Plan Review Details - Permit 04020684
Plan Review Stops For Permit 04020684
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2006-03-12 Cont ID  
Sent By rbrown Date 2006-03-12 Time 00:14 Rev Time 0.00
Received By rbrown Date 2006-03-12 Time 00:14 Sent To  
Notes
2006-03-12 00:00:00ARCHITECTURAL REVISION SUBMITTED
 11/28/05 FOR REVISED CEILING HEIGHTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2005-08-04 Cont ID  
Sent By rbrown Date 2005-08-04 Time 15:30 Rev Time 0.00
Received By rbrown Date 2005-08-04 Time 15:30 Sent To  
Notes
2005-08-04 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION SUBMITTED 6/22/05
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 --PROVISO--
 THE DOCUMENTS FOR THE DOOR AND WINDOW
 PERMIT APPLICATION PACKAGE (PERMIT#
 05020638) SHALL BE REVISED TO
 INCORPORATE THE NEW WINDOWS AND DOORS
 INTRODUCED BY THIS REVISION.
 ALTERNATIVELY, A SEPARATE PERMIT
 APPLICATION MAY BE SUBMITTED FOR THOSE
 DOORS AND WINDOWS.
  
  
 NOTE:
 THE FOLLOWING NON-COMPLIANCE HAS BEEN
 ACCEPTED IN ACCORDANCE WITH THE RULING
 OF CONSTRUCTION BOARD OF APPEALS ORDER
 (CASE# 1253):
 FBC 1003.2.5ON SHEET A-6.2 (STAIR
 NO.2 SECTION) THE HEADROOM IS SHOWN, AS
 AN "EXISTING CONDITION", AT 6 FT 6
 INCHES.THE REQUIREMENT OF THE CODE
 APPLICABLE TO THE CURRENT PROJECT IS 6
 FT 8 INCHES.ACCEPTED IN ACCORDANCE
 WITH CBAA CASE# 1253

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2005-07-25 Cont ID  
Sent By rbrown Date 2005-07-25 Time 11:53 Rev Time 0.00
Received By rbrown Date 2005-07-25 Time 15:30 Sent To  
Notes
2005-07-25 00:00:00ARCHITECTURAL REVISION SUBMITTED 6/2/05
 FOR SHEETS A-2.3.A, A-2.4, A-2.4A AND
 A-5.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-06-22 Cont ID  
Sent By rbrown Date 2005-06-22 Time 19:25 Rev Time 0.00
Received By rbrown Date 2005-06-22 Time 19:25 Sent To FIRE
Notes
2005-06-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 ARCHITECTURAL AND STRUCTURAL REVISION
 SUBMITTED 4/25/05
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC* 104.2SHEET A-2.2 SHOWS THE
 REVISED LAYOUT THE STAIR #9 WALKWAY AND
 THE CORRIDOR BETWEEN STAIR #2 AND #4.
 SHEETS A-1.1, A-2.7A, A-2.8, A-4.6,
 A-6.2 AND S1-2A HAVE NOT BEEN AMENDED TO
 REFLECT THE NEW LAYOUT.SUBMIT REVISED
 SHEETS.
  
 REMAINDER OF ARCHITECTURAL AND
 STRUCTURAL SHEETS HAVE BEEN
 REVIEWED/STAMPED AND ONE COPY RETAINED
 FOR CITY RECORDS.
  
 NOTE:
 THE FOLLOWING NON-COMPLIANCE HAS BEEN
 ACCEPTED IN ACCORDANCE WITH THE RULING
 OF CONSTRUCTION BOARD OF APPEALS ORDER
 (CASE# 1253):
 FBC 1003.2.5ON SHEET A-6.1 (STAIR
 NO.1 SECTION) AND SHEET A-6.2 (STAIR
 NO.2 SECTION) THE HEADROOM IS SHOWN, AS
 AN "EXISTING CONDITION", AT 6 FT 6-1/2
 INCHES AND 6 FT 6 INCHES RESPECTIVELY.
 THE REQUIREMENT OF THE CODE APPLICABLE
 TO THE CURRENT PROJECT IS 6 FT 8
 INCHES.ACCEPTED IN ACCORDANCE WITH
 CBAA CASE# 1253

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2005-01-03 Cont ID  
Sent By rbrown Date 2005-01-03 Time 16:34 Rev Time 0.00
Received By rbrown Date 2005-01-03 Time 16:34 Sent To  
Notes
2005-01-03 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL ON 12/28/04 FOR R.C. ALUMINUM
 DOOR AND WINDOW PACKAGE.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) THE PERMIT WAS ISSUED WITH THE
 FOLLOWING PROVISO:
  
 "INSUFFICIENT PRODUCT APPROVAL INFO:
 AS REQUESTED IN VILLA LOFTS' LETTER
 DATED APRIL 26, 2004, THE FIXED GLASS
 WINDOWS, HORIZONTAL SLIDING WINDOWS
 AND FRENCH DOORS SHALL BE UNDER A
 SEPARATE PERMIT WITH FEES BASED ON A
 MINIMUM VALUE OF $104,308.75"
  
 THIS CONDITION HAS NOT BEEN MET.THIS
 R.C. ALUMINUM PACKAGE WAS BROUGHT IN,
 ON
 12/28/04, AS A 'NO FEE SUBMITTAL'.
 RESUBMIT AS A SEPARATE PERMIT
 APPLICATION.THE FEE CALCULATION WILL
 BE BASED ON THE VALUE OF THE CONTRACT
 FOR THE R.C. ALUMINUM DOOR AND WINDOW
 PACKAGE
  
 2) A FULL REVIEW HAS NOT BEEN CARRIED
 OUT (SEE COMMENT 1, ABOVE).THE
 FOLLOWING INITIAL OBSERVATIONS ARE MADE
 ONLY TO EXPEDITE THE PROCESS.A FULL
 REVIEW WILL BE CARRIED OUT WHEN THE
 REQUIRED PERMIT APPLICATION IS
 RECEIVED.
  
 3) FBC* 101.4.2APPROPRIATE BUILDING
 CODE.R.C. ALUMINUM INDUSTRIES
 CALCULATION SHEET DC-1 CITES SOUTH
 FLORIDA BUILDING CODE 2004 FOR DESIGN.
 THE APPLICABLE CODE IS FLORIDA BUILDING
 CODE 2001 (WITH 2002 AND 2003
 AMENDMENTS).AMEND THE CALCULATIONS.
  
 4) SUBMITTED PRODUCT APPROVALS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
 (IF YOU FIND THAT THE QUOTED WEB PAGE
 IS
 NO LONGER AVAILABLE, PLEASE INFORM THE
 PLAN REVIEWER)
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL
 INFO
 TELEPHONE: (561) 805 6716ROBERT
 BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-12-07 Cont ID  
Sent By rbrown Date 2004-12-07 Time 10:25 Rev Time 0.00
Received By rbrown Date 2004-12-07 Time 10:25 Sent To  
Notes
2004-12-07 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 REVISION SUBMITTED 11/15/03
  
 1) FBC 1003.2.5ON SHEET A-6.1 (STAIR
 NO.1 SECTION) AND SHEET A-6.2 (STAIR
 NO.2 SECTION) THE HEADROOM IS SHOWN, AS
 AN "EXISTING CONDITION", AT 6 FT 6-1/2
 INCHES AND 6 FT 6 INCHES RESPECTIVELY.
 THE REQUIREMENT OF THE CODE APPLICABLE
 TO THE CURRENT PROJECT IS 6 FT 8
 INCHES.
 AMEND THE PLAN TO SHOW HOW THIS WILL BE
 ACHIEVED.IT IS NOTED THAT THIS IS AN
 EXISTING CONDITION BUT CURRENT CODE
 REQUIREMENTS FOR MEANS OF EGRESS MUST
 BE
 MET.
  
 2) FBC* 104.2.1.3SHEET S6-3 HAS ONE
 CLOUDED REVISION BUT THERE IS NO
 REVISION MARKER AND REVISION HISTORY
 HAS
 BEEN OMITTED FROM THE TITLE BLOCK.
 ALSO
 THE ADDITION OF DETAIL 14 HAS NOT BEEN
 FLAGGED.
  
 3) SHEET PT-1 THROUGH PT-4, THE
 POST-TENSION SHOP DRAWINGS SHALL BE
 REVIEWED AND STAMPED BY THE ENGINEER OF
 RECORD BEFORE SUBMITTAL.ALSO THE
 TITLE
 BLOCK SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION (ENGINEERING BUSINESS)
 NUMBER (EB 9829) FOR NEWTONIAN SOLUTIONS
 INC.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-11-18 Cont ID  
Sent By rbrown Date 2004-11-18 Time 12:54 Rev Time 0.00
Received By rbrown Date 2004-11-18 Time 12:54 Sent To  
Notes
2004-11-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL FOR NORMAN L BROWN
 SHORING ACCEPTANCE LETTER DATED
 10/18/04
  
 1) THE FIRST SENTENCE HAS BEEN ALTERED.
 ALL ALTERATION TO SIGNED AND SEALED
 DOCUMENTS SHALL BE INITAILED AND DATED
 BY THE ENGINEER THAT SEALED THE
 DOCUMENT.
  
 2) TO BE CONSISTENT WITH THE ABOVE
 ALTERATION, THE FIFTH SENTENCE SHOULD
 REFER TO INSPECTION OF RE-SHORING UNDER
 THE FIFTH FLOOR.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-11-18 Cont ID  
Sent By rbrown Date 2004-11-18 Time 12:44 Rev Time 0.00
Received By rbrown Date 2004-11-18 Time 12:44 Sent To  
Notes
2004-11-18 00:00:00STRUCTURAL SUBMITTAL FOR NORMAN L BROWN
 SHORING ACCEPTANCE LETTERS DATED
 10/8/04, 10/27/04, 11/9/04.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-09-17 Cont ID  
Sent By rbrown Date 2004-09-17 Time 17:57 Rev Time 0.00
Received By rbrown Date 2004-09-17 Time 17:57 Sent To  
Notes
2004-09-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 STRUCTURAL SUBMITTAL 9-1-04 FOR RAUL
 PUIG (EOR) SKETCHES, VSL SHOP DRAWINGS
 AND NORMAN BROWN SHORING PLANS.
  
