| Plan Review Stops For Permit 04020684 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2006-03-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-03-12 |
Time |
00:14 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2006-03-12 |
Time |
00:14 |
Sent To |
|
|
| Notes |
| 2006-03-12 00:00:00 | ARCHITECTURAL REVISION SUBMITTED | | | 11/28/05 FOR REVISED CEILING HEIGHTS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2005-08-04 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-08-04 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-08-04 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2005-08-04 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | ARCHITECTURAL REVISION SUBMITTED 6/22/05 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | --PROVISO-- | | | THE DOCUMENTS FOR THE DOOR AND WINDOW | | | PERMIT APPLICATION PACKAGE (PERMIT# | | | 05020638) SHALL BE REVISED TO | | | INCORPORATE THE NEW WINDOWS AND DOORS | | | INTRODUCED BY THIS REVISION. | | | ALTERNATIVELY, A SEPARATE PERMIT | | | APPLICATION MAY BE SUBMITTED FOR THOSE | | | DOORS AND WINDOWS. | | | | | | | | | NOTE: | | | THE FOLLOWING NON-COMPLIANCE HAS BEEN | | | ACCEPTED IN ACCORDANCE WITH THE RULING | | | OF CONSTRUCTION BOARD OF APPEALS ORDER | | | (CASE# 1253): | | | FBC 1003.2.5ON SHEET A-6.2 (STAIR | | | NO.2 SECTION) THE HEADROOM IS SHOWN, AS | | | AN "EXISTING CONDITION", AT 6 FT 6 | | | INCHES.THE REQUIREMENT OF THE CODE | | | APPLICABLE TO THE CURRENT PROJECT IS 6 | | | FT 8 INCHES.ACCEPTED IN ACCORDANCE | | | WITH CBAA CASE# 1253 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2005-07-25 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-07-25 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-07-25 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2005-07-25 00:00:00 | ARCHITECTURAL REVISION SUBMITTED 6/2/05 | | | FOR SHEETS A-2.3.A, A-2.4, A-2.4A AND | | | A-5.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2005-06-22 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-06-22 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-06-22 |
Time |
19:25 |
Sent To |
FIRE |
|
| Notes |
| 2005-06-22 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | ARCHITECTURAL AND STRUCTURAL REVISION | | | SUBMITTED 4/25/05 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) FBC* 104.2SHEET A-2.2 SHOWS THE | | | REVISED LAYOUT THE STAIR #9 WALKWAY AND | | | THE CORRIDOR BETWEEN STAIR #2 AND #4. | | | SHEETS A-1.1, A-2.7A, A-2.8, A-4.6, | | | A-6.2 AND S1-2A HAVE NOT BEEN AMENDED TO | | | REFLECT THE NEW LAYOUT.SUBMIT REVISED | | | SHEETS. | | | | | | REMAINDER OF ARCHITECTURAL AND | | | STRUCTURAL SHEETS HAVE BEEN | | | REVIEWED/STAMPED AND ONE COPY RETAINED | | | FOR CITY RECORDS. | | | | | | NOTE: | | | THE FOLLOWING NON-COMPLIANCE HAS BEEN | | | ACCEPTED IN ACCORDANCE WITH THE RULING | | | OF CONSTRUCTION BOARD OF APPEALS ORDER | | | (CASE# 1253): | | | FBC 1003.2.5ON SHEET A-6.1 (STAIR | | | NO.1 SECTION) AND SHEET A-6.2 (STAIR | | | NO.2 SECTION) THE HEADROOM IS SHOWN, AS | | | AN "EXISTING CONDITION", AT 6 FT 6-1/2 | | | INCHES AND 6 FT 6 INCHES RESPECTIVELY. | | | THE REQUIREMENT OF THE CODE APPLICABLE | | | TO THE CURRENT PROJECT IS 6 FT 8 | | | INCHES.ACCEPTED IN ACCORDANCE WITH | | | CBAA CASE# 1253 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2005-01-03 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2005-01-03 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-01-03 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2005-01-03 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | SUBMITTAL ON 12/28/04 FOR R.C. ALUMINUM | | | DOOR AND WINDOW PACKAGE. | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1) THE PERMIT WAS ISSUED WITH THE | | | FOLLOWING PROVISO: | | | | | | "INSUFFICIENT PRODUCT APPROVAL INFO: | | | AS REQUESTED IN VILLA LOFTS' LETTER | | | DATED APRIL 26, 2004, THE FIXED GLASS | | | WINDOWS, HORIZONTAL SLIDING WINDOWS | | | AND FRENCH DOORS SHALL BE UNDER A | | | SEPARATE PERMIT WITH FEES BASED ON A | | | MINIMUM VALUE OF $104,308.75" | | | | | | THIS CONDITION HAS NOT BEEN MET.THIS | | | R.C. ALUMINUM PACKAGE WAS BROUGHT IN, | | | ON | | | 12/28/04, AS A 'NO FEE SUBMITTAL'. | | | RESUBMIT AS A SEPARATE PERMIT | | | APPLICATION.THE FEE CALCULATION WILL | | | BE BASED ON THE VALUE OF THE CONTRACT | | | FOR THE R.C. ALUMINUM DOOR AND WINDOW | | | PACKAGE | | | | | | 2) A FULL REVIEW HAS NOT BEEN CARRIED | | | OUT (SEE COMMENT 1, ABOVE).THE | | | FOLLOWING INITIAL OBSERVATIONS ARE MADE | | | ONLY TO EXPEDITE THE PROCESS.A FULL | | | REVIEW WILL BE CARRIED OUT WHEN THE | | | REQUIRED PERMIT APPLICATION IS | | | RECEIVED. | | | | | | 3) FBC* 101.4.2APPROPRIATE BUILDING | | | CODE.R.C. ALUMINUM INDUSTRIES | | | CALCULATION SHEET DC-1 CITES SOUTH | | | FLORIDA BUILDING CODE 2004 FOR DESIGN. | | | THE APPLICABLE CODE IS FLORIDA BUILDING | | | CODE 2001 (WITH 2002 AND 2003 | | | AMENDMENTS).AMEND THE CALCULATIONS. | | | | | | 4) SUBMITTED PRODUCT APPROVALS. | | | NOTE: FL. ADMIN CODE RULE 9B-72 (IN | | | EFFECT SINCE OCTOBER 1, 2003) REQUIRES | | | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR | | | SITE-SPECIFIC PRODUCT APPROVAL.THE | | | SUBMITTAL SHOULD INCLUDE THE STATEWIDE | | | PRODUCT APPROVAL NUMBER (FL###), | | | AVAILABLE FROM THE DEPT OF COMMUNITY | | | AFFAIRS PRODUCT APPROVAL WEBSITE | | | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP | | | (IF YOU FIND THAT THE QUOTED WEB PAGE | | | IS | | | NO LONGER AVAILABLE, PLEASE INFORM THE | | | PLAN REVIEWER) | | | | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL | | | INFO | | | TELEPHONE: (561) 805 6716ROBERT | | | BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2004-12-07 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-12-07 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-12-07 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2004-12-07 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | REVISION SUBMITTED 11/15/03 | | | | | | 1) FBC 1003.2.5ON SHEET A-6.1 (STAIR | | | NO.1 SECTION) AND SHEET A-6.2 (STAIR | | | NO.2 SECTION) THE HEADROOM IS SHOWN, AS | | | AN "EXISTING CONDITION", AT 6 FT 6-1/2 | | | INCHES AND 6 FT 6 INCHES RESPECTIVELY. | | | THE REQUIREMENT OF THE CODE APPLICABLE | | | TO THE CURRENT PROJECT IS 6 FT 8 | | | INCHES. | | | AMEND THE PLAN TO SHOW HOW THIS WILL BE | | | ACHIEVED.IT IS NOTED THAT THIS IS AN | | | EXISTING CONDITION BUT CURRENT CODE | | | REQUIREMENTS FOR MEANS OF EGRESS MUST | | | BE | | | MET. | | | | | | 2) FBC* 104.2.1.3SHEET S6-3 HAS ONE | | | CLOUDED REVISION BUT THERE IS NO | | | REVISION MARKER AND REVISION HISTORY | | | HAS | | | BEEN OMITTED FROM THE TITLE BLOCK. | | | ALSO | | | THE ADDITION OF DETAIL 14 HAS NOT BEEN | | | FLAGGED. | | | | | | 3) SHEET PT-1 THROUGH PT-4, THE | | | POST-TENSION SHOP DRAWINGS SHALL BE | | | REVIEWED AND STAMPED BY THE ENGINEER OF | | | RECORD BEFORE SUBMITTAL.ALSO THE | | | TITLE | | | BLOCK SHALL INCLUDE THE CERTIFICATE OF | | | AUTHORIZATION (ENGINEERING BUSINESS) | | | NUMBER (EB 9829) FOR NEWTONIAN SOLUTIONS | | | INC. | | | | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2004-11-18 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-11-18 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-11-18 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2004-11-18 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | STRUCTURAL SUBMITTAL FOR NORMAN L BROWN | | | SHORING ACCEPTANCE LETTER DATED | | | 10/18/04 | | | | | | 1) THE FIRST SENTENCE HAS BEEN ALTERED. | | | ALL ALTERATION TO SIGNED AND SEALED | | | DOCUMENTS SHALL BE INITAILED AND DATED | | | BY THE ENGINEER THAT SEALED THE | | | DOCUMENT. | | | | | | 2) TO BE CONSISTENT WITH THE ABOVE | | | ALTERATION, THE FIFTH SENTENCE SHOULD | | | REFER TO INSPECTION OF RE-SHORING UNDER | | | THE FIFTH FLOOR. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-11-18 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-11-18 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-11-18 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2004-11-18 00:00:00 | STRUCTURAL SUBMITTAL FOR NORMAN L BROWN | | | SHORING ACCEPTANCE LETTERS DATED | | | 10/8/04, 10/27/04, 11/9/04. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-09-17 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-09-17 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-09-17 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2004-09-17 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | STRUCTURAL SUBMITTAL 9-1-04 FOR RAUL | | | PUIG (EOR) SKETCHES, VSL SHOP DRAWINGS | | | AND NORMAN BROWN SHORING PLANS. | | | | | | 1) RAUL PUIG GROUP SKETCHES. | | | 61G15-23.002(2)FL. ADMIN. CODE. | | | SHEETS SIGNED & SEALED BY A PROFESSIONAL | | | ENGINEER SHALL INCLUDE THE PRINTED NAME | | | AND LICENSE NUMBER OF THE ENGINEER AND | | | THE NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS THROUGH WHICH THE ENGINEER IS | | | PRACTICING (471.025 F.S AND 471.023 F.S) | | | | | | 2) NORMAN L. BROWN III, P.E. SHORING | | | PLANS. | | | STRUCTURAL SHOP DRAWINGS SHALL BE | | | REVIEWED AND STAMPED BY THE ENGINEER OF | | | RECORD BEFORE SUBMITTAL. | | | | | | 3) VSL SHOP DRAWINGS. | | | (A) SUBMIT THREE COPIES OF ALL PLANS. | | | ONLY TWO WERE COPIES SUBMITTED. | | | (B) 61G15-23.002(2)FL. ADMIN. CODE. | | | PLANS SIGNED & SEALED BY A PROFESSIONAL | | | ENGINEER SHALL INCLUDE THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER AND THE | | | NAME, ADDRESS AND CERTIFICATE OF | | | AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS THROUGH WHICH THE ENGINEER IS | | | PRACTICING (471.025 F.S AND 471.023 F.S) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-04-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-01 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-04-27 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2004-04-19 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | --PROVISO-- | | | | | | INSUFFICIENT PRODUCT APPROVAL INFO: | | | AS REQUESTED IN VILLA LOFTS' LETTER | | | DATED APRIL 26, 2004, THE FIXED GLASS | | | WINDOWS, HORIZONTAL SLIDING WINDOWS AND | | | FRENCH DOORS SHALL BE UNDER A SEPARATE | | | PERMIT WITH FEES BASED ON A MINIMUM | | | VALUE OF $104,308.75 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-04-02 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-04-02 |
Time |
19:49 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-03-16 |
Time |
16:42 |
Sent To |
Z |
|
| Notes |
| 2004-03-16 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) FBC 3401.7.1ADDITION TO AN EXISTING | | | BUILDING.THE NEW 'TOWER' IS CONSIDERED | | | AS AN ADDITION AND IT'S AREA EQUALS 25%, | | | OR MORE, OF THE AREA OF THE EXISTING | | | BUILDING.EITHER (A) THE EXISTING | | | BUILDING SHALL BE UPGRADED TO COMPLY | | | WITH THE CODE IN EFFECT ON FEB' 14, 2004 | | | (THE DATE OF PERMIT APPLICATION), EXCEPT | | | THE STRUCTURAL REQUIREMENTS OF THE CODE, | | | OR (B) THE NEW 'TOWER' SHALL BE | | | SEPERATED FROM THE EXISTING BUILDING BY | | | A FOUR HOUR RATED FIRE WALL. | | | | | | 2) CONDOMINIUM V APARTMENTS.IF THE | | | DWELLING UNITS ARE TO BE SOLD AS | | | CONDOMINIUMS, NO CERTIFICATE OF | | | OCCUPANCY CAN BE ISSUED UNTIL A | | | 'DECLARATION OF CONDOMINIUM' HAS BEEN | | | SUBMITTED TO THE STATE FOR APPROVAL, AND | | | THEN RECORDED WITH THE CLERK OF THE | | | COUNTY COURT.A RECORDED COPY SHALL BE | | | SUBMITTED TO THE CITY FOR RECORDS, | | | ADDRESSING PURPOSES, AND NOTIFICATION OF | | | PALM BEACH COUNTY PROPERTY APPRAISER'S | | | OFFICE. | | | | | | 3) FBC 13-103.1.2BEFORE A BUILDING | | | PERMIT CAN BE ISSUED, THE SUBMITTED | | | ENERGY CODE COMPLIANCE FORMS SHALL BE | | | SIGNED BY THE BUILDING OWNER, THE | | | OWNER'S ARCHITECT OR OTHER AUTHORIZED | | | AGENT LEGALLY DESIGNATED BY THE OWNER. | | | ALSO, THE CORRECT JURISDICTION NAME AND | | | NUMBER IS 'WEST PALM BEACH (604700)', | | | THE CORRECT PROJECT ADDRESS IS | | | 1617 N. FLAGLER DR (CITY: WEST PALM BCH, | | | ZIP: 33407), THE CORRECT PERMIT NUMBER | | | IS 04020684 AND THE OCCUPANCY IS | | | RESIDENTIAL.AMEND THE ENERGY CODE | | | COMPLIANCE FORM. | | | | | | 4) FBC 13-103.1.1.1IT IS NOTED THAT | | | RAFAEL PENA'S NAME AND LICENSE NUMBER | | | ARE ON SHEET TWO OF THE ENERGY CODE | | | COMPLIANCE FORMS, BUT THE PROFESSIONALS | | | RESPONSIBLE FOR THE DESIGN OF THE | | | BUILDING SHELL AND THE ELECTRICAL, | | | LIGHTING, MECHANICAL AND PLUMBING | | | SYSTEMS SHALL EACH SIGN THE ENERGY CODE | | | COMPLIANCE FORM, TO CERTIFY COMPLIANCE. | | | | | | 5) THE PROPOSED BUILDING STRUCTURE | | | TRANSGRESSES LEGAL BOUNDARY LINES | | | BETWEEN THE LOTS WHICH COMBINE TO FORM | | | 'THE SITE'.SUBMIT A COPY OF THE 'UNITY | | | OF TITLE' DOCUMENT SO THAT FBC TABLE 600 | | | BOUNDARY LINE REQUIREMENTS MAY BE DEEMED | | | NOT APPLICABLE. | | | | | | 6) FBC* 104.6.5BUILDING PERMIT | | | VALUATION.THE STATED VALUE OF THE | | | PROJECT HAS BEEN UNDER-ESTIMATED AT | | | $4,832,516.THE VALUE CALCULATED USING | | | THE SOUTHERN BUILDING CODE CONGRESS | | | INTERNATIONAL (SBCCI) VALUATION TABLES | | | IS $5,563,825.THE PERMIT APPLICATION | | | FEE HAS BEEN ADJUSTED ACCORDINGLY, SO | | | THERE IS AN OUTSTANDING BALANCE OF | | | $32,886.96 WHICH INCLUDES $573.50 RADON | | | FEES AND THE BALANCE OF THE PERMIT FEES | | | NOT PAID AT THE TIME OF APPLICATION. | | | | | | 7) 61G15-23.002(2)FL. ADMIN. CODE. | | | STRUCTURAL ENGINEER'S PLANS FS-1 TO S7-5 | | | PLANS SIGNED & SEALED BY A PROFESSIONAL | | | ENGINEER SHALL INCLUDE THE CERTIFICATE | | | AUTHORIZATION NUMBER (6063 FOR THE RAUL | | | PUIG GROUP, P.A.) FOR THE ENGINEERING | | | BUSINESS THROUGH THROUGH WHICH THE | | | ENGINEER IS PRACTICING. | | | (471.025 F.S. AND 471.023 F.S.). | | | | | | 8) FBC 104.2.2 ONE SET OF THE STRUCTURAL | | | PLANS DOES NOT HAVE AN THE ORIGINAL | | | SIGNATURE OR RAISED SEAL OF THE ENGINEER | | | | | | 9) FBC 503.2.6SPECIAL UNLIMITED HEIGHT | | | FOR TYPE II BUILDINGS.SHEET A-1.1, | | | CODE ANALYSIS TABLE STATES THAT THE | | | ROOF/CEILING AND THE BEAMS, GIRDERS, | | | TRUSSES AND ARCHES REQUIRE FIRE | | | RESISTANCE RATING OF 1-HR.BECAUSE THE | | | BUILDING IS TO BE TYPE II CONSTRUCTION | | | AND EXCEEDS 80 FEET IN HEIGHT A MINIMUM | | | OF 1-1/2 HOURS FIRE RESISTANCE RATING IS | | | REQUIRED FOR THE ROOFS AND THEIR | | | SUPPORTING BEAMS, GIRDERS, TRUSSES AND | | | ARCHES.ALSO THE NOTE ABOUT FIRE | | | RESISTANCE RATING BEING NOT REQUIRED FOR | | | STRUCTURE SUPPORTING ROOF ONLY, WHERE | | | THE CLEAR HEIGHT IS AT LEAST 20 FEET, IS | | | NOT APPLICABLE AND SHOULD BE DELETED. | | | AMEND SHEET A-1.1 | | | | | | 10) FBC 412.5SMOKE CONTROL.THE PLANS | | | DO NOT DEMONSTRATE FULL COMPLIANCE WITH | | | FBC 412.5(3).AMEND THE PLANS TO SHOW | | | COMPLIANCE WITH ON OF THE SMOKE CONTROL | | | OPTIONS IN FBC 412.5 | | | | | | 11) FBC 1012.1.2 EGRESS DOOR.SHEETS | | | A-2.1.D AND A-2.1 SHOW AN INWARD OPENING | | | PARKING GARAGE EXIT DOOR ADJACENT THE | | | AT&T ROOM.THE DOOR SHALL SWING OUTWARD | | | TO OPEN IN THE DIRECTION OF EGRESS. | | | | | | 12) FBC 1003.3.4SHEET A-2.1, PARKING | | | GARAGE EXIT.THE PARKING SPACE ADJACENT | | | THE EXIT BY THE AT&T ROOM SHALL BE | | | 'PAINTED OUT' AND NO LONGER USED, IN | | | ORDER TO MAINTAIN THE REQUIRED EXIT | | | WIDTH. | | | | | | 13) FBC 1004.1.2SHEET A-2.1, EGRESS | | | FROM EMPLOYEE LOUNGE.THE TRAVEL | | | DISTANCE TO THE EXIT EXCEEDS 75 FEET AND | | | EGRESS THROUGH THE PARKING GARAGE IS NOT | | | PERMITTED, SO THERE IS NO ALTERNATIVE | | | ROUTE.RELOCATE THIS ROOM TO REDUCE THE | | | TRAVEL DISTANCE. | | | | | | 14) FBC TABLE 705.1.2SHEET A-4.1.THE | | | TRASH ROOM SHALL BE SHOWN TO HAVE A MIN. | | | 1-HR FIRE RATING FOR ALL WALLS | | | (INCLUDING EXISTING) AND A 3/4 HR RATING | | | FOR THE DOOR (EXISTING). | | | | | | 15) FBC 1005.6.5SHEET A-2.1.STAIR #2 | | | SHALL NOT DISCHARGE THROUGH THE PARKING | | | GARAGE.AMEND THE PLANS TO SHOW CODE | | | COMPLIANT EXIT DISCHARGE FROM STAIR #2. | | | | | | 16) FBC 1004.1.4SHEET A-2.2.THE | | | COMMON PATH OF TRAVEL FROM THE SECOND | | | FLOOR COMMON AREA (AND BAR) EXCEEDS | | | 75 FEET.ANNOTATE THE PLANS (INCLUDING | | | SHEET A-4.4) TO CONFIRM AVAILABILITY OF | | | ALTERNATIVE EGRESS, THROUGH THE EXISTING | | | EAST TOWER, VIA THE OPENING OPPOSITE THE | | | MANAGER'S OFFICE DOOR. | | | | | | 17) FBC 1003.1.2SHEET A-2.2.PROVIDE | | | A LIFE SAFETY PLAN TO SHOW OCCUPANT LOAD | | | AND EGRESS FOR THE TRANQUILITY GARDEN, | | | POOL DECK AND POOL. | | | | | | 18) FBC 1006.1.1SHEET A-2.3.NO EXIT | | | DOOR IS SHOWN AT STAIR #1.AMEND THE | | | PLAN. | | | | | | 19) FBC 412.6.2ELEVATOR LOBBIES.THE | | | TRASH CHUTE AND ELECTRICAL ROOMS SHALL | | | NOT OPEN INTO THE ELEVATOR LOBBIES. | | | AMEND THE PLANS. | | | | | | 20) FBC 1608.2.2SHEET A-8.1. GUARDRAIL | | | DETAILS 3, 4, AND 8.NOTE 4 GIVES AN | | | INCOMPLETE SPECIFICATION FOR GUARDRAIL | | | STRENGTH REQUIREMENTS.THE GUARDRAIL | | | SHALL BE DESIGNED AND CONSTRUCTED FOR A | | | CONCENTRATED LOAD OF 200 LB APPLIED IN | | | ANY DIRECTION AT THE TOP OF THE | | | GUARDRAIL, A CONCENTRATED HORIZONTAL | | | LOAD OF 200 LB APPLIED ON A 1 SQ FT AREA | | | AT ANY POINT, AND A LINE LOAD OF 50 PLF | | | APPLIED HORIZONTALLY AT THE REQUIRED | | | GUARDRAIL HEIGHT WITH A SIMULTANEOUS | | | LINE LOAD OF 100 PLF APPLIED VERTICALLY | | | DOWNWARD ON THE TOP OF THE GUARDRAIL. | | | THESE LOADS SHALL NOT BE APPLIED | | | SIMULTANEOUSLY (UNLESS NOTED ABOVE) BUT | | | SHALL BE APPLIED INDIVIDUALLY TO PRODUCE | | | MAXIMUM STRESS IN EACH OF THE COMPONENTS | | | OR SUPPORTS.AMEND/ANNOTATE THE PLANS. | | | NOTE:THESE LOADS ALSO APPLY TO THE | | | GUARDING SHOWN ON SHEET A-6.3, DETAILS | | | 2, 3, 6 AND 9 (THE SPECIFIED HANDRAIL | | | LOADING IS NOTED). | | | | | | 21) FBC 11-4.1.2(5)(E)VALET PARKING. | | | AMEND THE NOTE ON SHEET A-1.1 TO STATE | | | THAT VALET PARKING WILL BE PROVIDED IN | | | ACCORDANCE WITH FBC 11-4.1.2(5)(E) AND | | | FBC 11-4.6.6. | | | | | | 22) FBC 11-4.13.6MANEUVERING CLEARANCE | | | AT DOORS.AMEND DOOR 12 ON SHEET A-4.1 | | | AND DOORS 29 AND 31 ON SHEET A-4.3 TO | | | SHOW THE REQUIRED 18" CLEARANCE BETWEEN | | | THE STRIKE EDGE OF THE DOOR AND THE | | | ADJACENT WALL ON THE PULL SIDE OF THE | | | DOOR (REF FIG. 25) | | | | | | 23) FBC 3003.4.1STRETCHER ACCESSIBLE | | | ELEVATOR.AT LEAST ONE PASSENGER | | | ELEVATOR SHALL ACCOMMODATE AN AMBULANCE | | | STRETCHER 76" LONG AND 24" WIDE IN THE | | | HORIZONTAL POSITION.THIS ELEVATOR | | | SHALL BE IDENTIFIED BY SIGNAGE.AMEND | | | THE PLANS TO DEMONSTRATE COMPLIANCE. | | | | | | 24) FBC 2405.2THE FOLLOWING GLAZING IS | | | IN A 'HAZARDOUS LOCATION' AND IS | | | REQUIRED TO BE SAFETY GLASS SATISFYING | | | THE REQUIREMENTS OF THE CONSUMER PRODUCT | | | SAFETY COMMISSION 16, CODE OF FEDERAL | | | REGULATIONS, PART 1201 (CPSC 16-CFR, | | | PART 1201): | | | DOOR #12 (SHEET A-5.1 - DOOR SCHED.) | | | DOOR #28 (SHEET A-5.1 - DOOR SCHED.) | | | DOOR #29 (SHEET A-5.1 - DOOR SCHED.) | | | DOOR #37 (SHEET A-5.1 - DOOR SCHED.) | | | SUBMIT DETAILS TO DEMONSTRATE COMPLIANCE | | | | | | 25) SUBMIT PRODUCT APPROVALS FOR THE | | | ROOF COVERINGS, WINDOWS, EXTERIOR DOORS | | | AND EXTERIOR SLIDING GLASS DOORS. | | | NOTE: FL. ADMIN CODE RULE 9B-72 (IN | | | EFFECT SINCE OCTOBER 1, 2003) REQUIRES | | | THAT PRODUCTS HAVE STATEWIDE, LOCAL OR | | | SITE-SPECIFIC PRODUCT APPROVAL.THE | | | SUBMITTAL SHOULD INCLUDE THE STATEWIDE | | | PRODUCT APPROVAL NUMBER (FL###), | | | AVAILABLE FROM THE DEPT OF COMMUNITY | | | AFFAIRS PRODUCT APPROVAL WEBSITE | | | WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP | | | | | | 26) PRODUCT APPROVAL.RULE 9B-72 FAC. | | | FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE | | | PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL | | | CAN BE ACHIEVED IF THERE IS A QUALITY | | | ASSURANCE PROGRAM IN PLACE WITH A STATE | | | APPROVED QUALITY ASSURANCE ENTITY.IF | | | NEITHER IS APPLICABLE, THEN SITE | | | SPECIFIC APPROVAL IS REQUIRED.LOCAL | | | PRODUCT APPROVAL WILL ALLOW A PRODUCT TO | | | BE USED, IN ACCORDANCE WITH THE TEST | | | CRITERIA, THROUGHOUT THE JURISDICTION OF | | | WEST PALM BEACH.SITE SPECIFIC PRODUCT | | | APPROVAL WILL ALLOW A PRODUCT TO BE | | | USED ONLY ON THE PROJECT FOR WHICH THAT | | | SITE SPECIFIC APPROVAL IS GRANTED. | | | LOCAL AND SITE SPECIFIC PRODUCT APPROVAL | | | APPLICATION FORMS ARE AVAILABLE FROM | | | THIS OFFICE.APPROVED QUALITY ASSURANCE | | | ENTITIES ARE LISTED ON THE DCA WEBSITE: | | | WWW.FLORIDABUILDING.ORG/COMMON/C_ORG_ | | | REGI_SRCH.ASP | | | | | | 27) FBC 1606.1.7WIND LOAD. SHEET S0.0, | | | DESIGN LOAD NOTE #2 REFERS TO 'SOUTH | | | FLORIDA BUILDING CODE 1994' FOR WIND | | | DESIGN.AMEND THE NOTE TO READ 'FLORIDA | | | BUILDING CODE 2001'.ALSO THE PLANS | | | SHALL STATE THE BASIC WIND SPEED, WIND | | | IMPORTANCE FACTOR, WIND EXPOSURE | | | CATEGORY, INTERNAL PRESSURE COEFFICIENT, | | | AND EXTERIOR COMPONENT AND CLADDING | | | DESIGN WIND PRESSURES.AMEND THE PLANS. | | | | | | 28) FBC TABLE 600.FIRE RESISTANCE. | | | SHT S0.0 (EG.REINFORCING STEEL NOTE #3) | | | MAKES NO REFERENCE TO THE REQUIRED FIRE | | | RESISTANCE RATINGS FOR THE STRUCTURAL | | | ELEMENTS AS LISTED ON SHEET A-1.1. | | | CO-ORDINATE THE ARCHITECTURAL AND | | | STRUCTURAL PLANS TO ENSURE ADEQUATE | | | FIRE RESISTANCE FOR THE STRUCTURAL | | | MEMBERS. | | | | | | 29) FBC 3502REFERENCE STANDARDS. | | | SHEET A-9.1, GENERAL NOTES #24 AND #25 | | | REFER TO OUT-DATED CODES AND SHALL BE | | | AMENDED AS FOLLOWS: | | | - ACI 530.1-95/ASCE 6-96/TMS 602-95 | | | SHALL READ ACI 530.1/ASCE 6/TMS 602-02 | | | - ASTM C 91-66 SHALL READ ASTM C 91-91 | | | - ASTM C 150-67 SHALL READ ASTM C 150-94 | | | - ASTM C 34-62 SHALL READ ASTM C 33-62 | | | | | | 30) FBC 3502REFERENCE TO ASCE 7. | | | SHEET A-9.1, STOREFRONT/../DOOR NOTE #4 | | | AND SHEET A-9.2 ROOFING NOTE D BOTH | | | REFER TO ASCE 7-95.AMEND THE REFERENCE | | | TO READ ASCE 7-98 | | | | | | 31) TO EXPEDITE REVIEW OF A RESUBMITTAL | | | WHICH REQUIRES NEW PLANS IN ORDER TO | | | ADDRESS THE ABOVE COMMENTS, THE OLD | | | SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHOULD BE STAPLED/CLIPPED TO THE | | | REMAINING OLD SHEETS FOR COMPARISON OF | | | REVISIONS WHEN REVIEWING THE RESUBMITTED | | | PLANS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2006-04-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2006-04-07 |
Time |
06:32 |
Rev Time |
2.00 |
| Received By |
jleahy |
Date |
2006-04-07 |
Time |
06:31 |
Sent To |
|
|
| Notes |
| 2006-04-07 00:00:00 | AS BUILTS FOR JOB WENT OVER WITH DAN | | | KEMPA. 4/6/06 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2005-12-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-24 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-24 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2005-12-24 00:00:00 | REV'S FOR | | | | | | E-2,3,4,5,10 AND 15 OK, STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-07 |
Time |
21:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-07 |
Time |
21:33 |
Sent To |
|
|
| Notes |
| 2005-12-07 00:00:00 | REDLINED, | | | FIRE PUMP FEEDERS, SEC'S SHALL NOT BE | | | SPLICED OR IN SAME SPLICE BOX. | | | MUST BE INCASED/OR UNDER BLDG. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2005-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-27 |
Time |
19:16 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2005-09-27 |
Time |
19:16 |
Sent To |
|
|
| Notes |
| 2005-09-27 00:00:00 | REDLINED EQUIPMENT GROUNDING CONDUCTORS | | | IN NUMEROUS LOCATION ON RISER WHICH | | | APPEAR TO BE MISSING. | | | RESPONSE LTR MENTIONED RMC IS NOT BEING | | | INSTALLED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2005-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-07-18 |
Time |
07:39 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2005-07-15 |
Time |
20:53 |
Sent To |
|
|
| Notes |
| 2005-07-18 00:00:00 | *********** UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTORS FROM CONDUITS ON | | | RISER DIAGRAM. PLEASE SEE SOME OF THESE | | | WERE NOTED ON PREVIOUS REVIEW. | | | MAIN 1 TO TAP BOX? ETC, | | | 250.110,250.24,250.122 | | | | | | 2)NOTE: PLEASE SEE APARTMENT PANEL "C", | | | WHICH APPEARS TO SHOW DRYER AND WASHER | | | AS "SPARE"? PLEASE SEE NEC | | | 210.52F,210.11C2 WHICH REQUIRES A MIN OF | | | ONE LAUNDRY RM CIRCUIT/WASHER FOR A | | | DWELLING. | | | | | | 3)NOTE: PLEASE SEE PREVIOUS REQUESTED | | | FIRE PUMP/ FIRE PUMP CONTROLLER, | | | GENERATOR, AND ATS TO BE PERMITTED. THIS | | | WAS GIVEN ON PROVISO AND THIS MUST BE | | | ADDRESSED BEFORE REVISIONS WILL BE | | | STAMPED. | | | | | | 4)NOTE: PLEASE SEE REVISED ELECTRICAL | | | ROOMS, ELEVATOR MACHINE RM IS NOW NOT ON | | | PLANS?? | | | PLEASE CLARIFY? | | | 620.23,620.24 | | | | | | 5)NOTE: PLEASE SEE 445.13 FOR AMPACITY | | | OF CONDUCTORS FOR GENERATOR. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | 2005-07-15 00:00:00 | PLANS IN ELECTRICAL FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2005-05-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-17 |
Time |
09:55 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2005-05-17 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2005-05-17 00:00:00 | ************* UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE "PROVISO" GIVEN ON | | | 4/18/04. | | | PLEASE SEE NO FURTHER ELECTRICAL | | | REVISIONS SHALL BE STAMPED FOR REVIEW | | | UNTIL FIRE PUMP/FIRE PUMP CONTROLLER, | | | GENERATOR/ATS ETC IS APPLIED FOR FOR | | | PERMIT. | | | THIS WAS REQUESTED OVER 1YR AGO. | | | | | | 2)NOTE: PLEASE SEE EQUIPMENT GROUNDING | | | CONDUCTORS SHOWN FROM FPL/METER TO THE | | | FIRST MEANS OF DISCONNETC. (FIRE PUMP )? | | | PLEASE SEE SOME CONDUITS ON RISER ARE | | | MISSING EQUIPMENT GROUNDING CONDUCTORS. | | | 250.24,250.110, SIZED PER 250.122 | | | | | | | | | NOTES FOR SIGNAGE AND MAPPING ADDED ON | | | PLANS. | | | MCB WAS ADDED TO EDP. | | | | | | PLEASER BE SURE TO SUBMIT INFORMATION | | | FOR PERMIT BEFORE FURTHER REVISIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-12-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-12-02 |
Time |
16:48 |
Rev Time |
2.50 |
| Received By |
dpalmer |
Date |
2004-12-02 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2004-12-02 00:00:00 | *********** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE NOTES FROM "PROVISO" | | | WHEN PLANS WERE ISSUED. | | | NONE OF THESE PROVISO NOTES HAVE BEEN | | | ADDED OR ADDRESSED. | | | | | | 2)NOTE: PLEASE SEE GENERATOR PERMIT HAS | | | NOT BEEN APPLIED FOR AT THE DATE OF | | | THIS | | | REVIEW. | | | | | | 3)NOTE: NOTE FOR ALUM CONDUCTORS HAS | | | BEEN ADDED, HOWEVER NO CHANGES TO | | | CONDUCTORS HAS BEEN MADE. PLEASE | | | INDICATES IF THESE CONDUCTORS ARE TO BE | | | CHANGED OR REMAIN COPPER. | | | ANY CHANGES IN TYPE AND SIZES OF THESE | | | ARE REQUIRED TO BE REVIEWED BEFORE | | | INSTALLATION. | | | 310.16,240.4, 215.5 ETC | | | | | | NO REVISIONS WILL BE SIGNED OFF UNTIL | | | ORIGINAL PROVISO/REDLINES HAVE BEEN | | | ADDRESSED. | | | | | | | | | **************************************** | | | *************************************** | | | PLEASE SEE OUR SYSTEM SHOWS LICENSE | | | INFORMATION ETC FOR BOB MOSS | | | CONTRACTING | | | AS EXPIRED. | | | PLEASE UPDATE RECORDS ASAP. | | | | | | *************************************** | | | | | | PLEASE SEE POSSIBLE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-04-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-04-18 |
Time |
16:47 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2004-04-18 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2004-04-18 00:00:00 | ******* NOTES REDLINED ******* | | | ******* PROVISO ******** | | | | | | 1)NOTE: PLEASE PROVIDE ALL INFORMATION/ | | | SPECS FOR FIRE PUMP CONTROLLER/ PUMP/ | | | AND GENERATOR. | | | PLEASE SEE FIRE REVIEW COMMENTS PERTAIN- | | | ING GENERATOR SYSTEM. THIS WILL BE REQ'D | | | TO BE UNDER A SEPARATE PERMIT. | | | PLEASE BE SURE FIRE PUMP CONTROLLER | | | MEETS 230.76,230.79 AND 110.27 | | | FIRE DEPT MAY NOT OPEN EQUIPMENT TO | | | DISCONNECT POWER. 110.27ALL SPECS WILL | | | BE REQUIRED TO BE SUBMITTED W/PERMIT | | | APPLICATION IF NOT BEFORE, PENDING FIRE | | | REVIEW COMMENTS. | | | | | | 2)NOTE: NOTES REDLINED FOR ALL REQ'D | | | SIGNAGE AT EACH ELECTRICAL ROOM AND FIRE | | | PUMP ROOM. SIGNAGE AND A DIAGRAM WILL BE | | | REQ'D AT FIRE CONTROL ROOM TO INDICATE | | | AND DIRECT FIRE DEPT PERSONNEL TO ALL | | | MAIN ELECTRICAL ROOMS/ GENERATOR LOCAT- | | | -IONS/FIRE PUMP ROOMS. | | | 230.2E | | | | | | 3)NOTE: NOTES REDLINED FOR PANIC HARD- | | | -WARE REQ'D ON MAIN ELECTRICAL ROOM | | | DOORS PER 110.26 | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-03-04 |
Time |
11:50 |
Rev Time |
8.00 |
| Received By |
dpalmer |
Date |
2004-03-04 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2004-03-04 00:00:00 | ************ UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE FS 481.219, 471.023. | | | PLANS REQ;D TO HAVE ALL LICENSE #'S | | | AS REQ'D PER ABOVE ON TITLE BLOCKS PER | | | FAC 61G15-23.002, 61G1-16.004 | | | THIS IS REQ'D FOR ARCH'S AND ENG'S. | | | THIS IS ALSO REQ'D ON ALL SHEETS AND | | | FOR ALL TRADES WEATHER OR NOT COMMENT | | | IS MADE BY OTHERREVIEWERS. | | | | | | 2)NOTE: PLEASE 110.26 FOR EXITING REQ'D | | | FOR ELECTRICAL ROOMS. MIN. | | | | | | 3)NOTE; PLEASE NOTE ON PLANS/RISER. | | | TACTICAL SIGNAGE/MAPS BE REQ'D FOR FIRE | | | PERSSONELL TO MAIN ELECTRICAL ROOMS. | | | KNOX BOX FOR KEYS TO MAIN ELECTRICAL | | | ROOMS. | | | | | | 4)NOTE: PLEASE SEE CIRCUITING FOR SD'S | | | IN UNITS. SHOWS SD'S ON MORE THAN ONE | | | CIRCUIT. SD'D ARE REQ'D TO BE WIRED | | | "INLINE", THIS WOULD CAUSE AN ELECTRIC- | | | -AL PROBLEM ON MORE THAN ONE CIRCUIT. | | | PLEASE SEE NFPA-72 8-1.4.2 FOR INSTALL- | | | -ATION OF SD'S AND CLEARENCES FROM BATH | | | / KITCHEN DOORS AND FROM KITCHEN COOKING | | | APPLIANCES. A NOTE MAY BE ADDED FOR THIS | | | | | | 5)NOTE: PLEASE SEE SOME UNITS DO NOT | | | SEEM TO HAVE COMPLETED WALLS. DOES NOT | | | SHOW RECEPTS REQUIRED FOR WALLS,210.52 | | | EGRESS LT CONTROL PER 210.70 | | | ETC. | | | | | | 6)NOTE: PLEASE PROVIDE PLANS FOR | | | EXISTING TOWER ELECTRICAL TO BRING UP TO | | | 2002 NEC PER FBC CHAPTER 34 FOR ADDITION | | | -S TO EXISTING BLDGS. | | | | | | 7)NOTE: PLEASE SEE UNIT "F" PANEL. | | | SHOWS 164.9A'S W/ 200A OCP AND CONDUCTOR | | | -S NOT RATED FOR 200A'S PER 310.16 | | | | | | 8)NOTE: PLEASE INDICATE OCP FOR EACH | | | UNIT/PANEL. PLEASE CORRELATE OCP/AWG | | | | | | 9)NOTE: PLEASE CLARFIY/SHOW EQUIPMENT | | | GROUNDING CONDUCTORS REQ'D. 250.110 | | | 250.24, SIZE PER 250.122 | | | | | | 10)NOTE: PLEASE SEE AIC RATINGS SHOWN | | | FOR PANELS, SHOWS 100,000 RATED PANELS | | | PLEASE VERFIY. IF SHOWN AS 100,000, THEN | | | THATS WHAT WILL BE REQ'D TO BE INSTALLED | | | | | | 11)NOTE: PLEASE SEE NOTES MENTION THAT | | | ALUM CONDUCTORS AMY BE USED. | | | PER LOCAL AMENDMENTS ALUM CONDUCTOR ARE | | | NOT PERMITTED TO BE USED FOR GROUNDING | | | OR BONDING. 310.2 | | | CONTRACTOR MAY ALSO NOT JUST CHANGE | | | SIZES AND TYPE OF CONDUCTORS UNTIL PLANS | | | ARE REVISED BY THE ENGINEER OF RECORD, | | | SUBMITTED TO THE CITY OF WEST PALM BEACH | | | FOR REVIEW AS A REVISION. | | | PLEASE ADJUST NOTE. | | | | | | 12)NOTE: PLEASE LIST/NOTE THE REQUIRED | | | ARC FAULT PROTECTED CIRCUITS PER 210.12 | | | ON PANEL SCHEDULES FOR UNITS. | | | | | | 13)NOTE: PLEASE SEE LOAD SHOWN FOR | | | PANELS "E" AND "F". | | | LOAD CALCS SEEM TO BOTH FIGURED IN AS | | | TYPICAL?? | | | | | | 14)NOTE: PLEASE PROVIDE OCP/ NOTE | | | FOR MAIN FOR FIRE PUMP 695.4B1 | | | | | | 15)NOTE: PLEASE SEE EDP, PLEASE CORRE- | | | -LATE OCP / AWG'S PER 310.16. | | | WIRE SIZES ARE NOT RATED FOR OCP. | | | | | | PLANS SHOULD REFERENCE 2002 NEC | | | PLEASE GO OVER PLANS FOR CODE COMPLIANCE | | | BEFORE RESUBMITTING. | | | PLANS WILL HAVE A ONE TIME RESUB @ NO | | | CHARGE, EACH TIME THEREAFTER WILL BE A | | | 10% RESUB FEE. | | | | | | SEPARATION OF 4 HR FIRE WALL WILL BE | | | REQUIRED BETWEEN NEW AND EXSITING IF | | | CHAPTER 34 FBC IS NOT AN OPTION. | | | | | | COMPLETE ELECTRICAL REVIEW CAN NOT BE | | | DONE AT THIS TIME DUE TO PLANS NOT BEING | | | COMPLETE AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2004-12-03 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-12-03 |
Time |
08:39 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2004-12-03 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2004-04-13 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-04-13 |
Time |
13:57 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2004-04-13 |
Time |
13:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2004-02-25 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2004-02-25 |
Time |
15:03 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2004-02-25 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2004-02-25 00:00:00 | FAILED: | | | 1. COMMENTS AND ISSUES WITH PUBLIC | | | UTILITIES IN REGARD TO CIVIL PLANS | | | MUST BE ADDRESSED AND RESOLVED PRIOR TO | | | CONSTRUCTION SERVICES DEPARTMENT' | | | APPROVAL. | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-30 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-30 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2005-12-30 00:00:00 | ******PASSED****** | | | | | | NEW SHEETS ILLUSTRATING SMOKE BOMB | | | LOCATIONS WERE SUBMITTED WITH REVISED | | | SHEETS. PLEASE COORDINATE THE SMOKE TEST | | | WITH THE BUREAU OF FIRE PREVENTION AND | | | CONSTRUCTION SERVICES. THE ENGINEER | | | RESPONSIBLE FOR THE DESIGN OF THE SMOKE | | | CONTROL/EVAC SYSTEM SHALL BE PRESENT | | | DURING THE TEST. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2005-07-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-07-27 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-07-27 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2005-07-27 00:00:00 | SHEETS FP-1, FP-2 & FP-3A SUBMITTED FOR | | | REVISION DATED 6/20/05 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-06-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-06-24 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-06-24 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2005-06-24 00:00:00 | PLEASE REVIEW CBAA CASE NUMBER 1253 | | | FOR DETAILS. | | | | | | MIKE CARSILLO, FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2004-12-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-06-20 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-06-20 |
Time |
13:10 |
Sent To |
FIRE |
|
| Notes |
| 2005-06-20 00:00:00 | CALLED PAM YUSKO, CBAA SECRETARY AND | | | REQUESTED ON HER VOICE MAIL THE | | | CBAA DOCUMENTS FOR CASE # 1253 | | | REGARDING VARIANCE FOR PREVIOUS | | | ISSUE. | | | | | | MIKE CARSILLO, FIRE MARSHAL | | | 835-2910 | | 2004-12-15 00:00:00 | 1. WRONG HEADROOM NOTED FOR STAIR # 1. | | | MINIMUM HEADROOM CODE IS TO BE MET. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-04-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-04-22 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-12-15 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2004-04-22 00:00:00 | 1) THE ALTERNATIVE EGRESS FROM THE 2ND | | | FLOOR COMMON AREA THAT IS PROVIDED | | | THROUGH THE EXISTING TOWER SHALL BE | | | WIDE ENOUGH TO ACCEPT THE | | | ANTICIPATED LOAD. | | | | | | 2) NO STORAGE IS PERMITTED IN ANY | | | IDENTIFIED VOID AREAS DESIGNATED | | | ON THE PLANS. IF STORAGE IS PLANNED, | | | THE FIRE SPRINKLER PROTECTION IS | | | REQUIRED. | | | | | | 3) OAK TREES PLANNED CANNOT INTERFERE | | | WITH ANY FIRE LANES. | | | | | | 4) THE MIAMI STANDARD1 1/2 THREAD | | | NOTE IS NOT APPLICABLE TO THE CITY | | | OF WEST PALM BEACH. PAGE FP-7. | | | | | | 5) ROOF PLAN PAGE FP-5 INDICATES | | | FDC'S. THESE SHOULD BE CALLED ROOF | | | MANIFOLDS. | | | | | | 6) PRODUCT DATA WILL BE REQUIRED FOR | | | THE FIRE PUMP AND EMERGENCY | | | GENERATOR. SEPARATE PLANS AND PERMITS | | | REQUIRED. | | | | | | 7) SINCE EOL'S ARE SHOWN, THE FIRE | | | ALARM SYSTEM SHALL BE FULLY | | | ADDRESSABLE. | | | | | | 8) SMOKE DETECTORS IN UNITS B & C APPEAR | | | TO BE INSTALLED TOO CLOSE TOGETHER. | | | PLEASE REVISE. | | | | | | 9) EXIT SIGNS NEEDED NEAR GARAGE DOUBLE | | | DOOR EXIT TUNNEL. PLEASE PROVIDE. | | | | | | 10) PLEASE SEE ELECTRICAL PLAN | | | REVIEWER NOTES. | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-02-18 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-02-18 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-02-18 |
Time |
07:31 |
Sent To |
|
|
| Notes |
| 2004-02-18 00:00:00 | 1) ELECTRONIC SWITCHES WILL BE | | | REQUIRED ON THE FIRE LINE BACKFLOW | | | DEVICE. | | | | | | 2) A TEMPORARY STANDPIPE SYSTEM WILL | | | BE REQUIRED WHEN THE BUILDING REACHES | | | THREE STORIES OR 30 FEET IN HEIGHT. | | | | | | 3) EGRESS STAIRS FOR THE BUILDING | | | SHALL BE KEPT UP WITH CONSTRUCTION. | | | | | | 4) ALL DEMOLITION, RENOVATION, AND | | | CONSTRUCTION SHALL COMPLY WITH | | | NFPA 241. | | | | | | 5) A KNOX-BOX WILL BE REQUIRED. | | | | | | 6) ON A RECENT VISIT, THE EXISTING | | | PARKING GARAGE DISPLAYED POSSIBLE | | | CODE VIOLATIONS. IT IS UNKNOWN IF | | | THE REQUIRED VENTILATION SYSTEM FOR | | | THE GARAGE IS WORKING. ALSO ALMOST | | | ALL OF THE REQUIRED EXIT SIGNS WERE | | | NOT ILLUMINATED. PLEASE ADVISE | | | DISPOSITION OF THESE CODE VIOLATIONS. | | | | | | 7) A TWO HOUR FIRE SEPARATION IS | | | REQUIRED BETWEEN THE EXISTING PARKING | | | GARAGE AND THE NEW TOWER. | | | | | | 8) PLEASE INDICATE WHICH ELEVATORS | | | WILL BE STRETCHER ACCESSIBLE. | | | | | | 9) NO DOOR PRESENT FOR STAIR # 1 ON | | | PAGE A-2.3. | | | | | | 10) TACTILE SIGNAGE REQUIRED AT | | | STAIRWELL DOORS. | | | | | | 11) ALL SHAFTS THAT ARE LARGE ENOUGH | | | FOR PERSONS TO FALL INTO MUST BE | | | MARKED SHAFTWAY IN 6" HIGH LETTERS. | | | | | | 12) THE GROUND FLOOR LIFE SAFETY PLAN | | | APPEARS CONFUSING. PLEASE CLARIFY. | | | | | | 13) THE BUILDING ADDRESS IS REQUIRED | | | ON THE NEW BUILDING. A MINIMUM OF 6" | | | HIGH NUMBERS ARE REQUIRED. | | | | | | 14) FDC'S ARE NOTED ON THE ROOF. THEY | | | SHOULD READ ROOF MANIFOLDS. | | | | | | 15) PLEASE NOTE ON THE PLANS ALL | | | REQUIRED ITEMS TO BE INSTALLED IN | | | THE FIRE COMMAND ROOM AS PER 412 OF | | | THE FLORIDA BUILDING CODE. | | | | | | 16) THE NEW FIRE ALARM SYSTEM IS | | | REQUIRED TO BE UL LISTED FOR CENTRAL | | | STATION SERVICE. | | | | | | 17) PLANS NEED TO MENTION "ANTICIPATED | | | STACK" ON THE MECHANICAL PLANS. | | | | | | 18) ELEVATOR WARNING SIGNS REQUIRED. | | | | | | 19) PLEASE INDICATE OCCUPANT LOAD FOR | | | POOL DECK. | | | | | | 20) ALL NEW STAIRS AND RAMPS SHAL HAVE | | | HANDRAILS ON BOTH SIDES. | | | | | | 21) PLEASE PROVIDE DETAILS ON SOUND | | | ATTENUATION INSULATION FOR TRASH | | | CHUTE. | | | | | | 22) PLEASE DEMONSTRATE THAT GUARDRAILS | | | ON STAIRS WILL RESIST A 4" SPHERE. | | | | | | 23) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM INSTALLATION. | | | | | | 24) PLEASE EXPLAIN NOTE # 7 ON A-5.2. | | | HOW WILL FIRE RESCUE GAIN ACCESS TO | | | THE STAIRS FROM THE EXTERIOR. | | | | | | 25) PLEASE EXPLAIN 20 MINUTE FIRE | | | RATED DOORS AT ELEVATOR/LOBBY CORRIDOR. | | | THESE DOORS ARE NOT THE SAME AS ENTRY | | | DOORS TO APARTMENTS. | | | | | | 26) PLEASE INDICATE LOCATIONS OF ALL | | | PORTABLE FIRE EXTINGUISHERS. | | | | | | 27) THERE APPEARS TO BE DOORS LOCATED | | | WITHIN THE FOUR HOUR WALL ON PAGE | | | A-2.7. ARE THESE DOORS PROPERLY RATED. | | | | | | 28) THE EXITING FIRE SPRINKLER AND | | | LIFE SAFETY EQUIPMENT ARE TO REMAIN | | | WHILE THE WEST TOWER IS UNDER | | | CONSTRUCTION. | | | | | | 29) THE GARAGE IS PRESUMED TO REMAIN | | | OCCUPIED WHILE THE WEST TOWER IS | | | UNDER CONSTRUCTION. | | | | | | 30) THE EXITING DOOR AT THE TOP OF THE | | | STAIRS NEAR THE AT&T ROOM SWINGS | | | INWARD. THIS EXIT DOOR SHOULD IN THE | | | DIRECTION OF EXIT TRAVEL. PLEASE | | | REVISE PLANS. | | | | | | 31) PLEASE EXPLAIN WHY ON PAGE A-2.7 | | | THERE APPEARS TO BE A DEAD-END | | | CORRIDOR NEAR ELEVATOR # 1. | | | | | | 32) PLEASE DEMONSTRATE COMPLIANCE WITH | | | ALL SECTIONS OF 412, OF THE FLORIDA | | | BUILDING CODE. | | | | | | 33) IS THE PROPOSED FIRE CONTROL ROOM | | | LARGE ENOUGH TO CONTAIN ALL THE | | | REQUIRED EQUIPMENT IN 412 OF THE | | | FLORIDA BUILDING CODE, FIRE COMMAND | | | ROOM. | | | | | | 34) ENSURE THAT DOORS FOR THE PROJECT | | | SWING IN THE PROPER DIRECTION. | | | | | | 35) THE NEW FIRE ACCESS ROAD WILL | | | SUPPORT HOW MUCH WEIGHT. | | | | | | 36) SOME EXISTING ROOMS ARE MISSING | | | FIRE SPRINKLER HEADS NEAR PHASE I AND | | | PHASE II ROOMS. | | | | | | 37) PLEASE PROVIDE PRESCRIPTIVE | | | STRENGTH REQUIREMENTS FOR 3'- 6" HIGH | | | GLASS RAILING SHOWN ON A-2.2. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2006-02-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-24 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-24 |
Time |
10:18 |
Sent To |
B |
|
| Notes |
| 2006-02-24 00:00:00 | TO "RBROWN" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2006-02-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-15 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-15 |
Time |
10:54 |
Sent To |
B |
|
| Notes |
| 2006-02-15 00:00:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2005-12-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-14 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-14 |
Time |
16:06 |
Sent To |
M |
|
| Notes |
| 2005-12-14 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2005-12-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-05 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-05 |
Time |
11:47 |
Sent To |
M |
|
| Notes |
| 2005-12-05 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2005-12-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-01 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-01 |
Time |
12:42 |
Sent To |
M |
|
| Notes |
| 2005-12-01 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-30 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-30 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2005-12-19 00:00:00 | TO "COMM" BD#44 | | 2005-11-30 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2005-10-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-13 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-13 |
Time |
09:49 |
Sent To |
Z |
|
| Notes |
| 2005-10-14 00:00:00 | LANDSCAPE PLANS ROUTED TO ANGELLA | | | JONES-VANN FOR ZONING REVIEW. | | 2005-10-13 00:00:00 | SENT TO "Z" BOX FROM "COMM" BD#7 | | | SENT TO PAUL SCHMITZ TO REVIEW | | | IRRIGATION PLANS BEFORE ROUTING | | | LANDSCAPE PLANS TO ZONING. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-29 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-29 |
Time |
09:53 |
Sent To |
P |
|
| Notes |
| 2005-09-29 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2005-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-13 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-13 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2005-09-13 00:00:00 | TO "COMM" BD#10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2005-08-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-22 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-22 |
Time |
09:20 |
Sent To |
B |
|
| Notes |
| 2005-08-22 00:00:00 | TO "RBROWN" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-09 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-09 |
Time |
17:22 |
Sent To |
P |
|
| Notes |
| 2005-08-09 00:00:00 | TO "P" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-08-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-08-09 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-08-09 |
Time |
15:00 |
Sent To |
P |
|
| Notes |
| 2005-08-09 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-06-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-06-23 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-06-23 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2005-06-27 00:00:00 | TO "COMM" BD#34 | | 2005-06-23 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-06-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-06-08 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-06-08 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2005-06-08 00:00:00 | TO 'RBROWN' DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2005-05-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-05-03 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-05-03 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2005-06-22 00:00:00 | ARCH/STRUCT/MEP REVISION SENT BACK TO | | | FIRE PLAN REVIEW TO COMPLETE THEIR | | | REVIEW. | | | | | | | | 2005-05-03 00:00:00 | TO "COMM" BD#16/PLANS ON RACK 3 ROLLS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-25 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2005-05-03 00:00:00 | IN INCOMING/AWAITING SPACE ON "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-12-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-28 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-28 |
Time |
10:22 |
Sent To |
B |
|
| Notes |
| 2004-12-28 00:00:00 | TO "RB" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-11-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-15 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-15 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2004-11-15 00:00:00 | TO COMM BD#53 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-11-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-15 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-15 |
Time |
15:20 |
Sent To |
B |
|
| Notes |
| 2004-11-15 00:00:00 | TO RB DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-09-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-01 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-01 |
Time |
13:09 |
Sent To |
B |
|
| Notes |
| 2004-09-01 00:00:00 | TO RB DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-04-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-13 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-13 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2004-04-13 00:00:00 | TO COMM BD#40 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-04-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-20 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-02-20 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2004-02-20 00:00:00 | TO COMM BD#43 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
N |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-02-03 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-02-03 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2006-02-03 00:00:00 | MECHANICAL KEEPED A COPY OF SNOKE BOMB | | | LAYOUT SENT A COPY TO FIRE 2/3/06 HM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2005-12-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-12-19 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-12-19 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2005-12-19 00:00:00 | AC-1, EMPLOYEE LOUNGE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
|
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-12-07 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-12-07 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2005-12-07 00:00:00 | PLAN SHEET AC-3 KEY NOTES - HVAC ITEM | | | #11, INDICATES 1 1/2" VENTILATION PIPE | | | DOWN 6" AFF.PLAN DOES NOT REFLECT THIS | | | LINE.PLEASE INDIATE PURPOSE AND WAS | | | THIS ELIMINATED? |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2005-08-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-08-10 |
Time |
15:11 |
Rev Time |
1.50 |
| Received By |
pkrauss |
Date |
2005-08-10 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2005-08-10 00:00:00 | SMOKE EVAC TO ROOF USING OA DUCT & | | | CONTROLED BY DAMPERS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2005-07-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-07-22 |
Time |
12:37 |
Rev Time |
3.50 |
| Received By |
pkrauss |
Date |
2005-07-22 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2005-07-22 00:00:00 | DENIED: | | | PLEASE NOTE, COMMENTS FROM REVIEW DATED | | | 6/15/05 WERE NOT ADDRESSED.PAGES | | | SUBMITTED FOR REVISION ON 6-22-05 ARE AS | | | FOLLOWS; AC-1, AC-2, AC-3, AC-4, AC-4A. | | | | | | 1.PLAN SHEET AC-2 - EXIT CORRIDOR | | | INDICATES SPF-3,PLEASE CLARIFY, WILL | | | THIS ONLY RUN DURING EMERGENCY POWER? | | | PLEASE NOTE, SPF-3 IS NOT INDICATED ON | | | THE EQUIPMENT SCHEDULE ON PLAN SHEET | | | AC-8.0 OR LISTED WITH THE STAIRWELL | | | PRESSURIZATION EQUIPMENT LISTED ON PLAN | | | SHEET AC-11. | | | | | | 2.PLAN SHEET AC-3, AC-4 & AC-4A DO NOT | | | INDICATE LOCATION OF LEF-1.PLANS SHOW | | | LEF-1 HAS BEEN DELETED BUT IS STILL | | | INDICATED IN THE SEQUENCE OF OPERATION | | | ON PLAN SHEET AC-11 (THIS SHEET HAS NOT | | | BEEN REVISED).PLEASE INDICATE MEDTHOD | | | OF SMOKE CONTROL LISTED UNDER 2001 FBC | | | 412.5. | | | | | | PLEASE NOTE, MECHANICAL REVISIONS | | | SUBMITTED 6-2-05 WERE DENIED AND | | | COMMENTS WERE NOT ADDRESSED.REVISIONS | | | SUBMITTED UNDER THIS REVIEW CONTAIN THE | | | SAME COMMENTS TO PROPOSED REVISIONS. | | | PLEASE PROVIDE A RESPONSE LETTER TO | | | COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2005-06-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2005-06-15 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2005-06-15 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2005-06-15 00:00:00 | DENIED: | | | 1.PLAN SHEET AC-2 INDICATES SPF-4 | | | BEING DELETED.HOW WILL VENTILATION | | | REQUIREMENT BE MET INACCORDANCE WITH | | | 2001 FBC(M)TABLE 403.3.PLEASE ALSO | | | CLARIFY RATING OF THIS AREA AS WELL AS | | | HALL SERVICED BY SPF-3.ARE THESE EXIT | | | CORRIDORS? | | | | | | 2.PLAN SHEET AC-3 THROUGH AC-6 | | | INDICATES THE REMOVAL OF LEF-1.PLAN | | | SHEET AC-11 SEQUENCE OF OPERATION NOW | | | READS "RTU-1 WILL SHUT DOWN".PLEASE | | | CLARIFY HOW THE REQUIREMENTS OF 412.5 | | | WILL BE MET. | | | | | | 3.PLAN SHEET AC-11 THE SEQUENCE OF | | | OPERATION FOR FLOORS 2 THROUGH 12, STILL | | | INDICATES LEF-1 AS A PART OF THE SMOKE | | | CONTROL SYSTEM BUT ARE REMOVED FROM THE | | | PLAN SHEETS (AC-3 THRU AC-6). | | | | | | IF YOUHAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-04-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-22 |
Time |
13:05 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-04-22 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2004-04-22 00:00:00 | PROVISO: | | | RETURN AIR TO THE CONDOS SHALL BE | | | LOCATED WITHIN CLOSE PROXIMITY TO THE | | | RETURN AIR TO PROMOTE THE CIRCULATION | | | OF FRESH AIR INTO THE A/C SYSTEM. | | | | | | RECEIVED SUBMITTAL LETTER FROM RALPH | | | PENA ADDRESSING THE EXISTING VENTILATION | | | WAS DESIGNED PER CODE AT THE TIME OF | | | CONSTRUCTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
|
Date |
2004-04-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-15 |
Time |
12:36 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2004-04-15 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2004-04-15 00:00:00 | PLAN SHEET AC-8 INDICATES FRESH AIR TO | | | THE APARTMENTS THROUGH RTU-1.HOW WILL | | | THIS BE INTRODUCED INTO THE AHU TO THE | | | APARTMENTS.PLEASE INDICATE DUCT SIZE, | | | MATERIAL AND LAYOUT. PLANS ARE OTHERWISE | | | CODE COMPLIANT. | | | 4-16-04, PER CONVERSATION WITH ENG RALPH | | | PENA, PLAN WITH BE REVISED TO REFLECT | | | O.A. FROM RTU-1.PLAN TO BE SUBMITTED | | | 4-19-04. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-03-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-03-05 |
Time |
09:38 |
Rev Time |
7.00 |
| Received By |
pkrauss |
Date |
2004-03-05 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2004-03-05 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE SEQUENCE OF OPERATION | | | FOR THE SMOKE EVAC SYSTEM. | | | | | | 2.CORRIDORS IN THE "LOFT" AREAS APPEAR | | | TO BE BY SMOKE CONTROL/STACK EFFECT. | | | SHOW COMPLIANCE WITH 2001 FBC 412.5 | | | | | | 3.PLANS DO NOT INDICATE THE EXISTING | | | ENCLOSED GARAGE.INDICATE ANY NEW OR | | | EXISTING VENTILATION & EVAC SYSTEMS. | | | SHOW COMPLIANCE WITH 2001 FBC 411.4.2. | | | | | | 4.PLAN SHEET AC-1, TOILET EXHAUST IS | | | SHOWN TERMINATING IN THE ENCLOSED GARAGE | | | EXHAUST IS TO TERMINATE TO THE OUTDOORS | | | PER 2001 FBC(M) 501.3.PLEASE NOTE, | | | THE WALL WHERE THE EXHAUST IS TERMATING | | | AT IS A 4 HR FIRE RATED SEPARATION WALL. | | | | | | 5.PLAN SHEET AC-2, 2ND FLOOR PLAN | | | INDICATES 2 RTU-2, SHOULD INDICATE 1 | | | RTU-3 & 1 RTU-2. | | | | | | 6.PLAN SHEET AC-8.0, DRYER EXHAUST | | | INFORMATION, SPECIFIC DRYER TO BE | | | INSTALLED FOR FINAL INSPECTION. | | | | | | 7.PLAN SHEET AC-8.0 APARTMENT O.A. | | | CALCULATIONS, PER REVISION TO THE 2001 | | | FBC(M) 403.3 EFFECTIVE JUNE 30, 2003; | | | VENTILATION SYSTEMS FOR OTHER THAN R-3 | | | (ONE & TWO FAMILY DWELLINGS) SHALL BE | | | DESIGNED TO SUPPLY THE MINIMUM OF OUT- | | | DOOR AIR IN ACCORDANCE WITH TABLE 403.3. | | | | | | 8.PLAN SHEET AC-9.0 REFRIGERANT | | | ENCLOSURE TO BE 2 HR FIRE RATED & SHAFT | | | IS TO BE VENTILATED PER NFPA 90A 3-3.4 | | | & ASHRAE 15-92 11.12.3 (B) RESPECTIVELY. | | | | | | 9.PLAN SHEET AC-9.0 DETAIL FOR THE | | | TOILET & DRYER EXHAUST, TOILET AND FRESH | | | AIR INSTAKES ARE TO BE PROTECTED IN | | | ACCORDANCE WITH 2001 FBC(M) 401.6. | | | DRYER EXHAUST SHALL BE NON-SCREENED & | | | HAVE A BACK-DRAFT DAMPER PER 2001 FBC(M) | | | 504.4. | | | | | | 10. PLEASE PROVIDE INFORMATION ON THE | | | EMERGENCY GENERATOR; LOCATION, TYPE OF | | | GENERATOR, NEW OR EXISTING, TERMINATION | | | OF EXHAUST, ETC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2005-10-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-10-15 |
Time |
12:50 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2005-10-15 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2005-10-15 00:00:00 | REVISED PLUMBING PAGE P-4A OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-10-14 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-10-09 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2005-10-09 00:00:00 | REVISIONS: ADDRESSING COMMENTS FOR | | | 7-20-05 AND 8-26-05 | | | ALSO IRRIGATION. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2005-08-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-08-26 |
Time |
13:04 |
Rev Time |
3.00 |
| Received By |
kstevens |
Date |
