Plan Review Details - Permit 04020830
Plan Review Stops For Permit 04020830
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-12-23 Cont ID  
Sent By jgomez Date 2004-12-23 Time 14:39 Rev Time 0.00
Received By jgomez Date 2004-12-23 Time 14:39 Sent To  
Notes
2004-12-23 00:00:00CHECKLIST:
 1- PORCH DETAILS DON'T MATCH ROOF
 FRAMING PLAN.
  
 2-STRUCTURAL FASCIA DETAIL IS MISSING
 THE FASTENERS.
  
 3-PROVIDE ENTRY DOORS PRODUCT APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-12-17 Cont ID  
Sent By jgomez Date 2004-12-17 Time 13:56 Rev Time 0.00
Received By jgomez Date 2004-12-17 Time 13:56 Sent To PC
Notes
2004-12-17 00:00:00CHECKLIST:
 1-INFORMATION REQUESTED ON PROVISO DATED
 4-23-04 WAS NEVER SUBMITTED. SEE
 ATTACHED COPY.
  
 2-PROVIDE COMPLETE DETAILS FOR ENTRY
 PORCH ROOF CONSTRUCTION THAT MATCHES
 ACTUAL ROOF FRAMING PLAN. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001. CONSIDER
 ATTACHMENT OF 2X12 TO STEEL COLUMNS AND
 TO MASONRY WALL.
  
 3-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR ENTRY DOORS AS SHOWN ON PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 BACK AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-23 Cont ID  
Sent By jgomez Date 2004-04-23 Time 16:32 Rev Time 1.00
Received By jgomez Date 2004-04-23 Time 16:32 Sent To PC
Notes
2004-04-23 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE COMPLETE PRODUCT APPROVAL
 ASSEMBLY FOR FRENCH DOORS W/ SIDELITES
 AND TRANSOM ABOVE ASSEMBLY AS SHOWN ON
 PLANS. SPECIFY ALL FASTENERS INCLUDING
 ATTACHMENT OF MULLION TO WALL AND DOOR
 AND WINDOW ATTACHMENT TO MULLION. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 2-PROVIDE COMPLETE DETAIL FOR STRUCTURAL
 FACIA AT REAR PORCH. SPECIFY ALL
 FASTENERS. SEC. 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 3-PROVIDE COMPLETE DETAIL SHOWING
 INSTALLATION OF (2)B1 CONNECTORS AT
 THE ENDS OF GIRDER TRUSSES AT ENTRY
 PORCH. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 4-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL
 FOR ENTRY DOORS WITH IMPACT GLAZING AS
 CALLED FOR IN SHEET A1.
 5-PROVIDE COMPLETE KNEE WALL SECTION/DET
 AT ENTRY PORCH. SEE ROOF FRAMING PLAN
 AND PROVIDE ALSO A DETAIL SHOWING HOW
 IS 2X4 KNEE WALL ATTACHED TO TRUSSES
 BELOW IF TRUSSES RUN PARALLEL TO THE
 KNEE WALL. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 6-IF STORM SHUTTERS ARE TO BE INSTALLED
 IN THIS HOUSE, THEN PROVIDE COMPLETE
 INFORMATION UNDER A SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-29 Cont ID  
Sent By csiegber Date 2004-04-19 Time 09:06 Rev Time 2.50
Received By jgomez Date 2004-03-29 Time 17:14 Sent To PC
Notes
2004-03-29 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE STRUCTURAL BUCK DETAIL @ ENTRY
 DOORS SHOWING SIZE OF BUCK REQUIRED TO
 CLOSE GAP ACCORDING TO MASONRY OPENING
 SHOWN. SEC. 104.2.1.2 CITY AMENDMENTS.
 3-ENERGY CALCULATIONS: A)REVISE OPENINGS
 CARDINAL ORIENTATION TO MATCH PLANS.
 B)REVISE OVERHEAD HEIGHT AND LENGTH TO
 MATCH PLANS.
  
 4-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A)ALL STRUCTURAL CONNECTORS.
 B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 C) ENTRY DOORS.
  
