| 2004-03-23 00:00:00 | DENIED |
| | |
| | 1) THE PLAN REVIEW NUMBER ON THE COUNTY |
| | IMPACT FEE RECIEPT DOES NOT MATCH THE |
| | ONE ON THE PLANS. PLEASE SUBMIT THE |
| | CORRECT RECEIPT. |
| | |
| | 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON |
| | THE PLANS. FBC TABLE 1604.1 REQUIRES |
| | ATTICS WITHOUT STORAGE TO HAVE A LIVE |
| | LOAD OF 10 PSF AND 30 PSF FOR ATTICS |
| | WITH STORAGE. |
| | |
| | 3) THE COFFERED CEILING AREA SHOWN ON |
| | THE PLANS IS NOT INCLUDED IN THE CEILING |
| | AREA LISTED ON THE ENERGY CALC. FORM AS |
| | REQUIRED BY FBC CHAPTER 13. PLEASE |
| | REVISE. |
| | |
| | 4) REVISE THE SLIDING GLASS DOOR BUCK |
| | DETAIL ON A4 TO STATE THAT THEY ARE |
| | FASTENED THROUGH THE BUCK AND NOT TO IT. |
| | SEE FBC 1707.4.4.2. |
| | |
| | 5) THE HEIGHTS LISTED FOR THE MASONRY |
| | OPENINGS OF WINDOWS (12) & (13) ON THE |
| | RIGHT ELEVATION ON A4 ARE INCORRECT. |
| | THEY SHOULD BE 64" IN HEIGHT. |
| | |
| | 6) SPECIFY ON THE PLANS THAT THE DOOR |
| | FROM THE GARAGE TO THE CONDITIONED SPACE |
| | IS INSULATED OR SOLID CORE AS REQUIRED |
| | BY FBC 13-603. |
| | |
| | 7) UPDATE THE SEMCO TRUSS CONNECTOR |
| | SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT |
| | ANCHOR WITH STATE OR LOCAL PRODUCT |
| | APPROVAL. |
| | |
| | 8)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 9) SUBMIT PRODUCT APPROVALS FOR THE 16' |
| | LONG MULLION BETWEEN THE SLIDING GLASS |
| | DOOR AND TRANSOM AT THE GREAT ROOM. THE |
| | ONE SUBMITTED ONLY LISTS UP TO 12' MULL |
| | LENGTHS. |
| | |
| | 10) SUBMIT PRODUCT APPROVALS FOR |
| | CASEMENT WINDOWS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |