Plan Review Details - Permit 04020827
Plan Review Stops For Permit 04020827
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-15 Cont ID  
Sent By jgomez Date 2005-03-15 Time 11:21 Rev Time 1.00
Received By jgomez Date 2005-03-15 Time 11:21 Sent To PC
Notes
2005-03-15 00:00:00REVISED KITCHEN LAYOUT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-05 Cont ID  
Sent By btrobaug Date 2004-12-01 Time 14:52 Rev Time 0.00
Received By jgomez Date 2004-11-05 Time 14:58 Sent To PC
Notes
2004-11-05 00:00:00BUILDING PROVISO:
 1-DRAWING A1: ARCHITECT SPECIFIES 2X
 MULLION. PROVIDE PRODUCT APPROVAL FOR
 THIS SIZE MULLION.
 AND, CLEARLY INDICATE FASTENERS AND
 ATTACHMENT OF DOORS AND WINDOWS TO THIS
 STRUCTURAL MULLION. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH MISSILE IMPACT GLAZING AS
 SPECIFIED ON ARCHITECTURAL PLANS.
  
 3-PROVIDE COMPLETE SECTIONS AND DETAILS
 OF FRAMING AT ENTRY PORCH THAT MATCH
 ROOF FRAMING PLANS. SPECIFY ALL
 FASTENERS, SPECIALLY AT THE ENDS.
 CLARIFY HOW ARE BOTTOM 2X12'S ATTACHED
 TO STEEL COLUMN AND TO MASONRY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-09-16 Cont ID  
Sent By jgomez Date 2004-09-15 Time 16:24 Rev Time 2.00
Received By jgomez Date 2004-09-16 Time 09:20 Sent To PC
Notes
2004-09-15 00:00:00CHECKLIST:
 1-MODEL WAS CHANGED. NEED SURVEY SHOWING
 NEW MODEL LAYOUT FOR ZONING APPROVAL.
 2-NOTICE OF COMMENCEMENT IS EXPIRED.
 NEED RENEWED ONE.
 3-A)NEED FLORIDA/LOCALPRODUCT APPROVAL
 FOR FIXED WINDOWS WITH SIZES AS SHOWN
 ON PLAN. EG: SEE LENGTH OF WINDOW AT
 KITCHEN AREA.
 B)NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR SINGLE HUNG WINDOWS.
 4-A)MULLION PRODUCT APPROVAL:
 CLEARLY INDICATE SIZE OF MULLIONS AND
 ANCHOR TYPE AND SPACING TO BE USED IN
 ORDER TO CHECK IF IT WILL MEET THE
 DESIGN PRESSURES CALCULATED ON PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-CLEARLY SPECIFY HOW ARE FIXED WINDOWS
 AND DOORS ATTACHED TO THE STRUCTURAL
 MULLIONS. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 6-STORM SHUTTERS NOTE ON PAGE A1 CALLS
 FOR SHUTTERS ON GLAZED OPENINGS AND
 HURRICANE MISSILE IMPACT GLAZING ON
 ENTRY DOOR. PRODUCT APPROVAL PACKAGE
 SUBMITTED IS FOR MISSILE IMPACT GLASS
 IN ALL DOORS AND WINDOWS EXCEPT ENTRY
 DOOR. ARCHITECT'S NOTE AND PRODUCT
 APPROVAL SUBMITTAL NEED TO MATCH.
 AND, IF ENTRY DOORS WILL NOT HAVE
 IMPACT GLASS, THEN PROVIDE COMPLETE
 INFO. FOR STORM SHUTTERS (FL. PRODUCT
 APPROVAL AND INSTALLATION SCHEDULE).
 7-DETAIL C/7 DOESN'T MATCH CONDITIONS
 SHOWN ON ROOF FRAMING. PROVIDE DETAIL
 THAT SHOWS ACTUAL CORNER CONDITION AND
 SPECIFY ALL FASTENERS. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 8-DETAIL G/7:SPECIFY HOW IS 2X4 BLOCKING
 ATTACHED TO TRUSSES. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 9-PROVIDE COMPLETE SECTION DETAIL AT
 ENTRY PORCH SHOWING HOW IS FRONT WALL
 FRAMED. SPECIFY ALL FASTENERS TOP AND
 BOTTOM AND FRAMING AROUND OPENINGS.
 SEE FRONT ELEVATION. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 10-SHEET A7: CROSS SECTIONS DRAWINGS FOR
 BEAMS AND LINTELS HAVE THE COPY OF THE
 ENGINEER'S SEAL. NEED ORIGINAL SEAL,