 1) RAUL PUIG GROUP SKETCHES.
 61G15-23.002(2)FL. ADMIN. CODE.
 SHEETS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE THE PRINTED NAME
 AND LICENSE NUMBER OF THE ENGINEER AND
 THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS THROUGH WHICH THE ENGINEER IS
 PRACTICING (471.025 F.S AND 471.023 F.S)
  
 2) NORMAN L. BROWN III, P.E. SHORING
 PLANS.
 STRUCTURAL SHOP DRAWINGS SHALL BE
 REVIEWED AND STAMPED BY THE ENGINEER OF
 RECORD BEFORE SUBMITTAL.
  
 3) VSL SHOP DRAWINGS.
 (A) SUBMIT THREE COPIES OF ALL PLANS.
 ONLY TWO WERE COPIES SUBMITTED.
 (B) 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE THE NAME AND
 LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS THROUGH WHICH THE ENGINEER IS
 PRACTICING (471.025 F.S AND 471.023 F.S)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-27 Cont ID  
Sent By csiegber Date 2004-09-01 Time 13:09 Rev Time 0.00
Received By rbrown Date 2004-04-27 Time 08:51 Sent To  
Notes
2004-04-19 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
  
 INSUFFICIENT PRODUCT APPROVAL INFO:
 AS REQUESTED IN VILLA LOFTS' LETTER
 DATED APRIL 26, 2004, THE FIXED GLASS
 WINDOWS, HORIZONTAL SLIDING WINDOWS AND
 FRENCH DOORS SHALL BE UNDER A SEPARATE
 PERMIT WITH FEES BASED ON A MINIMUM
 VALUE OF $104,308.75

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-04-02 Cont ID  
Sent By rbrown Date 2004-04-02 Time 19:49 Rev Time 0.00
Received By rbrown Date 2004-03-16 Time 16:42 Sent To Z
Notes
2004-03-16 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 3401.7.1ADDITION TO AN EXISTING
 BUILDING.THE NEW 'TOWER' IS CONSIDERED
 AS AN ADDITION AND IT'S AREA EQUALS 25%,
 OR MORE, OF THE AREA OF THE EXISTING
 BUILDING.EITHER (A) THE EXISTING
 BUILDING SHALL BE UPGRADED TO COMPLY
 WITH THE CODE IN EFFECT ON FEB' 14, 2004
 (THE DATE OF PERMIT APPLICATION), EXCEPT
 THE STRUCTURAL REQUIREMENTS OF THE CODE,
 OR (B) THE NEW 'TOWER' SHALL BE
 SEPERATED FROM THE EXISTING BUILDING BY
 A FOUR HOUR RATED FIRE WALL.
  
 2) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, NO CERTIFICATE OF
 OCCUPANCY CAN BE ISSUED UNTIL A
 'DECLARATION OF CONDOMINIUM' HAS BEEN
 SUBMITTED TO THE STATE FOR APPROVAL, AND
 THEN RECORDED WITH THE CLERK OF THE
 COUNTY COURT.A RECORDED COPY SHALL BE
 SUBMITTED TO THE CITY FOR RECORDS,
 ADDRESSING PURPOSES, AND NOTIFICATION OF
 PALM BEACH COUNTY PROPERTY APPRAISER'S
 OFFICE.
  
 3) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
 ALSO, THE CORRECT JURISDICTION NAME AND
 NUMBER IS 'WEST PALM BEACH (604700)',
 THE CORRECT PROJECT ADDRESS IS
 1617 N. FLAGLER DR (CITY: WEST PALM BCH,
 ZIP: 33407), THE CORRECT PERMIT NUMBER
 IS 04020684 AND THE OCCUPANCY IS
 RESIDENTIAL.AMEND THE ENERGY CODE
 COMPLIANCE FORM.
  
 4) FBC 13-103.1.1.1IT IS NOTED THAT
 RAFAEL PENA'S NAME AND LICENSE NUMBER
 ARE ON SHEET TWO OF THE ENERGY CODE
 COMPLIANCE FORMS, BUT THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN THE ENERGY CODE
 COMPLIANCE FORM, TO CERTIFY COMPLIANCE.
  
 5) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 6) FBC* 104.6.5BUILDING PERMIT
 VALUATION.THE STATED VALUE OF THE
 PROJECT HAS BEEN UNDER-ESTIMATED AT
 $4,832,516.THE VALUE CALCULATED USING
 THE SOUTHERN BUILDING CODE CONGRESS
 INTERNATIONAL (SBCCI) VALUATION TABLES
 IS $5,563,825.THE PERMIT APPLICATION
 FEE HAS BEEN ADJUSTED ACCORDINGLY, SO
 THERE IS AN OUTSTANDING BALANCE OF
 $32,886.96 WHICH INCLUDES $573.50 RADON
 FEES AND THE BALANCE OF THE PERMIT FEES
 NOT PAID AT THE TIME OF APPLICATION.
  
 7) 61G15-23.002(2)FL. ADMIN. CODE.
 STRUCTURAL ENGINEER'S PLANS FS-1 TO S7-5
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE THE CERTIFICATE
 AUTHORIZATION NUMBER (6063 FOR THE RAUL
 PUIG GROUP, P.A.) FOR THE ENGINEERING
 BUSINESS THROUGH THROUGH WHICH THE
 ENGINEER IS PRACTICING.
 (471.025 F.S. AND 471.023 F.S.).
  
 8) FBC 104.2.2 ONE SET OF THE STRUCTURAL
 PLANS DOES NOT HAVE AN THE ORIGINAL
 SIGNATURE OR RAISED SEAL OF THE ENGINEER
  
 9) FBC 503.2.6SPECIAL UNLIMITED HEIGHT
 FOR TYPE II BUILDINGS.SHEET A-1.1,
 CODE ANALYSIS TABLE STATES THAT THE
 ROOF/CEILING AND THE BEAMS, GIRDERS,
 TRUSSES AND ARCHES REQUIRE FIRE
 RESISTANCE RATING OF 1-HR.BECAUSE THE
 BUILDING IS TO BE TYPE II CONSTRUCTION
 AND EXCEEDS 80 FEET IN HEIGHT A MINIMUM
 OF 1-1/2 HOURS FIRE RESISTANCE RATING IS
 REQUIRED FOR THE ROOFS AND THEIR
 SUPPORTING BEAMS, GIRDERS, TRUSSES AND
 ARCHES.ALSO THE NOTE ABOUT FIRE
 RESISTANCE RATING BEING NOT REQUIRED FOR
 STRUCTURE SUPPORTING ROOF ONLY, WHERE
 THE CLEAR HEIGHT IS AT LEAST 20 FEET, IS
 NOT APPLICABLE AND SHOULD BE DELETED.
 AMEND SHEET A-1.1
  
 10) FBC 412.5SMOKE CONTROL.THE PLANS
 DO NOT DEMONSTRATE FULL COMPLIANCE WITH
 FBC 412.5(3).AMEND THE PLANS TO SHOW
 COMPLIANCE WITH ON OF THE SMOKE CONTROL
 OPTIONS IN FBC 412.5
  
 11) FBC 1012.1.2 EGRESS DOOR.SHEETS
 A-2.1.D AND A-2.1 SHOW AN INWARD OPENING
 PARKING GARAGE EXIT DOOR ADJACENT THE
 AT&T ROOM.THE DOOR SHALL SWING OUTWARD
 TO OPEN IN THE DIRECTION OF EGRESS.
  
 12) FBC 1003.3.4SHEET A-2.1, PARKING
 GARAGE EXIT.THE PARKING SPACE ADJACENT
 THE EXIT BY THE AT&T ROOM SHALL BE
 'PAINTED OUT' AND NO LONGER USED, IN
 ORDER TO MAINTAIN THE REQUIRED EXIT
 WIDTH.
  
 13) FBC 1004.1.2SHEET A-2.1, EGRESS
 FROM EMPLOYEE LOUNGE.THE TRAVEL
 DISTANCE TO THE EXIT EXCEEDS 75 FEET AND
 EGRESS THROUGH THE PARKING GARAGE IS NOT
 PERMITTED, SO THERE IS NO ALTERNATIVE
 ROUTE.RELOCATE THIS ROOM TO REDUCE THE
 TRAVEL DISTANCE.
  
 14) FBC TABLE 705.1.2SHEET A-4.1.THE
 TRASH ROOM SHALL BE SHOWN TO HAVE A MIN.
 1-HR FIRE RATING FOR ALL WALLS
 (INCLUDING EXISTING) AND A 3/4 HR RATING
 FOR THE DOOR (EXISTING).
  
 15) FBC 1005.6.5SHEET A-2.1.STAIR #2
 SHALL NOT DISCHARGE THROUGH THE PARKING
 GARAGE.AMEND THE PLANS TO SHOW CODE
 COMPLIANT EXIT DISCHARGE FROM STAIR #2.
  
 16) FBC 1004.1.4SHEET A-2.2.THE
 COMMON PATH OF TRAVEL FROM THE SECOND
 FLOOR COMMON AREA (AND BAR) EXCEEDS
 75 FEET.ANNOTATE THE PLANS (INCLUDING
 SHEET A-4.4) TO CONFIRM AVAILABILITY OF
 ALTERNATIVE EGRESS, THROUGH THE EXISTING
 EAST TOWER, VIA THE OPENING OPPOSITE THE
 MANAGER'S OFFICE DOOR.
  
 17) FBC 1003.1.2SHEET A-2.2.PROVIDE
 A LIFE SAFETY PLAN TO SHOW OCCUPANT LOAD
 AND EGRESS FOR THE TRANQUILITY GARDEN,
 POOL DECK AND POOL.
  
 18) FBC 1006.1.1SHEET A-2.3.NO EXIT
 DOOR IS SHOWN AT STAIR #1.AMEND THE
 PLAN.
  
 19) FBC 412.6.2ELEVATOR LOBBIES.THE
 TRASH CHUTE AND ELECTRICAL ROOMS SHALL
 NOT OPEN INTO THE ELEVATOR LOBBIES.
 AMEND THE PLANS.
  
 20) FBC 1608.2.2SHEET A-8.1. GUARDRAIL
 DETAILS 3, 4, AND 8.NOTE 4 GIVES AN
 INCOMPLETE SPECIFICATION FOR GUARDRAIL
 STRENGTH REQUIREMENTS.THE GUARDRAIL
 SHALL BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB APPLIED IN
 ANY DIRECTION AT THE TOP OF THE
 GUARDRAIL, A CONCENTRATED HORIZONTAL
 LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA
 AT ANY POINT, AND A LINE LOAD OF 50 PLF
 APPLIED HORIZONTALLY AT THE REQUIRED
 GUARDRAIL HEIGHT WITH A SIMULTANEOUS
 LINE LOAD OF 100 PLF APPLIED VERTICALLY
 DOWNWARD ON THE TOP OF THE GUARDRAIL.
 THESE LOADS SHALL NOT BE APPLIED
 SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT
 SHALL BE APPLIED INDIVIDUALLY TO PRODUCE
 MAXIMUM STRESS IN EACH OF THE COMPONENTS
 OR SUPPORTS.AMEND/ANNOTATE THE PLANS.
 NOTE:THESE LOADS ALSO APPLY TO THE
 GUARDING SHOWN ON SHEET A-6.3, DETAILS
 2, 3, 6 AND 9 (THE SPECIFIED HANDRAIL
 LOADING IS NOTED).
  
 21) FBC 11-4.1.2(5)(E)VALET PARKING.
 AMEND THE NOTE ON SHEET A-1.1 TO STATE
 THAT VALET PARKING WILL BE PROVIDED IN
 ACCORDANCE WITH FBC 11-4.1.2(5)(E) AND
 FBC 11-4.6.6.
  
 22) FBC 11-4.13.6MANEUVERING CLEARANCE
 AT DOORS.AMEND DOOR 12 ON SHEET A-4.1
 AND DOORS 29 AND 31 ON SHEET A-4.3 TO
 SHOW THE REQUIRED 18" CLEARANCE BETWEEN
 THE STRIKE EDGE OF THE DOOR AND THE
 ADJACENT WALL ON THE PULL SIDE OF THE
 DOOR (REF FIG. 25)
  
 23) FBC 3003.4.1STRETCHER ACCESSIBLE
 ELEVATOR.AT LEAST ONE PASSENGER
 ELEVATOR SHALL ACCOMMODATE AN AMBULANCE
 STRETCHER 76" LONG AND 24" WIDE IN THE
 HORIZONTAL POSITION.THIS ELEVATOR
 SHALL BE IDENTIFIED BY SIGNAGE.AMEND
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 24) FBC 2405.2THE FOLLOWING GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201):
 DOOR #12 (SHEET A-5.1 - DOOR SCHED.)
 DOOR #28 (SHEET A-5.1 - DOOR SCHED.)
 DOOR #29 (SHEET A-5.1 - DOOR SCHED.)
 DOOR #37 (SHEET A-5.1 - DOOR SCHED.)
 SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE
  
 25) SUBMIT PRODUCT APPROVALS FOR THE
 ROOF COVERINGS, WINDOWS, EXTERIOR DOORS
 AND EXTERIOR SLIDING GLASS DOORS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 26) PRODUCT APPROVAL.RULE 9B-72 FAC.
 FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE
 PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL
 CAN BE ACHIEVED IF THERE IS A QUALITY
 ASSURANCE PROGRAM IN PLACE WITH A STATE
 APPROVED QUALITY ASSURANCE ENTITY.IF
 NEITHER IS APPLICABLE, THEN SITE
 SPECIFIC APPROVAL IS REQUIRED.LOCAL
 PRODUCT APPROVAL WILL ALLOW A PRODUCT TO
 BE USED, IN ACCORDANCE WITH THE TEST
 CRITERIA, THROUGHOUT THE JURISDICTION OF
 WEST PALM BEACH.SITE SPECIFIC PRODUCT
 APPROVAL WILL ALLOW A PRODUCT TO BE
 USED ONLY ON THE PROJECT FOR WHICH THAT
 SITE SPECIFIC APPROVAL IS GRANTED.
 LOCAL AND SITE SPECIFIC PRODUCT APPROVAL
 APPLICATION FORMS ARE AVAILABLE FROM
 THIS OFFICE.APPROVED QUALITY ASSURANCE
 ENTITIES ARE LISTED ON THE DCA WEBSITE:
 WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_
 REGI_SRCH.ASP
  
 27) FBC 1606.1.7WIND LOAD. SHEET S0.0,
 DESIGN LOAD NOTE #2 REFERS TO 'SOUTH
 FLORIDA BUILDING CODE 1994' FOR WIND
 DESIGN.AMEND THE NOTE TO READ 'FLORIDA
 BUILDING CODE 2001'.ALSO THE PLANS
 SHALL STATE THE BASIC WIND SPEED, WIND
 IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.AMEND THE PLANS.
  
 28) FBC TABLE 600.FIRE RESISTANCE.
 SHT S0.0 (EG.REINFORCING STEEL NOTE #3)
 MAKES NO REFERENCE TO THE REQUIRED FIRE
 RESISTANCE RATINGS FOR THE STRUCTURAL
 ELEMENTS AS LISTED ON SHEET A-1.1.
 CO-ORDINATE THE ARCHITECTURAL AND
 STRUCTURAL PLANS TO ENSURE ADEQUATE
 FIRE RESISTANCE FOR THE STRUCTURAL
 MEMBERS.
  
 29) FBC 3502REFERENCE STANDARDS.
 SHEET A-9.1, GENERAL NOTES #24 AND #25
 REFER TO OUT-DATED CODES AND SHALL BE
 AMENDED AS FOLLOWS:
 - ACI 530.1-95/ASCE 6-96/TMS 602-95
 SHALL READ ACI 530.1/ASCE 6/TMS 602-02
 - ASTM C 91-66 SHALL READ ASTM C 91-91
 - ASTM C 150-67 SHALL READ ASTM C 150-94
 - ASTM C 34-62 SHALL READ ASTM C 33-62
  
 30) FBC 3502REFERENCE TO ASCE 7.
 SHEET A-9.1, STOREFRONT/../DOOR NOTE #4
 AND SHEET A-9.2 ROOFING NOTE D BOTH
 REFER TO ASCE 7-95.AMEND THE REFERENCE
 TO READ ASCE 7-98
  
 31) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2006-04-07 Cont ID  
Sent By jleahy Date 2006-04-07 Time 06:32 Rev Time 2.00
Received By jleahy Date 2006-04-07 Time 06:31 Sent To  
Notes
2006-04-07 00:00:00AS BUILTS FOR JOB WENT OVER WITH DAN
 KEMPA. 4/6/06

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 14:39 Sent To  
Notes
2005-12-24 00:00:00REV'S FOR
  
 E-2,3,4,5,10 AND 15 OK, STAMPED.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-12-07 Cont ID  
Sent By dpalmer Date 2005-12-07 Time 21:33 Rev Time 0.00
Received By dpalmer Date 2005-12-07 Time 21:33 Sent To  
Notes
2005-12-07 00:00:00REDLINED,
 FIRE PUMP FEEDERS, SEC'S SHALL NOT BE
 SPLICED OR IN SAME SPLICE BOX.
 MUST BE INCASED/OR UNDER BLDG.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-09-27 Cont ID  
Sent By dpalmer Date 2005-09-27 Time 19:16 Rev Time 1.00
Received By dpalmer Date 2005-09-27 Time 19:16 Sent To  
Notes
2005-09-27 00:00:00REDLINED EQUIPMENT GROUNDING CONDUCTORS
 IN NUMEROUS LOCATION ON RISER WHICH
 APPEAR TO BE MISSING.
 RESPONSE LTR MENTIONED RMC IS NOT BEING
 INSTALLED.
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-07-18 Cont ID  
Sent By dpalmer Date 2005-07-18 Time 07:39 Rev Time 1.50
Received By dpalmer Date 2005-07-15 Time 20:53 Sent To  
Notes
2005-07-18 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM CONDUITS ON
 RISER DIAGRAM. PLEASE SEE SOME OF THESE
 WERE NOTED ON PREVIOUS REVIEW.
 MAIN 1 TO TAP BOX? ETC,
 250.110,250.24,250.122
  
 2)NOTE: PLEASE SEE APARTMENT PANEL "C",
 WHICH APPEARS TO SHOW DRYER AND WASHER
 AS "SPARE"? PLEASE SEE NEC
 210.52F,210.11C2 WHICH REQUIRES A MIN OF
 ONE LAUNDRY RM CIRCUIT/WASHER FOR A
 DWELLING.
  
 3)NOTE: PLEASE SEE PREVIOUS REQUESTED
 FIRE PUMP/ FIRE PUMP CONTROLLER,
 GENERATOR, AND ATS TO BE PERMITTED. THIS
 WAS GIVEN ON PROVISO AND THIS MUST BE
 ADDRESSED BEFORE REVISIONS WILL BE
 STAMPED.
  
 4)NOTE: PLEASE SEE REVISED ELECTRICAL
 ROOMS, ELEVATOR MACHINE RM IS NOW NOT ON
 PLANS??
 PLEASE CLARIFY?
 620.23,620.24
  
 5)NOTE: PLEASE SEE 445.13 FOR AMPACITY
 OF CONDUCTORS FOR GENERATOR.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-07-15 00:00:00PLANS IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-05-17 Cont ID  
Sent By dpalmer Date 2005-05-17 Time 09:55 Rev Time 1.50
Received By dpalmer Date 2005-05-17 Time 09:25 Sent To  
Notes
2005-05-17 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE "PROVISO" GIVEN ON
 4/18/04.
 PLEASE SEE NO FURTHER ELECTRICAL
 REVISIONS SHALL BE STAMPED FOR REVIEW
 UNTIL FIRE PUMP/FIRE PUMP CONTROLLER,
 GENERATOR/ATS ETC IS APPLIED FOR FOR
 PERMIT.
 THIS WAS REQUESTED OVER 1YR AGO.
  
 2)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS SHOWN FROM FPL/METER TO THE
 FIRST MEANS OF DISCONNETC. (FIRE PUMP )?
 PLEASE SEE SOME CONDUITS ON RISER ARE
 MISSING EQUIPMENT GROUNDING CONDUCTORS.
 250.24,250.110, SIZED PER 250.122
  
  
 NOTES FOR SIGNAGE AND MAPPING ADDED ON
 PLANS.
 MCB WAS ADDED TO EDP.
  
 PLEASER BE SURE TO SUBMIT INFORMATION
 FOR PERMIT BEFORE FURTHER REVISIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-12-02 Cont ID  
Sent By dpalmer Date 2004-12-02 Time 16:48 Rev Time 2.50
Received By dpalmer Date 2004-12-02 Time 16:48 Sent To  
Notes
2004-12-02 00:00:00*********** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES FROM "PROVISO"
 WHEN PLANS WERE ISSUED.
 NONE OF THESE PROVISO NOTES HAVE BEEN
 ADDED OR ADDRESSED.
  
 2)NOTE: PLEASE SEE GENERATOR PERMIT HAS
 NOT BEEN APPLIED FOR AT THE DATE OF
 THIS
 REVIEW.
  
 3)NOTE: NOTE FOR ALUM CONDUCTORS HAS
 BEEN ADDED, HOWEVER NO CHANGES TO
 CONDUCTORS HAS BEEN MADE. PLEASE
 INDICATES IF THESE CONDUCTORS ARE TO BE
 CHANGED OR REMAIN COPPER.
 ANY CHANGES IN TYPE AND SIZES OF THESE
 ARE REQUIRED TO BE REVIEWED BEFORE
 INSTALLATION.
 310.16,240.4, 215.5 ETC
  
 NO REVISIONS WILL BE SIGNED OFF UNTIL
 ORIGINAL PROVISO/REDLINES HAVE BEEN
 ADDRESSED.
  
  
 ****************************************
 ***************************************
 PLEASE SEE OUR SYSTEM SHOWS LICENSE
 INFORMATION ETC FOR BOB MOSS
 CONTRACTING
 AS EXPIRED.
 PLEASE UPDATE RECORDS ASAP.
  
 ***************************************
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-18 Cont ID  
Sent By dpalmer Date 2004-04-18 Time 16:47 Rev Time 2.00
Received By dpalmer Date 2004-04-18 Time 16:33 Sent To  
Notes
2004-04-18 00:00:00******* NOTES REDLINED *******
 ******* PROVISO ********
  
 1)NOTE: PLEASE PROVIDE ALL INFORMATION/
 SPECS FOR FIRE PUMP CONTROLLER/ PUMP/
 AND GENERATOR.
 PLEASE SEE FIRE REVIEW COMMENTS PERTAIN-
 ING GENERATOR SYSTEM. THIS WILL BE REQ'D
 TO BE UNDER A SEPARATE PERMIT.
 PLEASE BE SURE FIRE PUMP CONTROLLER
 MEETS 230.76,230.79 AND 110.27
 FIRE DEPT MAY NOT OPEN EQUIPMENT TO
 DISCONNECT POWER. 110.27ALL SPECS WILL
 BE REQUIRED TO BE SUBMITTED W/PERMIT
 APPLICATION IF NOT BEFORE, PENDING FIRE
 REVIEW COMMENTS.
  
 2)NOTE: NOTES REDLINED FOR ALL REQ'D
 SIGNAGE AT EACH ELECTRICAL ROOM AND FIRE
 PUMP ROOM. SIGNAGE AND A DIAGRAM WILL BE
 REQ'D AT FIRE CONTROL ROOM TO INDICATE
 AND DIRECT FIRE DEPT PERSONNEL TO ALL
 MAIN ELECTRICAL ROOMS/ GENERATOR LOCAT-
 -IONS/FIRE PUMP ROOMS.
 230.2E
  
 3)NOTE: NOTES REDLINED FOR PANIC HARD-
 -WARE REQ'D ON MAIN ELECTRICAL ROOM
 DOORS PER 110.26
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 AS THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-04 Cont ID  
Sent By dpalmer Date 2004-03-04 Time 11:50 Rev Time 8.00
Received By dpalmer Date 2004-03-04 Time 07:46 Sent To  
Notes
2004-03-04 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE FS 481.219, 471.023.
 PLANS REQ;D TO HAVE ALL LICENSE #'S
 AS REQ'D PER ABOVE ON TITLE BLOCKS PER
 FAC 61G15-23.002, 61G1-16.004
 THIS IS REQ'D FOR ARCH'S AND ENG'S.
 THIS IS ALSO REQ'D ON ALL SHEETS AND
 FOR ALL TRADES WEATHER OR NOT COMMENT
 IS MADE BY OTHERREVIEWERS.
  
 2)NOTE: PLEASE 110.26 FOR EXITING REQ'D
 FOR ELECTRICAL ROOMS. MIN.
  
 3)NOTE; PLEASE NOTE ON PLANS/RISER.
 TACTICAL SIGNAGE/MAPS BE REQ'D FOR FIRE
 PERSSONELL TO MAIN ELECTRICAL ROOMS.
 KNOX BOX FOR KEYS TO MAIN ELECTRICAL
 ROOMS.
  
 4)NOTE: PLEASE SEE CIRCUITING FOR SD'S
 IN UNITS. SHOWS SD'S ON MORE THAN ONE
 CIRCUIT. SD'D ARE REQ'D TO BE WIRED
 "INLINE", THIS WOULD CAUSE AN ELECTRIC-
 -AL PROBLEM ON MORE THAN ONE CIRCUIT.
 PLEASE SEE NFPA-72 8-1.4.2 FOR INSTALL-
 -ATION OF SD'S AND CLEARENCES FROM BATH
 / KITCHEN DOORS AND FROM KITCHEN COOKING
 APPLIANCES. A NOTE MAY BE ADDED FOR THIS
  
 5)NOTE: PLEASE SEE SOME UNITS DO NOT
 SEEM TO HAVE COMPLETED WALLS. DOES NOT
 SHOW RECEPTS REQUIRED FOR WALLS,210.52
 EGRESS LT CONTROL PER 210.70
 ETC.
  
 6)NOTE: PLEASE PROVIDE PLANS FOR
 EXISTING TOWER ELECTRICAL TO BRING UP TO
 2002 NEC PER FBC CHAPTER 34 FOR ADDITION
 -S TO EXISTING BLDGS.
  
 7)NOTE: PLEASE SEE UNIT "F" PANEL.
 SHOWS 164.9A'S W/ 200A OCP AND CONDUCTOR
 -S NOT RATED FOR 200A'S PER 310.16
  
 8)NOTE: PLEASE INDICATE OCP FOR EACH
 UNIT/PANEL. PLEASE CORRELATE OCP/AWG
  
 9)NOTE: PLEASE CLARFIY/SHOW EQUIPMENT
 GROUNDING CONDUCTORS REQ'D. 250.110
 250.24, SIZE PER 250.122
  
 10)NOTE: PLEASE SEE AIC RATINGS SHOWN
 FOR PANELS, SHOWS 100,000 RATED PANELS
 PLEASE VERFIY. IF SHOWN AS 100,000, THEN
 THATS WHAT WILL BE REQ'D TO BE INSTALLED
  
 11)NOTE: PLEASE SEE NOTES MENTION THAT
 ALUM CONDUCTORS AMY BE USED.
 PER LOCAL AMENDMENTS ALUM CONDUCTOR ARE
 NOT PERMITTED TO BE USED FOR GROUNDING
 OR BONDING. 310.2
 CONTRACTOR MAY ALSO NOT JUST CHANGE
 SIZES AND TYPE OF CONDUCTORS UNTIL PLANS
 ARE REVISED BY THE ENGINEER OF RECORD,
 SUBMITTED TO THE CITY OF WEST PALM BEACH
 FOR REVIEW AS A REVISION.
 PLEASE ADJUST NOTE.
  
 12)NOTE: PLEASE LIST/NOTE THE REQUIRED
 ARC FAULT PROTECTED CIRCUITS PER 210.12
 ON PANEL SCHEDULES FOR UNITS.
  
 13)NOTE: PLEASE SEE LOAD SHOWN FOR
 PANELS "E" AND "F".
 LOAD CALCS SEEM TO BOTH FIGURED IN AS
 TYPICAL??
  
 14)NOTE: PLEASE PROVIDE OCP/ NOTE
 FOR MAIN FOR FIRE PUMP 695.4B1
  
 15)NOTE: PLEASE SEE EDP, PLEASE CORRE-
 -LATE OCP / AWG'S PER 310.16.
 WIRE SIZES ARE NOT RATED FOR OCP.
  
 PLANS SHOULD REFERENCE 2002 NEC
 PLEASE GO OVER PLANS FOR CODE COMPLIANCE
 BEFORE RESUBMITTING.
 PLANS WILL HAVE A ONE TIME RESUB @ NO
 CHARGE, EACH TIME THEREAFTER WILL BE A
 10% RESUB FEE.
  
 SEPARATION OF 4 HR FIRE WALL WILL BE
 REQUIRED BETWEEN NEW AND EXSITING IF
 CHAPTER 34 FBC IS NOT AN OPTION.
  
 COMPLETE ELECTRICAL REVIEW CAN NOT BE
 DONE AT THIS TIME DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-12-03 Cont ID  
Sent By mamini Date 2004-12-03 Time 08:39 Rev Time 0.50
Received By mamini Date 2004-12-03 Time 08:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2004-04-13 Cont ID  
Sent By mamini Date 2004-04-13 Time 13:57 Rev Time 1.00
Received By mamini Date 2004-04-13 Time 13:57 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2004-02-25 Cont ID  
Sent By mamini Date 2004-02-25 Time 15:03 Rev Time 1.00
Received By mamini Date 2004-02-25 Time 15:03 Sent To  
Notes
2004-02-25 00:00:00FAILED:
 1. COMMENTS AND ISSUES WITH PUBLIC
 UTILITIES IN REGARD TO CIVIL PLANS
 MUST BE ADDRESSED AND RESOLVED PRIOR TO
 CONSTRUCTION SERVICES DEPARTMENT'
 APPROVAL.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2005-12-30 Cont ID  
Sent By mwennerg Date 2005-12-30 Time 10:27 Rev Time 0.00
Received By mwennerg Date 2005-12-30 Time 10:27 Sent To  
Notes
2005-12-30 00:00:00******PASSED******
  
 NEW SHEETS ILLUSTRATING SMOKE BOMB
 LOCATIONS WERE SUBMITTED WITH REVISED
 SHEETS. PLEASE COORDINATE THE SMOKE TEST
 WITH THE BUREAU OF FIRE PREVENTION AND
 CONSTRUCTION SERVICES. THE ENGINEER
 RESPONSIBLE FOR THE DESIGN OF THE SMOKE
 CONTROL/EVAC SYSTEM SHALL BE PRESENT
 DURING THE TEST.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2005-07-27 Cont ID  
Sent By mwennerg Date 2005-07-27 Time 13:30 Rev Time 0.00
Received By mwennerg Date 2005-07-27 Time 13:30 Sent To  
Notes
2005-07-27 00:00:00SHEETS FP-1, FP-2 & FP-3A SUBMITTED FOR
 REVISION DATED 6/20/05

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2005-06-24 Cont ID  
Sent By mcarsill Date 2005-06-24 Time 10:37 Rev Time 0.00
Received By mcarsill Date 2005-06-24 Time 10:37 Sent To  
Notes
2005-06-24 00:00:00PLEASE REVIEW CBAA CASE NUMBER 1253
 FOR DETAILS.
  
 MIKE CARSILLO, FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2004-12-15 Cont ID  
Sent By mcarsill Date 2005-06-20 Time 13:10 Rev Time 0.00
Received By mcarsill Date 2005-06-20 Time 13:10 Sent To FIRE
Notes
2005-06-20 00:00:00CALLED PAM YUSKO, CBAA SECRETARY AND
 REQUESTED ON HER VOICE MAIL THE
 CBAA DOCUMENTS FOR CASE # 1253
 REGARDING VARIANCE FOR PREVIOUS
 ISSUE.
  
 MIKE CARSILLO, FIRE MARSHAL
 835-2910
2004-12-15 00:00:001. WRONG HEADROOM NOTED FOR STAIR # 1.
 MINIMUM HEADROOM CODE IS TO BE MET.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-04-22 Cont ID  
Sent By mcarsill Date 2004-04-22 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2004-12-15 Time 09:57 Sent To  
Notes
2004-04-22 00:00:001) THE ALTERNATIVE EGRESS FROM THE 2ND
 FLOOR COMMON AREA THAT IS PROVIDED
 THROUGH THE EXISTING TOWER SHALL BE
 WIDE ENOUGH TO ACCEPT THE
 ANTICIPATED LOAD.
  
 2) NO STORAGE IS PERMITTED IN ANY
 IDENTIFIED VOID AREAS DESIGNATED
 ON THE PLANS. IF STORAGE IS PLANNED,
 THE FIRE SPRINKLER PROTECTION IS
 REQUIRED.
  
 3) OAK TREES PLANNED CANNOT INTERFERE
 WITH ANY FIRE LANES.
  
 4) THE MIAMI STANDARD1 1/2 THREAD
 NOTE IS NOT APPLICABLE TO THE CITY
 OF WEST PALM BEACH. PAGE FP-7.
  
 5) ROOF PLAN PAGE FP-5 INDICATES
 FDC'S. THESE SHOULD BE CALLED ROOF
 MANIFOLDS.
  
 6) PRODUCT DATA WILL BE REQUIRED FOR
 THE FIRE PUMP AND EMERGENCY
 GENERATOR. SEPARATE PLANS AND PERMITS
 REQUIRED.
  
 7) SINCE EOL'S ARE SHOWN, THE FIRE
 ALARM SYSTEM SHALL BE FULLY
 ADDRESSABLE.
  
 8) SMOKE DETECTORS IN UNITS B & C APPEAR
 TO BE INSTALLED TOO CLOSE TOGETHER.
 PLEASE REVISE.
  
 9) EXIT SIGNS NEEDED NEAR GARAGE DOUBLE
 DOOR EXIT TUNNEL. PLEASE PROVIDE.
  
 10) PLEASE SEE ELECTRICAL PLAN
 REVIEWER NOTES.
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-02-18 Cont ID  
Sent By mcarsill Date 2004-02-18 Time 07:31 Rev Time 0.00
Received By mcarsill Date 2004-02-18 Time 07:31 Sent To  
Notes
2004-02-18 00:00:001) ELECTRONIC SWITCHES WILL BE
 REQUIRED ON THE FIRE LINE BACKFLOW
 DEVICE.
  
 2) A TEMPORARY STANDPIPE SYSTEM WILL
 BE REQUIRED WHEN THE BUILDING REACHES
 THREE STORIES OR 30 FEET IN HEIGHT.
  
 3) EGRESS STAIRS FOR THE BUILDING
 SHALL BE KEPT UP WITH CONSTRUCTION.
  
 4) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH
 NFPA 241.
  
 5) A KNOX-BOX WILL BE REQUIRED.
  
 6) ON A RECENT VISIT, THE EXISTING
 PARKING GARAGE DISPLAYED POSSIBLE
 CODE VIOLATIONS. IT IS UNKNOWN IF
 THE REQUIRED VENTILATION SYSTEM FOR
 THE GARAGE IS WORKING. ALSO ALMOST
 ALL OF THE REQUIRED EXIT SIGNS WERE
 NOT ILLUMINATED. PLEASE ADVISE
 DISPOSITION OF THESE CODE VIOLATIONS.
  
 7) A TWO HOUR FIRE SEPARATION IS
 REQUIRED BETWEEN THE EXISTING PARKING
 GARAGE AND THE NEW TOWER.
  
 8) PLEASE INDICATE WHICH ELEVATORS
 WILL BE STRETCHER ACCESSIBLE.
  
 9) NO DOOR PRESENT FOR STAIR # 1 ON
 PAGE A-2.3.
  
 10) TACTILE SIGNAGE REQUIRED AT
 STAIRWELL DOORS.
  
 11) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY IN 6" HIGH LETTERS.
  
 12) THE GROUND FLOOR LIFE SAFETY PLAN
 APPEARS CONFUSING. PLEASE CLARIFY.
  
 13) THE BUILDING ADDRESS IS REQUIRED
 ON THE NEW BUILDING. A MINIMUM OF 6"
 HIGH NUMBERS ARE REQUIRED.
  
 14) FDC'S ARE NOTED ON THE ROOF. THEY
 SHOULD READ ROOF MANIFOLDS.
  
 15) PLEASE NOTE ON THE PLANS ALL
 REQUIRED ITEMS TO BE INSTALLED IN
 THE FIRE COMMAND ROOM AS PER 412 OF
 THE FLORIDA BUILDING CODE.
  
 16) THE NEW FIRE ALARM SYSTEM IS
 REQUIRED TO BE UL LISTED FOR CENTRAL
 STATION SERVICE.
  
 17) PLANS NEED TO MENTION "ANTICIPATED
 STACK" ON THE MECHANICAL PLANS.
  
 18) ELEVATOR WARNING SIGNS REQUIRED.
  
 19) PLEASE INDICATE OCCUPANT LOAD FOR
 POOL DECK.
  
 20) ALL NEW STAIRS AND RAMPS SHAL HAVE
 HANDRAILS ON BOTH SIDES.
  
 21) PLEASE PROVIDE DETAILS ON SOUND
 ATTENUATION INSULATION FOR TRASH
 CHUTE.
  
 22) PLEASE DEMONSTRATE THAT GUARDRAILS
 ON STAIRS WILL RESIST A 4" SPHERE.
  
 23) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
  
 24) PLEASE EXPLAIN NOTE # 7 ON A-5.2.
 HOW WILL FIRE RESCUE GAIN ACCESS TO
 THE STAIRS FROM THE EXTERIOR.
  
 25) PLEASE EXPLAIN 20 MINUTE FIRE
 RATED DOORS AT ELEVATOR/LOBBY CORRIDOR.
 THESE DOORS ARE NOT THE SAME AS ENTRY
 DOORS TO APARTMENTS.
  
 26) PLEASE INDICATE LOCATIONS OF ALL
 PORTABLE FIRE EXTINGUISHERS.
  
 27) THERE APPEARS TO BE DOORS LOCATED
 WITHIN THE FOUR HOUR WALL ON PAGE
 A-2.7. ARE THESE DOORS PROPERLY RATED.
  
 28) THE EXITING FIRE SPRINKLER AND
 LIFE SAFETY EQUIPMENT ARE TO REMAIN
 WHILE THE WEST TOWER IS UNDER
 CONSTRUCTION.
  
 29) THE GARAGE IS PRESUMED TO REMAIN
 OCCUPIED WHILE THE WEST TOWER IS
 UNDER CONSTRUCTION.
  
 30) THE EXITING DOOR AT THE TOP OF THE
 STAIRS NEAR THE AT&T ROOM SWINGS
 INWARD. THIS EXIT DOOR SHOULD IN THE
 DIRECTION OF EXIT TRAVEL. PLEASE
 REVISE PLANS.
  
 31) PLEASE EXPLAIN WHY ON PAGE A-2.7
 THERE APPEARS TO BE A DEAD-END
 CORRIDOR NEAR ELEVATOR # 1.
  
 32) PLEASE DEMONSTRATE COMPLIANCE WITH
 ALL SECTIONS OF 412, OF THE FLORIDA
 BUILDING CODE.
  
 33) IS THE PROPOSED FIRE CONTROL ROOM
 LARGE ENOUGH TO CONTAIN ALL THE
 REQUIRED EQUIPMENT IN 412 OF THE
 FLORIDA BUILDING CODE, FIRE COMMAND
 ROOM.
  
 34) ENSURE THAT DOORS FOR THE PROJECT
 SWING IN THE PROPER DIRECTION.
  
 35) THE NEW FIRE ACCESS ROAD WILL
 SUPPORT HOW MUCH WEIGHT.
  
 36) SOME EXISTING ROOMS ARE MISSING
 FIRE SPRINKLER HEADS NEAR PHASE I AND
 PHASE II ROOMS.
  
 37) PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR 3'- 6" HIGH
 GLASS RAILING SHOWN ON A-2.2.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2006-02-24 Cont ID  
Sent By adarroug Date 2006-02-24 Time 10:18 Rev Time 0.00
Received By adarroug Date 2006-02-24 Time 10:18 Sent To B
Notes
2006-02-24 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 10:54 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 10:54 Sent To B
Notes
2006-02-15 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-14 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-12-14 Time 16:06 Sent To M
Notes
2005-12-14 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 11:47 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 11:47 Sent To M
Notes
2005-12-05 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2005-12-01 Cont ID  
Sent By adarroug Date 2005-12-01 Time 12:42 Rev Time 0.00
Received By adarroug Date 2005-12-01 Time 12:42 Sent To M
Notes
2005-12-01 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 17:47 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 17:47 Sent To  
Notes
2005-12-19 00:00:00TO "COMM" BD#44
2005-11-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-10-13 Cont ID  
Sent By adarroug Date 2005-10-13 Time 09:49 Rev Time 0.00
Received By adarroug Date 2005-10-13 Time 09:49 Sent To Z
Notes
2005-10-14 00:00:00LANDSCAPE PLANS ROUTED TO ANGELLA
 JONES-VANN FOR ZONING REVIEW.
2005-10-13 00:00:00SENT TO "Z" BOX FROM "COMM" BD#7
 SENT TO PAUL SCHMITZ TO REVIEW
 IRRIGATION PLANS BEFORE ROUTING
 LANDSCAPE PLANS TO ZONING.
  

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 09:53 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 09:53 Sent To P
Notes
2005-09-29 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 14:29 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 14:29 Sent To  
Notes
2005-09-13 00:00:00TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-08-22 Cont ID  
Sent By adarroug Date 2005-08-22 Time 09:20 Rev Time 0.00
Received By adarroug Date 2005-08-22 Time 09:20 Sent To B
Notes
2005-08-22 00:00:00TO "RBROWN" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 17:22 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 17:22 Sent To P
Notes
2005-08-09 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 15:00 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 15:00 Sent To P
Notes
2005-08-09 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-06-23 Cont ID  
Sent By adarroug Date 2005-06-23 Time 16:37 Rev Time 0.00
Received By adarroug Date 2005-06-23 Time 16:37 Sent To  
Notes
2005-06-27 00:00:00TO "COMM" BD#34
2005-06-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-08 Cont ID  
Sent By mjacobs Date 2005-06-08 Time 08:30 Rev Time 0.00
Received By mjacobs Date 2005-06-08 Time 08:30 Sent To  
Notes
2005-06-08 00:00:00TO 'RBROWN' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-03 Cont ID  
Sent By adarroug Date 2005-05-03 Time 17:41 Rev Time 0.00
Received By adarroug Date 2005-05-03 Time 17:41 Sent To  
Notes
2005-06-22 00:00:00ARCH/STRUCT/MEP REVISION SENT BACK TO
 FIRE PLAN REVIEW TO COMPLETE THEIR
 REVIEW.
  
  
2005-05-03 00:00:00TO "COMM" BD#16/PLANS ON RACK 3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2005-04-25 Time 17:12 Sent To  
Notes
2005-05-03 00:00:00IN INCOMING/AWAITING SPACE ON "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-12-28 Cont ID  
Sent By mjacobs Date 2004-12-28 Time 10:22 Rev Time 0.00
Received By mjacobs Date 2004-12-28 Time 10:22 Sent To B
Notes
2004-12-28 00:00:00TO "RB" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-15 Cont ID  
Sent By csiegber Date 2004-11-15 Time 15:58 Rev Time 0.00
Received By csiegber Date 2004-11-15 Time 15:58 Sent To  
Notes
2004-11-15 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-15 Cont ID  
Sent By csiegber Date 2004-11-15 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-11-15 Time 15:20 Sent To B
Notes
2004-11-15 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-01 Cont ID  
Sent By csiegber Date 2004-09-01 Time 13:09 Rev Time 0.00
Received By csiegber Date 2004-09-01 Time 13:09 Sent To B
Notes
2004-09-01 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-13 Cont ID  
Sent By csiegber Date 2004-04-13 Time 08:56 Rev Time 0.00
Received By csiegber Date 2004-04-13 Time 08:56 Sent To  
Notes
2004-04-13 00:00:00TO COMM BD#40

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-02-20 Time 14:03 Rev Time 0.00
Received By rbrown Date 2004-02-20 Time 14:02 Sent To  
Notes
2004-02-20 00:00:00TO COMM BD#43

Review Stop M MECHANICAL (A/C)
Rev No 9 Status N Date 2006-02-03 Cont ID  
Sent By hmoser Date 2006-02-03 Time 12:53 Rev Time 0.00
Received By hmoser Date 2006-02-03 Time 12:53 Sent To  
Notes
2006-02-03 00:00:00MECHANICAL KEEPED A COPY OF SNOKE BOMB
 LAYOUT SENT A COPY TO FIRE 2/3/06 HM.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2005-12-19 Cont ID  
Sent By pkrauss Date 2005-12-19 Time 10:46 Rev Time 0.00
Received By pkrauss Date 2005-12-19 Time 10:46 Sent To  
Notes
2005-12-19 00:00:00AC-1, EMPLOYEE LOUNGE

Review Stop M MECHANICAL (A/C)
Rev No 7 Status   Date 2005-12-07 Cont ID  
Sent By pkrauss Date 2005-12-07 Time 10:58 Rev Time 0.00
Received By pkrauss Date 2005-12-07 Time 06:51 Sent To  
Notes
2005-12-07 00:00:00PLAN SHEET AC-3 KEY NOTES - HVAC ITEM
 #11, INDICATES 1 1/2" VENTILATION PIPE
 DOWN 6" AFF.PLAN DOES NOT REFLECT THIS
 LINE.PLEASE INDIATE PURPOSE AND WAS
 THIS ELIMINATED?

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2005-08-10 Cont ID  
Sent By pkrauss Date 2005-08-10 Time 15:11 Rev Time 1.50
Received By pkrauss Date 2005-08-10 Time 15:11 Sent To  
Notes
2005-08-10 00:00:00SMOKE EVAC TO ROOF USING OA DUCT &
 CONTROLED BY DAMPERS.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2005-07-22 Cont ID  
Sent By pkrauss Date 2005-07-22 Time 12:37 Rev Time 3.50
Received By pkrauss Date 2005-07-22 Time 12:37 Sent To  
Notes
2005-07-22 00:00:00DENIED:
 PLEASE NOTE, COMMENTS FROM REVIEW DATED
 6/15/05 WERE NOT ADDRESSED.PAGES
 SUBMITTED FOR REVISION ON 6-22-05 ARE AS
 FOLLOWS; AC-1, AC-2, AC-3, AC-4, AC-4A.
  
 1.PLAN SHEET AC-2 - EXIT CORRIDOR
 INDICATES SPF-3,PLEASE CLARIFY, WILL
 THIS ONLY RUN DURING EMERGENCY POWER?
 PLEASE NOTE, SPF-3 IS NOT INDICATED ON
 THE EQUIPMENT SCHEDULE ON PLAN SHEET
 AC-8.0 OR LISTED WITH THE STAIRWELL
 PRESSURIZATION EQUIPMENT LISTED ON PLAN
 SHEET AC-11.
  
 2.PLAN SHEET AC-3, AC-4 & AC-4A DO NOT
 INDICATE LOCATION OF LEF-1.PLANS SHOW
 LEF-1 HAS BEEN DELETED BUT IS STILL
 INDICATED IN THE SEQUENCE OF OPERATION
 ON PLAN SHEET AC-11 (THIS SHEET HAS NOT
 BEEN REVISED).PLEASE INDICATE MEDTHOD
 OF SMOKE CONTROL LISTED UNDER 2001 FBC
 412.5.
  
