLASS WINDOW.
  
 9)SUBMIT STATE OR LOCAL PRODUCT APPROVAL
 FOR THE 12' STRUCTURAL MULLION BETWEEN
 THE FRENCH DOORS WITH SIDELITES AND THE
 TRANSOM ABOVE OR REVISE PLANS TO SHOW A
 BEAM OR LINTEL BETWEEN THE OPENINGS.
  
 10) ONLY TWO COPIES OF SUBMITTAL ITEMS
 ARE REQUIRED. PLEASE REMOVE ALL EXTRA
 COPIES FROM THE PACKAGE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-15 Time 14:09 Rev Time 3.00
Received By rmcdouga Date 2004-04-01 Time 14:59 Sent To  
Notes
2004-04-01 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE ATTIC LIVE LOAD ON THE
 PLANS (BOTTOM CORD L.L.). SEE FBC TABLE
 1604.1.
  
 3) ENGINEER IS REQUIRED TO SIGN AND SEAL
 DRAWINGS WHICH HAVE HIS TITLE BLOCK PER
 CHAPTER 471 FLORIDA STATUTES.
  
 4) THE ROOF FRAMING PLAN ON A5 HAS SOME
 ERRORS. SOME OF THE ANCHOR ID TAGS HAVE
 TWO UPLIFTS AND NO ANCHOR SPECIFIED. THE
 LOCATION OF THE UPLIFT AND ANCHORS ON
 THE PLAN ARE REVERSED FROM THE KEY IN
 THE LEGEND.
  
 5) CLARIFY THE 1A AND 1B ANCHORS SPEC.
 IN THE ANCHOR TAG BUT NOT IN THE LEGEND.
  
 6) SOME OF THE ANCHORS IN THE LEGEND
 HAVE UPLIFT VALUES WHICH INCLUDE A ONE-
 THIRD INCREASE IN THE STEEL CALCS. THIS
 IS NOT ALLOWED BY FBC 1609.4.3. PLEASE
 REVISE.
  
 7) SUBMIT STATE OR LOCAL PRODUCT
 APPROVALS FOR THE BUTT GLASS WINDOW.
  
 8) SUBMIT STATE PRODUCT APPROVAL WITH
 STATUS OF APPROVED FOR THE ALUFAB
 HURRICANE PANELS. THE STATE COVER SHEETS
 DO NOT MATCH THE MIAMI-DADE NOA. THE
 GAGES OF THE METAL ARE DIFFERENT. SOME
 OF THE NOA IS ILLEGIBLE. THE DRAWING #S
 ON THE WIND PRESSURE CHARTS DO NOT
 MATCH THE NOA. SOME OF THE SPANS IN THE
 INSTALLATION SCHEDULE EXCEED THE LIMITS
 OF THE NOA. PLEASE CORRECT.
  
 9) SUBMIT STATE PRODUCT APPROVAL FOR THE
 MONIER ROOF TILE OR THE EVALUATION
 REPORT FOR THE HANSON ROOF TILE.
  
 10) SUBMIT STATE PRODUCT APPROVAL FOR
 DOUBLE OUTSWING FRENCH DOORS WITH SIDE-
 LITES.
  
 11) SUBMIT STATE PRODUCT APPROVALS FOR
 IMPACT RATED ENTRY DOORS.(EMERGENCY
 EGRESS)
  
 12) SUBMIT AN ADDITIONAL COPY OF THE
 SOIL REPORT.
  
 13) SUBMIT AN EASEMENT RELEASE FOR THE
 2.5' SHOWN ON SURVEY IN A DRAINAGE
 EASEMENT.
  
 14) ONLY SUBMIT PRODUCT APPROVALS FOR
 ITEMS THAT WILL BE USED IN THIS
 STRUCTURE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-10-07 Cont ID  
Sent By btrobaug Date 2004-10-07 Time 16:00 Rev Time 0.50
Received By btrobaug Date 2004-10-07 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:52 Rev Time 0.50
Received By btrobaug Date 2004-03-01 Time 07:26 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 14:52 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 14:52 Sent To E
Notes
2004-10-05 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 15:04 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 15:04 Sent To B
Notes
2004-04-30 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-15 Cont ID  
Sent By csiegber Date 2004-04-15 Time 14:09 Rev Time 0.00
Received By csiegber Date 2004-04-15 Time 14:09 Sent To B
Notes
2004-04-15 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-01 Cont ID  
Sent By rmcdouga Date 2004-04-01 Time 14:59 Rev Time 0.00
Received By rmcdouga Date 2004-02-23 Time 11:52 Sent To  
Notes
2004-02-25 00:00:00TO Z
 TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-28 Cont ID  
Sent By hmoser Date 2004-02-28 Time 12:46 Rev Time 0.50
Received By hmoser Date 2004-02-28 Time 12:46 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-05-06 Cont ID  
Sent By rmcdouga Date 2004-05-06 Time 08:34 Rev Time 0.00
Received By rmcdouga Date 2004-05-06 Time 08:34 Sent To  
Notes
2004-05-06 00:00:00OK PER J.LEECH 5/6/04

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By btrobaug Date 2004-03-01 Time 09:44 Rev Time 0.33
Received By jleech Date 2004-03-08 Time 19:37 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-24 Cont ID  
Sent By mmclean Date 2004-02-24 Time 08:21 Rev Time 0.00
Received By mmclean Date 2004-02-24 Time 08:21 Sent To I
Notes
***NONE***