 SIGNATURE AND DATE FROM THE ENGINEER
 AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
 B)CROSS SECTIONS DRAWINGS AREN'T LEGIBLE
 NEED LEGIBLE DRAWINGS.
 11-OWES $2258.84 FOR UPDATE VALUATION
 WITH CHANGE OF MODEL, RESUBMITTAL FEE
 AND BALANCE DUE BECAUSE ONLY PARTIAL
 PAYMENT WAS PAID AT TIME OF PERMIT
 APPLICATION. ALSO, RE-SUBMITTAL FEES
 WILL BE CHARGED AT TIME OF RESUBMITTAL
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-26 Cont ID  
Sent By pkrauss Date 2004-08-26 Time 13:37 Rev Time 2.00
Received By jgomez Date 2004-04-26 Time 09:32 Sent To PC
Notes
2004-04-26 00:00:00BUILDING REVIEW CHECKLIST:
 1-NOTICE OF COMMENCEMENT IS EXPIRED.NEED
 TO RENEW IT.
 2-REVISE/CLARIFY SHEET A1:
 A)STORM SHUTTERS NOTE AND WINDOW GLAZING
 NOTE ARE CONFLICTING. CLARIFY IF USING
 STORM SHUTTERS OR MISSILE IMPACT GLASS
 B)NORTH ARROW IS POINTING TO THE WRONG
 ORIENTATION. SEE SURVEY AND REVISE
 AS REQUIRED.
 **NOTE: SAME THING ABOUT NORTH ARROW
 APPLIES TO SITE PLAN ON SHEET A5.
 3-ACCORDING TO CLARIFICATION REGARDING
 MISSILE IMPACT PROTECTION AT GLAZED
 OPENINGS PROVIDE COMPLETE INFORMATION
 FOR EITHER OPTION.
 4-PROVIDE COMPLETE SECTION DETAIL THRU
 ENTRY PORCH THAT MATCHES ROOF FRAMING
 PLAN. DETAILS ON SHEET A6 FOR KNEE
 WALL AND ENTRY PORCH SEC. DON'T MATCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 WHERE IS DETAIL E/6 TAKEN AT?.
 5-CLEARLY SPECIFY ON PLANS IF ATTIC
 SPACE ABOVE GARAGE IS TO BE USED FOR
 STORAGE OR NOT. SEE TABLE 1604.1 FBC
 2001. FOR REQUIRED DESIGN CRITERIA.
 6-PROVIDE ATTIC ACCESS AT GUEST HOUSE.
 SEC. 2309.6 FBC 2001.
 7-PROVIDE COMPLETE SECTION THRU BAY
 WINDOW. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 8-PLEASE PROVIDE ONLY THE DETAILS THAT
 APPLY TO THIS HOUSE TO EXPEDITE THE
 REVIEW PROCESS.
 9-PRODUCT APPROVAL PACKAGE: A)FIXED
 WINDOWS NEED NOA AND DWGS THAT MATCH
 FLORIDA PRODUCT APPROVAL REPORT.
 B)PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS WITH IMPACT GLAZING IF THIS
 OPTION IS TAKEN ON PLANS.
 C)PROVIDE COMPLETE PRODUCT APPROVAL FOR
 FRENCH DOORS WITH SIDELITES & TRANSOM
 ABOVE SINGLE ASSEMBLY AS SHOWN ON
 PLANS. CLEARLY SPECIFY ALL CONNECTIONS
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-31 Cont ID  
Sent By dpalmer Date 2004-04-21 Time 19:15 Rev Time 2.50
Received By jgomez Date 2004-03-31 Time 17:04 Sent To PC
Notes
2004-03-31 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE STRUCTURAL BUCK DETAIL @ ENTRY
 DOORS SHOWING SIZE OF BUCK REQUIRED TO
 CLOSE GAP ACCORDING TO MASONRY OPENING
 SHOWN. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 3-ENERGY CALCULATIONS: A)SINCE THIS IS
 NOT A WORST CASE SCENARIO CALCS, THEN
 ORIENTATION OF OPENINGS NEED TO MATCH
 PLANS. ALSO, OPENINGS TO MATCH PLANS.
 B)REVISE OVERHANG LENGTH AND HEIGHT TO
 MATCH FLOOR PLANS.
 4-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR:
 A)ALL STRUCTURAL CONNECTORS.
 B)FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 ASSEMBLY AS SHOWN ON PLANS.
 C)FIXED WINDOWS FOR BIG SIZES AS SHOWN
 ON PLANS.
 D)ROOF TILE
 E)WINDOW MULLIONS.
 F)GLASS BLOCK. 2 COPIES.
  