 PLEASE NOTE, MECHANICAL REVISIONS
 SUBMITTED 6-2-05 WERE DENIED AND
 COMMENTS WERE NOT ADDRESSED.REVISIONS
 SUBMITTED UNDER THIS REVIEW CONTAIN THE
 SAME COMMENTS TO PROPOSED REVISIONS.
 PLEASE PROVIDE A RESPONSE LETTER TO
 COMMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2005-06-15 Cont ID  
Sent By pkrauss Date 2005-06-15 Time 14:08 Rev Time 0.00
Received By pkrauss Date 2005-06-15 Time 14:08 Sent To  
Notes
2005-06-15 00:00:00DENIED:
 1.PLAN SHEET AC-2 INDICATES SPF-4
 BEING DELETED.HOW WILL VENTILATION
 REQUIREMENT BE MET INACCORDANCE WITH
 2001 FBC(M)TABLE 403.3.PLEASE ALSO
 CLARIFY RATING OF THIS AREA AS WELL AS
 HALL SERVICED BY SPF-3.ARE THESE EXIT
 CORRIDORS?
  
 2.PLAN SHEET AC-3 THROUGH AC-6
 INDICATES THE REMOVAL OF LEF-1.PLAN
 SHEET AC-11 SEQUENCE OF OPERATION NOW
 READS "RTU-1 WILL SHUT DOWN".PLEASE
 CLARIFY HOW THE REQUIREMENTS OF 412.5
 WILL BE MET.
  
 3.PLAN SHEET AC-11 THE SEQUENCE OF
 OPERATION FOR FLOORS 2 THROUGH 12, STILL
 INDICATES LEF-1 AS A PART OF THE SMOKE
 CONTROL SYSTEM BUT ARE REMOVED FROM THE
 PLAN SHEETS (AC-3 THRU AC-6).
  
 IF YOUHAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-04-22 Cont ID  
Sent By pkrauss Date 2004-04-22 Time 13:05 Rev Time 0.55
Received By pkrauss Date 2004-04-22 Time 13:05 Sent To  
Notes
2004-04-22 00:00:00PROVISO:
 RETURN AIR TO THE CONDOS SHALL BE
 LOCATED WITHIN CLOSE PROXIMITY TO THE
 RETURN AIR TO PROMOTE THE CIRCULATION
 OF FRESH AIR INTO THE A/C SYSTEM.
  
 RECEIVED SUBMITTAL LETTER FROM RALPH
 PENA ADDRESSING THE EXISTING VENTILATION
 WAS DESIGNED PER CODE AT THE TIME OF
 CONSTRUCTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date 2004-04-15 Cont ID  
Sent By pkrauss Date 2004-04-15 Time 12:36 Rev Time 1.00
Received By pkrauss Date 2004-04-15 Time 07:04 Sent To  
Notes
2004-04-15 00:00:00PLAN SHEET AC-8 INDICATES FRESH AIR TO
 THE APARTMENTS THROUGH RTU-1.HOW WILL
 THIS BE INTRODUCED INTO THE AHU TO THE
 APARTMENTS.PLEASE INDICATE DUCT SIZE,
 MATERIAL AND LAYOUT. PLANS ARE OTHERWISE
 CODE COMPLIANT.
 4-16-04, PER CONVERSATION WITH ENG RALPH
 PENA, PLAN WITH BE REVISED TO REFLECT
 O.A. FROM RTU-1.PLAN TO BE SUBMITTED
 4-19-04.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-05 Cont ID  
Sent By pkrauss Date 2004-03-05 Time 09:38 Rev Time 7.00
Received By pkrauss Date 2004-03-05 Time 06:52 Sent To  
Notes
2004-03-05 00:00:00DENIED:
 1.PLEASE PROVIDE SEQUENCE OF OPERATION
 FOR THE SMOKE EVAC SYSTEM.
  
 2.CORRIDORS IN THE "LOFT" AREAS APPEAR
 TO BE BY SMOKE CONTROL/STACK EFFECT.
 SHOW COMPLIANCE WITH 2001 FBC 412.5
  
 3.PLANS DO NOT INDICATE THE EXISTING
 ENCLOSED GARAGE.INDICATE ANY NEW OR
 EXISTING VENTILATION & EVAC SYSTEMS.
 SHOW COMPLIANCE WITH 2001 FBC 411.4.2.
  
 4.PLAN SHEET AC-1, TOILET EXHAUST IS
 SHOWN TERMINATING IN THE ENCLOSED GARAGE
 EXHAUST IS TO TERMINATE TO THE OUTDOORS
 PER 2001 FBC(M) 501.3.PLEASE NOTE,
 THE WALL WHERE THE EXHAUST IS TERMATING
 AT IS A 4 HR FIRE RATED SEPARATION WALL.
  
 5.PLAN SHEET AC-2, 2ND FLOOR PLAN
 INDICATES 2 RTU-2, SHOULD INDICATE 1
 RTU-3 & 1 RTU-2.
  
 6.PLAN SHEET AC-8.0, DRYER EXHAUST
 INFORMATION, SPECIFIC DRYER TO BE
 INSTALLED FOR FINAL INSPECTION.
  
 7.PLAN SHEET AC-8.0 APARTMENT O.A.
 CALCULATIONS, PER REVISION TO THE 2001
 FBC(M) 403.3 EFFECTIVE JUNE 30, 2003;
 VENTILATION SYSTEMS FOR OTHER THAN R-3
 (ONE & TWO FAMILY DWELLINGS) SHALL BE
 DESIGNED TO SUPPLY THE MINIMUM OF OUT-
 DOOR AIR IN ACCORDANCE WITH TABLE 403.3.
  
 8.PLAN SHEET AC-9.0 REFRIGERANT
 ENCLOSURE TO BE 2 HR FIRE RATED & SHAFT
 IS TO BE VENTILATED PER NFPA 90A 3-3.4
 & ASHRAE 15-92 11.12.3 (B) RESPECTIVELY.
  
 9.PLAN SHEET AC-9.0 DETAIL FOR THE
 TOILET & DRYER EXHAUST, TOILET AND FRESH
 AIR INSTAKES ARE TO BE PROTECTED IN
 ACCORDANCE WITH 2001 FBC(M) 401.6.
 DRYER EXHAUST SHALL BE NON-SCREENED &
 HAVE A BACK-DRAFT DAMPER PER 2001 FBC(M)
 504.4.
  
 10. PLEASE PROVIDE INFORMATION ON THE
 EMERGENCY GENERATOR; LOCATION, TYPE OF
 GENERATOR, NEW OR EXISTING, TERMINATION
 OF EXHAUST, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 8 Status P Date 2005-10-15 Cont ID  
Sent By jleech Date 2005-10-15 Time 12:50 Rev Time 1.00
Received By jleech Date 2005-10-15 Time 12:50 Sent To  
Notes
2005-10-15 00:00:00REVISED PLUMBING PAGE P-4A OK

Review Stop P PLUMBING
Rev No 7 Status P Date 2005-10-14 Cont ID  
Sent By pschmitz Date 2005-10-14 Time 10:41 Rev Time 0.00
Received By pschmitz Date 2005-10-09 Time 14:14 Sent To  
Notes
2005-10-09 00:00:00REVISIONS: ADDRESSING COMMENTS FOR
 7-20-05 AND 8-26-05
 ALSO IRRIGATION.

Review Stop P PLUMBING
Rev No 6 Status F Date 2005-08-26 Cont ID  
Sent By kstevens Date 2005-08-26 Time 13:04 Rev Time 3.00
Received By kstevens Date 2005-08-26 Time 13:04 Sent To  
Notes
2005-08-26 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 A. FROM PREVIOUS REVISION REVIEW:
 4. SHT P-12 INDICATE THE TOTAL SQUARE
 FEET DRAINING INTO THE EXISTING 6" STORM
 LINE INCLUDING THE 2880 SF FROM RWL #2,
 AND ON THE OTHER STORM LINE INCLUDING
 THE 1310 SF FROM RWL #6. TABLE 1106.3
 ***************NEW COMMENT**************
 1B. GAS RISER DIAGRAM WAS NOT INCLUDED
 IN THE ORIGINAL PLANS. GAS PLANS WERE
 SUBMITTED BY THE PLUMBING CONTRACTOR AND
 WERE APPROVED. GAS PERMIT WAS ISSUED ON
 THE GAS RISER DIAGRAM PROVIDED AND DOES
 NOT REFLECT THE GAS RISER SUBMITTED IN
 THIS REVISION. PLEASE COORDINATE WITH
 THE PLUMBING CONTRACTOR AND INDICATE
 WHICH SYSTEM WILL BE USED, AND IF A
 REVISION WILL BE SUBMITTED, IT WILL BE
 SUBMITTED UNDER THE GAS PERMIT
 (05031733).
 2B. INFORMATIONAL: SHT P-10.0 HAS BEEN
 APPROVED, BUT AS INDICATED IN PRIOR
 REVISION, RISERS S/2B & S/3 SHALL BE
 REVISED TO REFLECT THE CHANGES SHOWN ON
 SHEET P-4.A.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-07-20 Cont ID  
Sent By kstevens Date 2005-07-20 Time 16:00 Rev Time 4.33
Received By kstevens Date 2005-07-20 Time 16:00 Sent To  
Notes
2005-07-20 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P-1 REVISION #7 INDICATE RWL
 NUMBER OF STORM LINE CONNECTING BETWEEN
 PARKING SPACES 26 & 27. - NO REVISION #8
 FOUND. PLEASE CLARIFY. SECTION 104.2.1.
 2. SHT P-2 SEE PROVISO FROM REVISION
 DATE STAMPED JUNE 13, 2005. SHOW THE
 LOCATION OF SECONDARY ROOF DRAINS.
 SECTION 1107.
 3. SHT P-4A WHITE OUT IS NOT APPROVED
 FOR PLAN CORRECTIONS/CHANGES. SECTION
 104.2.1.3.
 4. P-12 INDICATE THE TOTAL SQUARE FEET
 DRAINING INTO THE EXISTING 6" STORM LINE
 INCLUDING THE 2880 SF FROM RWL #2, AND
 ON THE OTHER STORM LINE INCLUDING THE
 1310 SF FROM RWL #6. TABLE 1106.3
 5. RECALCULATE THE SQUARE FEET FOR THE
 STORM DRAIN LINE FOR RWL #4. CHECK ALL
 PIPE SIZES PER TABLE 1106.3.
 6. THE SANITARY RISER DIAGRAMS S/2B AND
 S/3 SHALL BE REVISED TO REFLECT THE
 CHANGES SHOWN ON SHEET P-4.A. SECTION
 104.2.1.
 7. INFORMATIONAL - THE FOLLOWING SHEETS
 HAVE BEEN APPROVED AS REVISIONS, AND ONE
 SET HAS BEEN RETAINED FOR THE FILE SET.
 P-3, P-4.A, P-8 AND P-13.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-06-13 Cont ID  
Sent By kstevens Date 2005-06-13 Time 19:39 Rev Time 2.80
Received By kstevens Date 2005-06-13 Time 19:39 Sent To  
Notes
2005-06-13 00:00:00REVISION DENIED
  
