| 2004-03-23 00:00:00 | DENIED |
| | |
| | 1) SPECIFY THE BOTTOM CORD LIVE LOAD ON |
| | THE PLANS. SEE FBC TABLE 1604.1. |
| | |
| | 2) THE COFFERED CEILING AREA IS NOT |
| | INCLUDED IN THE ATTIC AREA LISTED IN THE |
| | ENERGY CALCS. AS REQUIRED BY FBC CHAPTER |
| | 13. PLEASE REVISE. ENERGY CALCS. ARE |
| | REQUIRED TO BE SIGNED BY THE OWNER/AGENT |
| | |
| | 3) REVISE THE SLIDING GLASS DOOR BUCK |
| | DETAIL ON A4 TO STATE THAT THEY ARE |
| | FASTENED THROUGH THE BUCK AND NOT TO THE |
| | BUCK. SEE FBC 1707.4.4.2. |
| | |
| | 4) SPECIFY ON THE PLANS THAT THE DOOR |
| | FROM THE GARAGE TO THE CONDITIONED SPACE |
| | IS INSULATED OR SOLID CORE AS REQUIRED |
| | BY FBC CHAPTER 13 SECTION 603. |
| | |
| | 5) THE MASONRY OPENING HEIGHTS LISTED |
| | FOR WINDOWS (12) & (13) ON THE LEFT |
| | ELEVATION ON A4 ARE INCORRECT (SHOULD BE |
| | 64"). PLEASE CORRECT. |
| | |
| | 6) UPDATE THE SEMCO TRUSS CONNECTOR |
| | SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT |
| | ANCHOR WITH STATE OR LOCAL APPROVAL. |
| | |
| | 7)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 8) SUBMIT PRODUCT APPROVALS FOR THE 16' |
| | LONG MULLION BETWEEN THE SLIDING GLASS |
| | DOOR AND THE TRANSOM AT THE GREAT ROOM. |
| | THE ONE SUBMITTED ONLY LISTS UP TO A 12' |
| | MULL LENGTH. |
| | |
| | 9) SUBMIT PRODUCT APPROVALS FOR THE |
| | CASEMENT WINDOWS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |