Plan Review Details - Permit 04020930
Plan Review Stops For Permit 04020930
Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-01-31 Cont ID  
Sent By dpalmer Date 2005-01-31 Time 10:31 Rev Time 0.50
Received By dpalmer Date 2005-01-31 Time 10:30 Sent To Z
Notes
2005-01-31 00:00:00************ UNSAT ************
  
 1)NOTE: PLEASE SUBMIT TWO COPIES OF
 MANUFACTURE SPECS FOR GENERATOR/TRANSFER
 SWITCH ETC.
 PLEASE SEE ZONING NOTES FOR SURVEY AND
 SET BACKS.
 ONLY ONE COPY OF SURVEY SUBMITTED.
  
 2)NOTE: PLEASE SEE 700.6 FOR TRANSFER OF
 POWER FOR EM POWER. TRANSFER OF POWER
 SHOWN ON RISER IS NOT PERMITTED.
 A FAIL SAFE MANNER IS REQUIRED.
  
 3)NOTE: PLEASE SEE BLDG C.O. HAS BEEN
 REVOKED AND DATE REMOVED. PLEASE SEE NOT
 ONLY DO PLANS NEED TO BE REVISED, BUT
 THERE MAY BE A NEED FOR A RE-INSPECTION
 OF ELECTRICAL EQUIPMENT/SET BACK ETC.
  
 4)NOTE: PLEASE SEE MECH NOTES, FOR
 GENERATOR TO BE A MIN OF 10' FROM
 OPENINGS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-12-02 Cont ID  
Sent By btrobaug Date 2004-12-02 Time 14:22 Rev Time 0.50
Received By btrobaug Date 2004-12-02 Time 14:22 Sent To  
Notes
2004-12-02 00:00:00 
 ALL CHANGES TO PLANS MUST BE DONE BY
 THEDESIGNER OF RECORD. HAND DRAWN
 CHANGESARE NOT ACCEPTABLE. THE
 ARCHITECT WHO SIGNED THIS PLAN IS NOT
 THE ORIGINAL ARCHITECT IN VIOLATION OF
 ARTICLE 481.221(1)(A)(4), FLORIDA
 STATUTES.
  
 THE GAS GENERATOR SHOWN ON THE ATTACHED
 RISER DIAGRAM WAS NOT PERMITTED. SUBMIT
 ALL RELATED DRAWINGS FOR SAME AS A
 REVISION TO THIS PLAN OR UNDER A NEW
 APPLICATION. THESE PLANS MUST INCLUDE
 WIRING DIAGRAMS, ALL PANELS AND TRANSFER
 SWITCHES AND RELATED EQUIPMENT. ALSO
 SUBMIT A CURRENT SURVEY SHOWINGLOCATION
 OF SAME FOR ZONING REVIEW. A GAS PERMIT
 IS ALSO REQUIRED. THE COST OF THE
 EQUIPMENT AS WELL AS LABOR MUST BE
 SHOWN AND THE VALUE OF THE JOB MUST BE
 INCREASED TO REFLECT SAME.
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.PER 110.9/215.5. SUBMIT PANEL
 SCHEDULES FOR ALL PANELS. INCREASE VALUE
 TO REFLECT LABOR & EQUIPMENT PER
 104.6.5
 FBC.
  
 PROVIDE LOAD CALCULATIONS FOR ALL LOADS
 INCLUDING ADDED AND EXISTING A/C, &
 BOTH TANKLESS UNITS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-02-25 Cont ID  
Sent By csiegber Date 2004-02-19 Time 11:46 Rev Time 0.50
Received By btrobaug Date 2004-02-24 Time 15:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-11-24 Cont ID  
Sent By mjacobs Date 2004-11-24 Time 12:26 Rev Time 0.00
Received By mjacobs Date 2004-11-24 Time 12:25 Sent To E
Notes
2004-11-24 00:00:00SENT TO "BT" DESK/AS BUILT PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 11:46 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 11:46 Sent To E
Notes
***NONE***