 1. SHT P10 FROM PREVIOUS REVIEW. SANT.
 RISERS S/1A-S/7 & S/1C/CU. FIXTURE UNITS
 ADDED TO STACKS SHALL BE 16 NOT 10. 5FU
 FOR BATHROOM GROUP, AND 1FU FOR LAV AND
 2FU FOR ADDED TUB OR SHOWER. - SHOW
 CORRECT FIXTURE UNITS FOR STACKS. - ONE
 SHT P10 IS A COPY OF THE SIGNED, SEALED,
 DATED SHEET. ALL SETS SHALL BE SIGNED,
 SEALED & DATED. FAC 61G15-23.002
  
 2. SHT P12 ALL CORRECTIONS HAVE BEEN
 ADDRESSED FROM LAST REVISION REVIEW, BUT
 A NEW COMMENT WAS DISCOVERED. THE 6"
 PIPE AT 5490 SF IS NOT LARGE ENOUGH.
 MINIMUM 8" PIPE IS REQUIRED. TABLE
 1106.3.
  
 3. ALL OTHER SHEETS HAVE BEEN APPROVED
 AND ONE SET HAS THEM REMOVED FOR FILE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-12-11 Cont ID  
Sent By kstevens Date 2004-12-11 Time 15:47 Rev Time 2.75
Received By kstevens Date 2004-12-11 Time 15:47 Sent To  
Notes
2004-12-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT P-1 CONDENSATE SHALL DRAIN
 SEPARATELY FROM THE BUILDING AND THEN
 CONNECT TO STORM DRAIN, OR A CATCH
 BASIN
 A RELIEF VENT IS REQUIRED AS CONDENSATE
 EXITS THE BUILDING.
 2) SHT P-10 INDICATES REVISION #1, BUT
 THE REVISIONS ARE NUMBERED #2. PLEASE
 CLARIFY. SECTION 104.2.1
 3) SHT P-10 SANT RISERS 5/1A-S/7, AND
 S1C/S7. FIXTURE UNITS ADDED TO STACK
 SHALL BE 16 NOT 10. 5 FU FOR BATHROOM
 GROUP, A 1 FU FOR LAV, AND 2 FOR ADDED
 TUB OR SHOWER.
 4) SHT P-11 CONDENSATE RISERS C/1A, C/2,
 AND C/2A APPEAR TO HAVE BEEN CAPPED OFF.
 THESE RISERS SHALL VENT THROUGH THE ROOF
 AND SHALL NOT BE CAPPED OFF. PLEASE
 CLARIFY. SECTION 104.2.1
 5) SHT P-12 RWL/2 AND RWL/6 COMBINED
 TOTAL UP TO 3500 SF. MAXIMUM SF ON 5"
 STORM HORIZONTAL DRAINAGE PIPE IS 2969
 SF ON 5" PIPE. TABLE 1106.3
 6) FOLLOWING SHEETS WERE OK AND WILL BE
 STAMPED WHEN RESUBMITTED. P-2, P-3, P-4,
 P-5, P-5.1, P-7, P-8, P-9, P-10.1, AND
 P-13.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-04-19 Cont ID  
Sent By kstevens Date 2004-04-19 Time 16:26 Rev Time 4.00
Received By kstevens Date 2004-04-19 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-26 Cont ID  
Sent By kstevens Date 2004-02-26 Time 10:31 Rev Time 10.00
Received By kstevens Date 2004-02-26 Time 10:31 Sent To  
Notes
2004-02-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FLORIDA STATUTES
  
 1) EAST TOWER SHALL COMPLY WITH FBC-2001
 PLUMBING PER SECTION 3401.7.1.1.1
 2) CERTIFICATE OF AUTHORIZATION NUMBER
 IS REQUIRED ON ALL ARCHITECTURAL SHEETS
 PER FS 481.291.
 3) SHT A-2.1 TRENCH DRAIN AT TRASH DUMP-
 STER. IS THIS TRENCH DRAIN CONNECTED TO
 STORM? WILL THE DUMPSTER PAD BE WASHED
 DOWN INTO THE TRENCH DRAIN? PLEASE
 CLAIRFY.
 4) SHT A2.2 SUBMIT CALCULATIONS FOR
 COMMON AREAS PER TABLE 403.1. INDICATE
 AREAS TO INCLUDE CONFERENCE ROOM, MULTI-
 MEDIA, HEALTH CLUB, MANAGERS OFFICE ECT.
 5) SHT A-5.5 EMPLOYEE TOILET ROOM @ THE
 GROUND FLOOR, DOOR SHALL NOT OPEN INTO
 THE TURNING CIRCLE AND WATER CLOSET
 SHALL NOT OBSTRUCT THE TURNING CILCLE.
 SECTION 11-4.22.3.
 6) SHT A-8.2 DETAIL #4, PER SECTION
 1503.4.2 OVERFLOW SCUPPERS SHALL BE IN-
 STALLED IN WALLS OR PARAPETS WITH THE
 INLET FLOW LINE NOT LESS THAN 2" ABOVE
 THE ROOF SURFACE, EXCLUDING SUMPS, OR
 MORE THAN 4" ABOVE THE ROOF SURFACE AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL
 TO REQUIRED VERTICAL LEADERS OR DOWN-
 SPOUTS OR WALL OR PARAPET SCUPPERS.
 7) SHT P-7 WATER RISER DIAGRAMS, AIR
 CHAMBERS ARE NOT APPROVED PER SECTION
 604.9. DELETE FROM RISER DIAGRAMS.
 8) SHT P-8 SANITARY PIPING COLLECTION
 ISOMETRIC, FLOOR DRAINS IN EMPLOYEE AND
 GUEST TOILET ROOMS ARE NOT VENTED.
 CONNECT F.D.'S TO TOILET ROOM PIPING.
 SECTION 901.2.1
 9) THERMAL EXPANSION CONTROL IS REQUIRED
 PER SECTION 607.3.2
 10) SHT P-11 WATER RISER W/3, AN RPZ
 BACKFLOW IS REQUIRED ON WATER LINE TO
 TRASH CHUTE. SECTION 608.13.2
 11) SHT P-12 STORM DRAIN PIPING, RWL/2
 1620 SF - MAX 1600 SF @ 1/8" PER FT.
 EITHER INCREASE PIPE SIZE OF SHOW 1/4"
 PER FT. SLOPE ON PIPE. - RWL/3 6" SHOWS
 170 SF, BUT ADDS UP TO 1700 SF. PLEASE
 CHANGE PLANS.
 12) SHT P-10.1 IDENTIFY RISER BETWEEN
 S/4 & S/6. SHOW FU'S. - S/7 FU'S TO BE
 A TOTAL OF 16. (SHOWS 10). ADD ONE LAV
 AND TUB OR SHOWER TO EACH FLOOR.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2005-10-19 Cont ID  
Sent By sgraham Date 2005-10-19 Time 14:18 Rev Time 0.00
Received By sgraham Date 2005-10-19 Time 14:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-22 Cont ID  
Sent By ajones Date 2004-04-22 Time 10:04 Rev Time 0.25
Received By ajones Date   Time   Sent To  
Notes
2004-04-22 00:00:00APPROVED WITH THE PROVISO THAT THE LETTE
 R FROM JOE CROSSEN GRATNING PERMISSION T
 O USE THE 10 FOOT EASEMENT FOR FIRE ACCE
 SS IS RECEVIED PRIOR TO CO.ANY CHANGES
 TO THE LANDSCAPE PLAN ON SITE REQUIRE A
 NGELLA VANN'S APPROVAL.

Review Stop Z ZONING
Rev No 1 Status F Date 2004-04-05 Cont ID  
Sent By rbrown Date 2004-04-02 Time 20:04 Rev Time 0.25
Received By ajones Date   Time   Sent To  
Notes
2004-04-05 00:00:001. NO LANDSCAPING PLAN IS PROVIDED
 2. UNITY TO TITLE NEEDED AS REQUIRED BY
 ORD.
 3. 10 FOOT RESERVATION SHOWN ON PLAN HAS
 NOT BEEN RESOLVED
 4. WAS DUMPSTER LOCATION APPROVED IN ORI
 GINAL APPROVAL.