 5-PROVIDE APROVAL AND SPECS FOR BBQ AS
 REQUIRED BY SEC. 2808 FBC 2001.
 6-CLARIFY IF USING MISSILE IMPACT GLASS
 OR SHUTTERS. SEE NOTE ON SHEET A1 AND
 PROVIDE COMPLETE INFORMATION OF EITHER
 OPTION.
 7-SPECIFY FASTENERS FOR 2X4 BLOCKING AT
 ARCHED OPENINGS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 8-PROVIDE COMPLETE KNEE WALL DETAIL AT
 ENTRY PORCH. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 9-SPECIFY 7/8" MIN. STUCCO THICKNESS AT
 FRAMED WALLS AS REQ'D BY ASTM C-926.
 10-SPECIFY SAFETY GLASS AS REQUIRED BY
 SEC. 2405.2(IF NOT USING IMPACT GLASS)
 B)GLASS BLOCK TO HAVE SAFETY GLASS ALSO
 IF FACE THICKNESS IS LESS THAN 0.25".
 SPECIFY FACE THICKNESS TO BE USED.
 11-SHEET A3: A)CLARIFY IF ATTIC ABOVE
 GARAGE AREA IS DESIGNEDFOR STORAGE
 OR NOT STORAGE. ATTIC ACCESS W/ LADDER
 SUGGESTS ATTIC TO BE USED FOR STORAGE.
 IF SO, THEN PROVIDE SPECIFICATIONS.
 SEE TABLE 1604.1 FBC 2001.
 B)ATTIC LIVE LOAD IS MEASURED IN PSF,
 NOT PSI. REVISE NOTE AS REQUIRED.
 12-DRAWINGS ON SHEET A1 ARE NOT LEGIBLE.
 13-PROVIDE ATTIC ACCESS AT GUEST HOUSE.
 SEC. 2309.6 FBC 2001.
 14-PROVIDE COMPLETE SECTION THRU BAY
 WINDOW. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 15-PROVIDE COMPLETE LEDGER DETAIL FOR
 ROOF TRUSSES @ ENTRY PORCH. SEE PLANS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 16-PLEASE PROVIDE ONLY THE DETAILS THAT
 APPLY TO THIS HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 BACK AT 805-6712.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-08-12 Cont ID  
Sent By btrobaug Date 2005-08-12 Time 07:25 Rev Time 0.50
Received By btrobaug Date 2005-08-12 Time 07:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-03-02 Cont ID  
Sent By btrobaug Date 2005-03-02 Time 15:58 Rev Time 0.50
Received By btrobaug Date 2005-03-02 Time 15:17 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-01-11 Cont ID  
Sent By btrobaug Date 2005-01-11 Time 17:02 Rev Time 0.50
Received By btrobaug Date 2005-01-11 Time 16:45 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-12-01 Cont ID  
Sent By btrobaug Date 2004-12-01 Time 14:00 Rev Time 0.50
Received By btrobaug Date 2004-12-01 Time 13:17 Sent To B
Notes
2004-12-01 00:00:00 
 PROVIS0
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION.
  
 1} PLEASE SEE THAT A #2 EQUIPMENT
 GROUND IS SHOWN BEING RAN WITH THE
 FEEDERS TO THE PANELS FROMTHE
 DISCONNECTS.VERIFY THE SIZE OF SAME. A
 #6 IS REQUIRED PER 250.122.
  
 2} THE #2 EQUIPMENT GROUND RUNNING
 BETWEEN DISCONNECTS IS IN VIOLATION OF
 250.6(B) AND MUST NOT BE INSTALLED.
  
