Plan Review Details - Permit 04020744
Plan Review Stops For Permit 04020744
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-02 Cont ID  
Sent By rmcdouga Date 2004-04-02 Time 13:28 Rev Time 2.00
Received By rmcdouga Date 2004-04-02 Time 13:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-23 Cont ID  
Sent By btrobaug Date 2004-04-02 Time 11:36 Rev Time 0.00
Received By rmcdouga Date 2004-03-23 Time 13:27 Sent To  
Notes
2004-03-23 00:00:00DENIED
  
 1) THE PLAN REVIEW NUMBER ON THE COUNTY
 IMPACT FEE RECIEPT DOES NOT MATCH THE
 ONE ON THE PLANS. PLEASE SUBMIT THE
 CORRECT RECEIPT.
  
 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. FBC TABLE 1604.1 REQUIRES
 ATTICS WITHOUT STORAGE TO HAVE A LIVE
 LOAD OF 10 PSF AND 30 PSF FOR ATTICS
 WITH STORAGE.
  
 3) THE COFFERED CEILING AREA SHOWN ON
 THE PLANS IS NOT INCLUDED IN THE CEILING
 AREA LISTED ON THE ENERGY CALC. FORM AS
 REQUIRED BY FBC CHAPTER 13. PLEASE
 REVISE.
  
 4) REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL ON A4 TO STATE THAT THEY ARE
 FASTENED THROUGH THE BUCK AND NOT TO IT.
 SEE FBC 1707.4.4.2.
  
 5) THE HEIGHTS LISTED FOR THE MASONRY
 OPENINGS OF WINDOWS (12) & (13) ON THE
 RIGHT ELEVATION ON A4 ARE INCORRECT.
 THEY SHOULD BE 64" IN HEIGHT.
  
 6) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS INSULATED OR SOLID CORE AS REQUIRED
 BY FBC 13-603.
  
 7) UPDATE THE SEMCO TRUSS CONNECTOR
 SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT
 ANCHOR WITH STATE OR LOCAL PRODUCT
 APPROVAL.
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 9) SUBMIT PRODUCT APPROVALS FOR THE 16'
 LONG MULLION BETWEEN THE SLIDING GLASS
 DOOR AND TRANSOM AT THE GREAT ROOM. THE
 ONE SUBMITTED ONLY LISTS UP TO 12' MULL
 LENGTHS.
  
 10) SUBMIT PRODUCT APPROVALS FOR
 CASEMENT WINDOWS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-10-12 Cont ID  
Sent By btrobaug Date 2004-10-12 Time 09:11 Rev Time 0.50
Received By btrobaug Date 2004-10-12 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-09-21 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:57 Rev Time 0.50
Received By btrobaug Date 2004-09-21 Time 09:25 Sent To  
Notes
2004-09-21 00:00:00 
 THIS REVISION ADDS PANEL "B" BUT THE
 LOCATION OF THE PANEL IS NOT SHOWN ON
 THE PLAN. PLEASE SHOW LOCATION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-09-14 Time 09:26 Rev Time 0.50
Received By btrobaug Date 2004-04-02 Time 11:27 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-02-24 Cont ID  
Sent By btrobaug Date 2004-02-24 Time 07:42 Rev Time 0.50
Received By btrobaug Date 2004-02-24 Time 07:18 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:56 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 12:56 Sent To E
Notes
2004-10-04 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-14 Cont ID  
Sent By csiegber Date 2004-09-14 Time 09:26 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 09:26 Sent To E
Notes
2004-09-14 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:55 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:55 Sent To B
Notes
2004-04-01 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-23 Cont ID  
Sent By mmclean Date 2004-02-19 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2004-02-18 Time 09:05 Sent To  
Notes
2004-02-19 00:00:00TO SFD RACK/E
2004-02-18 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-28 Cont ID  
Sent By btrobaug Date 2004-02-24 Time 07:42 Rev Time 0.50
Received By hmoser Date 2004-02-28 Time 09:00 Sent To P
Notes
2004-02-28 00:00:00PASS PRIVISO
 PLEASE REFER TO SECTION 601.4 BALANCED
 RETURN AIR.
 NEED RETURN AIR FOR BONUS ROOM
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-03-08 Cont ID  
Sent By hmoser Date 2004-02-28 Time 09:00 Rev Time 0.25
Received By jleech Date 2004-03-08 Time 16:39 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-19 Cont ID  
Sent By mmclean Date 2004-02-19 Time 11:20 Rev Time 0.00
Received By mmclean Date 2004-02-19 Time 11:20 Sent To I
Notes
***NONE***