 5-CLARIFY IF USING MISSILE IMPACT GLASS
 OR SHUTTERS. PROVIDE COMPLETE INFO.
 FOR EITHER OPTION.
 6-PROVIDE COMPLETE DETAIL FOR ENTRY AND
 REAR CONCRETE PAD FOOTING SHOWING PAD
 EMBEDMENT IN REFERENCE TO GRADE LEVEL.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 7-SPECIFY FASTENERS FOR 2X4 BLOCKING AT
 ARCHED & OVAL OPENINGS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-PROVIDE COMPLETE KNEE WALL DETAIL AT
 ENTRY PORCH. SPECIFY ALL FASTENERS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 9-SPECIFY 7/8" MIN. STUCCO THICKNESS AT
 FRAMED WALL AS REQUIRED BY ASTM C-926.
 10-SPECIFY SAFETY GLASS IN MASTER BATH
 WINDOW (IF NOT USING IMPACT GLASS).
 11-CAP ON DETAIL F/6 FOR STEEL COLUMN @
 ENTRY PORCH DOESN'T WORK. PROVIDE
 DETAIL THAT SHOWS CORRECT CAP. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 12-SPECIFY CONNECTORS FOR BEAMS AT ENTRY
 PORCH THAT ARE RESTING ON MASONRY WALL
 SEE PLANS FOR COMMENTS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 13-PROVIDE COMPLETE DETAIL WITH SPECS
 TRUSSES AT REAR PORCH SHOWING HOW ARE
 THEY SUPPORTED IF THERE IS NOT A BEAM?
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 14-SHEET A3: LIVE LOAD IN ATTIC IS
 MEASURED IN PSF NOT PSI. REVISE NOTE
 AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-12-15 Cont ID  
Sent By btrobaug Date 2004-12-15 Time 14:39 Rev Time 0.33
Received By btrobaug Date 2004-12-15 Time 14:31 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By btrobaug Date 2004-03-08 Time 12:48 Rev Time 0.50
Received By btrobaug Date 2004-03-08 Time 11:18 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-12-22 Cont ID  
Sent By mjacobs Date 2004-12-22 Time 13:40 Rev Time 0.00
Received By mjacobs Date 2004-12-22 Time 13:40 Sent To B
Notes
2004-12-22 00:00:00SENT TO "JG" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-12-10 Cont ID  
Sent By mjacobs Date 2004-12-10 Time 13:20 Rev Time 0.00
Received By mjacobs Date 2004-12-10 Time 13:20 Sent To E
Notes
2004-12-10 00:00:00SEBT TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-19 Cont ID  
Sent By csiegber Date 2004-04-19 Time 09:06 Rev Time 0.00
Received By csiegber Date 2004-04-19 Time 09:06 Sent To B
Notes
2004-04-19 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-29 Cont ID  
Sent By mmclean Date 2004-02-19 Time 16:42 Rev Time 0.00
Received By jgomez Date 2004-02-19 Time 11:41 Sent To PC
Notes
2004-02-20 00:00:00TO SFD RACK/E
2004-02-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date 2004-12-16 Cont ID  
Sent By pkrauss Date 2004-12-16 Time 13:59 Rev Time 0.10
Received By pkrauss Date 2004-12-16 Time 13:53 Sent To B
Notes
2004-12-16 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 RESTAMP.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-18 Cont ID  
Sent By jleech Date 2004-03-13 Time 08:34 Rev Time 0.33
Received By pkrauss Date 2004-03-18 Time 11:24 Sent To B
Notes
2004-03-18 00:00:00APPROVED 3/9/04

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-12-15 Cont ID  
Sent By kstevens Date 2004-12-15 Time 17:41 Rev Time 0.25
Received By kstevens Date 2004-12-15 Time 17:41 Sent To M
Notes
2004-12-15 00:00:00RESTAMP OK

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-13 Cont ID  
Sent By jleech Date 2004-03-13 Time 08:34 Rev Time 0.33
Received By jleech Date 2004-03-13 Time 08:33 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-19 Cont ID  
Sent By mmclean Date 2004-02-19 Time 16:42 Rev Time 0.00
Received By mmclean Date 2004-02-19 Time 16:42 Sent To I
Notes
***NONE***