 3} THERE IS A POOL PUMP SHOWN ON THE
 DRAWINGS BUT NONE LISTED IN THE
 CALCULATIONS.ALSO IF THE POOL IS TO BE
 HEATED PLEASE SHOW THAT CALCULATION.
  
 4} AIR HANDLER #2 IS SHOWN ON THE
 CALCULATIONS @ 7.5 KW AND LISTED ON THE
 MECHANICAL PLANS AS 10KW. PLEASE
 CORRELATE.
  
 5} THE LOAD CALCULATIONS MUST CONTAIN A
 CALCULATION FOR THE DRYER PER 220.18.
  
 6} PLEASE SHOW THE RECEPTACLE LOCATION
 FOR THE "WHIRL-TUB" AND SHOW GFI
 COMPLIANCE PER 680.62(A).
  
 7} RECEPTACLES NEED TO BE ADDED
 TO BEDROOM #4 TO COMPLY WITH
 210.52(A)(2).
  
 ONE SET OF REVIEWED PLANS ARE MARKED TO
 INDICATE THE AREAS OF COMMENTS.PLEASE
 SEE THIS SET AND CALL IF THERE ARE ANY
 QUESTIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-08-19 Cont ID  
Sent By dpalmer Date 2004-08-19 Time 08:42 Rev Time 0.50
Received By dpalmer Date 2004-08-19 Time 08:42 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-21 Cont ID  
Sent By csiegber Date 2004-08-13 Time 12:44 Rev Time 0.50
Received By dpalmer Date 2004-04-21 Time 19:14 Sent To B
Notes
2004-04-21 00:00:00REDLINED PLANS,
 REVISE BEFORE ROUGH.
  
 EQUIPMENT GRNDS ARE MISSING BETWEEN MAIN
 -S AND PANELS. 250.110, 250.122
  
 PLEASE SEE KW HAS NOW BEEN CHANGED TO
 10KW, HOWEVER, OCP WAS NOT INCREASED
 PER 424.3B
  
 PLEASE SEE 250.66 FOR #2 MIN GEC FOR
 300A SERVICE. BASED ON MIN SEC'S IN
 310.15B6
 PLEASE ADJUST.
  
 PLEASE SUBMIT REVISED PLANS BEFORE ROUGH

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-04-20 Time 16:32 Rev Time 0.75
Received By btrobaug Date 2004-03-02 Time 08:40 Sent To M
Notes
2004-03-02 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THAT A #2 EQUIPMENT
 GROUND
 IS SHOWN BEING RAN WITH THE FEEDERS TO
 THE PANELS FROMTHE DISCONNECTS.VERIFY
 THE SIZE OF SAME. A # 6 IS REQUIRED PER
 250.122.
  
 2} THE #2 EQUIPMENT GROUND RUNNING
 BETWEEN DISCONNECTS IS IN VIOLATION OF
 250.6(B) AND MUST NOT BE INSTALLED.
  
 3} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED AT 1500 VA PER 220.16(B)
  
 4} THERE IS A POOL PUMP SHOWN ON THE
 DRAWINGS BUT NONE LISTED IN THE
 CALCULATIONS.ALSO IF THE POOL IS TO BE
 HEATED PLEASE SHOW THAT CALCULATION.
  
 5} AIR HANDLER #2 IS SHOWN ON THE
 CALCULATIONS @ 7.5 KW AND LISTED ON THE
 MECHANICAL PLANS AS 10KW. PLEASE
 CORRELATE.
  
 6} THE LOAD CALCULATIONS MUST CONTAIN A
 CALCULATION FOR THE DRYER PER 220.18.
  
 7} PLEASE ADD A RECEPTACLE AT THE FRONT
 OF THE HOUSE PER 220.52(E).
  
 8} PLEASE SHOW THE RECEPTACLE LOCATION
 FOR THE "WHIRL-TUB" AND SHOW GFI
 COMPLIANCE PER 680.62(A).
  
 9} RECEPTACLES NEED TO BE ADDED
 TO BEDROOMS #3 & #4 TO COMPLY WITH
 210.52(A)(2).
  
 ONE SET OF REVIEWED PLANS ARE MARKED TO
 INDICATE THE AREAS OF COMMENTS.PLEASE
 SEE THIS SET AND CALL IF THERE ARE ANY
 QUESTIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-08-08 Cont ID  
Sent By adarroug Date 2005-08-08 Time 10:58 Rev Time 0.00
Received By adarroug Date 2005-08-08 Time 10:58 Sent To E
Notes
2005-08-08 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-02-25 Cont ID  
Sent By adarroug Date 2005-02-25 Time 16:48 Rev Time 0.00
Received By adarroug Date 2005-02-25 Time 16:48 Sent To E
Notes
2005-02-25 00:00:00TO "BT" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-01-03 Cont ID  
Sent By mjacobs Date 2005-01-03 Time 15:24 Rev Time 0.00
Received By mjacobs Date 2005-01-03 Time 15:22 Sent To E
Notes
2005-01-03 00:00:00TO "BT" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-19 Cont ID  
Sent By csiegber Date 2004-11-19 Time 14:33 Rev Time 0.00
Received By csiegber Date 2004-11-19 Time 14:33 Sent To P
Notes
2004-11-19 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:43 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 16:43 Sent To P
Notes
2004-10-20 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-13 Cont ID  
Sent By csiegber Date 2004-08-13 Time 12:44 Rev Time 0.00
Received By csiegber Date 2004-08-13 Time 12:44 Sent To E
Notes
2004-08-13 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 16:32 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 16:32 Sent To E
Notes
2004-04-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-31 Cont ID  
Sent By mmclean Date 2004-02-19 Time 16:27 Rev Time 0.00
Received By jgomez Date 2004-02-19 Time 12:17 Sent To PC
Notes
2004-02-20 00:00:00TO SFD RACK/E
2004-02-19 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-02-08 Cont ID  
Sent By pkrauss Date 2005-02-08 Time 11:27 Rev Time 0.45
Received By pkrauss Date 2005-02-08 Time 11:27 Sent To  
Notes
2005-02-08 00:00:00REVISION APPROVED BY PAT RAFTER 1-13-05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-08-26 Cont ID  
Sent By kstevens Date 2004-08-21 Time 13:36 Rev Time 0.35
Received By pkrauss Date 2004-08-26 Time 13:36 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-05 Cont ID  
Sent By btrobaug Date 2004-03-02 Time 10:58 Rev Time 0.35
Received By pkrauss Date 2004-03-05 Time 06:26 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-03-09 Cont ID  
Sent By jleech Date 2005-03-09 Time 16:33 Rev Time 0.50
Received By jleech Date 2005-03-09 Time 16:33 Sent To B
Notes
2005-03-09 00:00:00REVISED RISER DIAGRAM ADDED BAR SINK TO
 RISER DIAGRAM PER KEN STEVEN'S PROVISO.

Review Stop P PLUMBING
Rev No 4 Status P Date 2005-01-12 Cont ID  
Sent By jleech Date 2005-01-12 Time 10:29 Rev Time 0.50
Received By jleech Date 2005-01-12 Time 10:29 Sent To M
Notes
2005-01-12 00:00:00REVISION; BAR SINK ADDED TO RISER
 DIAGRAM AS REQUESTED BY KEN STEVENS.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-30 Cont ID  
Sent By btrobaug Date 2005-01-11 Time 17:04 Rev Time 0.50
Received By kstevens Date 2004-11-30 Time 18:31 Sent To E
Notes
2004-11-30 00:00:00PASSED/PROVISO - REVISION REQUIRED. NO
 BAR SINK SHOWN ON THE RISER DIAGRAM

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-08-21 Cont ID  
Sent By csiegber Date 2004-10-20 Time 16:43 Rev Time 0.33
Received By kstevens Date 2004-08-21 Time 13:36 Sent To M
Notes
2004-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) SHT A4 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN AT THE MASTER
 BATH. SHOWS A DRY HORIZONTAL VENT NEXT
 TO THE W/C AND SHOWS 2 LAVS ON RISER AND
 ONLY ONE LAV ON THE FLOOR PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By dpalmer Date 2004-08-19 Time 08:42 Rev Time 0.33
Received By jleech Date 2004-03-08 Time 17:29 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mmclean Date 2004-11-05 Time 15:03 Sent To  
Notes
2004-11-05 00:00:00RESTAMP PLANS MM

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-19 Cont ID  
Sent By jgomez Date 2004-09-15 Time 16:25 Rev Time 0.00
Received By mmclean Date 2004-02-19 Time 16:27 Sent To I
Notes
***NONE***