2005-08-26 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2005-08-26 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | A. FROM PREVIOUS REVISION REVIEW: | | | 4. SHT P-12 INDICATE THE TOTAL SQUARE | | | FEET DRAINING INTO THE EXISTING 6" STORM | | | LINE INCLUDING THE 2880 SF FROM RWL #2, | | | AND ON THE OTHER STORM LINE INCLUDING | | | THE 1310 SF FROM RWL #6. TABLE 1106.3 | | | ***************NEW COMMENT************** | | | 1B. GAS RISER DIAGRAM WAS NOT INCLUDED | | | IN THE ORIGINAL PLANS. GAS PLANS WERE | | | SUBMITTED BY THE PLUMBING CONTRACTOR AND | | | WERE APPROVED. GAS PERMIT WAS ISSUED ON | | | THE GAS RISER DIAGRAM PROVIDED AND DOES | | | NOT REFLECT THE GAS RISER SUBMITTED IN | | | THIS REVISION. PLEASE COORDINATE WITH | | | THE PLUMBING CONTRACTOR AND INDICATE | | | WHICH SYSTEM WILL BE USED, AND IF A | | | REVISION WILL BE SUBMITTED, IT WILL BE | | | SUBMITTED UNDER THE GAS PERMIT | | | (05031733). | | | 2B. INFORMATIONAL: SHT P-10.0 HAS BEEN | | | APPROVED, BUT AS INDICATED IN PRIOR | | | REVISION, RISERS S/2B & S/3 SHALL BE | | | REVISED TO REFLECT THE CHANGES SHOWN ON | | | SHEET P-4.A. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2005-07-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-07-20 |
Time |
16:00 |
Rev Time |
4.33 |
| Received By |
kstevens |
Date |
2005-07-20 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2005-07-20 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT P-1 REVISION #7 INDICATE RWL | | | NUMBER OF STORM LINE CONNECTING BETWEEN | | | PARKING SPACES 26 & 27. - NO REVISION #8 | | | FOUND. PLEASE CLARIFY. SECTION 104.2.1. | | | 2. SHT P-2 SEE PROVISO FROM REVISION | | | DATE STAMPED JUNE 13, 2005. SHOW THE | | | LOCATION OF SECONDARY ROOF DRAINS. | | | SECTION 1107. | | | 3. SHT P-4A WHITE OUT IS NOT APPROVED | | | FOR PLAN CORRECTIONS/CHANGES. SECTION | | | 104.2.1.3. | | | 4. P-12 INDICATE THE TOTAL SQUARE FEET | | | DRAINING INTO THE EXISTING 6" STORM LINE | | | INCLUDING THE 2880 SF FROM RWL #2, AND | | | ON THE OTHER STORM LINE INCLUDING THE | | | 1310 SF FROM RWL #6. TABLE 1106.3 | | | 5. RECALCULATE THE SQUARE FEET FOR THE | | | STORM DRAIN LINE FOR RWL #4. CHECK ALL | | | PIPE SIZES PER TABLE 1106.3. | | | 6. THE SANITARY RISER DIAGRAMS S/2B AND | | | S/3 SHALL BE REVISED TO REFLECT THE | | | CHANGES SHOWN ON SHEET P-4.A. SECTION | | | 104.2.1. | | | 7. INFORMATIONAL - THE FOLLOWING SHEETS | | | HAVE BEEN APPROVED AS REVISIONS, AND ONE | | | SET HAS BEEN RETAINED FOR THE FILE SET. | | | P-3, P-4.A, P-8 AND P-13. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2005-06-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-13 |
Time |
19:39 |
Rev Time |
2.80 |
| Received By |
kstevens |
Date |
2005-06-13 |
Time |
19:39 |
Sent To |
|
|
| Notes |
| 2005-06-13 00:00:00 | REVISION DENIED | | | | | | 1. SHT P10 FROM PREVIOUS REVIEW. SANT. | | | RISERS S/1A-S/7 & S/1C/CU. FIXTURE UNITS | | | ADDED TO STACKS SHALL BE 16 NOT 10. 5FU | | | FOR BATHROOM GROUP, AND 1FU FOR LAV AND | | | 2FU FOR ADDED TUB OR SHOWER. - SHOW | | | CORRECT FIXTURE UNITS FOR STACKS. - ONE | | | SHT P10 IS A COPY OF THE SIGNED, SEALED, | | | DATED SHEET. ALL SETS SHALL BE SIGNED, | | | SEALED & DATED. FAC 61G15-23.002 | | | | | | 2. SHT P12 ALL CORRECTIONS HAVE BEEN | | | ADDRESSED FROM LAST REVISION REVIEW, BUT | | | A NEW COMMENT WAS DISCOVERED. THE 6" | | | PIPE AT 5490 SF IS NOT LARGE ENOUGH. | | | MINIMUM 8" PIPE IS REQUIRED. TABLE | | | 1106.3. | | | | | | 3. ALL OTHER SHEETS HAVE BEEN APPROVED | | | AND ONE SET HAS THEM REMOVED FOR FILE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-12-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-12-11 |
Time |
15:47 |
Rev Time |
2.75 |
| Received By |
kstevens |
Date |
2004-12-11 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2004-12-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT P-1 CONDENSATE SHALL DRAIN | | | SEPARATELY FROM THE BUILDING AND THEN | | | CONNECT TO STORM DRAIN, OR A CATCH | | | BASIN | | | A RELIEF VENT IS REQUIRED AS CONDENSATE | | | EXITS THE BUILDING. | | | 2) SHT P-10 INDICATES REVISION #1, BUT | | | THE REVISIONS ARE NUMBERED #2. PLEASE | | | CLARIFY. SECTION 104.2.1 | | | 3) SHT P-10 SANT RISERS 5/1A-S/7, AND | | | S1C/S7. FIXTURE UNITS ADDED TO STACK | | | SHALL BE 16 NOT 10. 5 FU FOR BATHROOM | | | GROUP, A 1 FU FOR LAV, AND 2 FOR ADDED | | | TUB OR SHOWER. | | | 4) SHT P-11 CONDENSATE RISERS C/1A, C/2, | | | AND C/2A APPEAR TO HAVE BEEN CAPPED OFF. | | | THESE RISERS SHALL VENT THROUGH THE ROOF | | | AND SHALL NOT BE CAPPED OFF. PLEASE | | | CLARIFY. SECTION 104.2.1 | | | 5) SHT P-12 RWL/2 AND RWL/6 COMBINED | | | TOTAL UP TO 3500 SF. MAXIMUM SF ON 5" | | | STORM HORIZONTAL DRAINAGE PIPE IS 2969 | | | SF ON 5" PIPE. TABLE 1106.3 | | | 6) FOLLOWING SHEETS WERE OK AND WILL BE | | | STAMPED WHEN RESUBMITTED. P-2, P-3, P-4, | | | P-5, P-5.1, P-7, P-8, P-9, P-10.1, AND | | | P-13. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-04-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-19 |
Time |
16:26 |
Rev Time |
4.00 |
| Received By |
kstevens |
Date |
2004-04-19 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-02-26 |
Time |
10:31 |
Rev Time |
10.00 |
| Received By |
kstevens |
Date |
2004-02-26 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2004-02-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FLORIDA STATUTES | | | | | | 1) EAST TOWER SHALL COMPLY WITH FBC-2001 | | | PLUMBING PER SECTION 3401.7.1.1.1 | | | 2) CERTIFICATE OF AUTHORIZATION NUMBER | | | IS REQUIRED ON ALL ARCHITECTURAL SHEETS | | | PER FS 481.291. | | | 3) SHT A-2.1 TRENCH DRAIN AT TRASH DUMP- | | | STER. IS THIS TRENCH DRAIN CONNECTED TO | | | STORM? WILL THE DUMPSTER PAD BE WASHED | | | DOWN INTO THE TRENCH DRAIN? PLEASE | | | CLAIRFY. | | | 4) SHT A2.2 SUBMIT CALCULATIONS FOR | | | COMMON AREAS PER TABLE 403.1. INDICATE | | | AREAS TO INCLUDE CONFERENCE ROOM, MULTI- | | | MEDIA, HEALTH CLUB, MANAGERS OFFICE ECT. | | | 5) SHT A-5.5 EMPLOYEE TOILET ROOM @ THE | | | GROUND FLOOR, DOOR SHALL NOT OPEN INTO | | | THE TURNING CIRCLE AND WATER CLOSET | | | SHALL NOT OBSTRUCT THE TURNING CILCLE. | | | SECTION 11-4.22.3. | | | 6) SHT A-8.2 DETAIL #4, PER SECTION | | | 1503.4.2 OVERFLOW SCUPPERS SHALL BE IN- | | | STALLED IN WALLS OR PARAPETS WITH THE | | | INLET FLOW LINE NOT LESS THAN 2" ABOVE | | | THE ROOF SURFACE, EXCLUDING SUMPS, OR | | | MORE THAN 4" ABOVE THE ROOF SURFACE AND | | | SHALL BE LOCATED AS CLOSE AS PRACTICAL | | | TO REQUIRED VERTICAL LEADERS OR DOWN- | | | SPOUTS OR WALL OR PARAPET SCUPPERS. | | | 7) SHT P-7 WATER RISER DIAGRAMS, AIR | | | CHAMBERS ARE NOT APPROVED PER SECTION | | | 604.9. DELETE FROM RISER DIAGRAMS. | | | 8) SHT P-8 SANITARY PIPING COLLECTION | | | ISOMETRIC, FLOOR DRAINS IN EMPLOYEE AND | | | GUEST TOILET ROOMS ARE NOT VENTED. | | | CONNECT F.D.'S TO TOILET ROOM PIPING. | | | SECTION 901.2.1 | | | 9) THERMAL EXPANSION CONTROL IS REQUIRED | | | PER SECTION 607.3.2 | | | 10) SHT P-11 WATER RISER W/3, AN RPZ | | | BACKFLOW IS REQUIRED ON WATER LINE TO | | | TRASH CHUTE. SECTION 608.13.2 | | | 11) SHT P-12 STORM DRAIN PIPING, RWL/2 | | | 1620 SF - MAX 1600 SF @ 1/8" PER FT. | | | EITHER INCREASE PIPE SIZE OF SHOW 1/4" | | | PER FT. SLOPE ON PIPE. - RWL/3 6" SHOWS | | | 170 SF, BUT ADDS UP TO 1700 SF. PLEASE | | | CHANGE PLANS. | | | 12) SHT P-10.1 IDENTIFY RISER BETWEEN | | | S/4 & S/6. SHOW FU'S. - S/7 FU'S TO BE | | | A TOTAL OF 16. (SHOWS 10). ADD ONE LAV | | | AND TUB OR SHOWER TO EACH FLOOR. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2005-10-19 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2005-10-19 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-04-22 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2004-04-22 |
Time |
10:04 |
Rev Time |
0.25 |
| Received By |
ajones |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-04-22 00:00:00 | APPROVED WITH THE PROVISO THAT THE LETTE | | | R FROM JOE CROSSEN GRATNING PERMISSION T | | | O USE THE 10 FOOT EASEMENT FOR FIRE ACCE | | | SS IS RECEVIED PRIOR TO CO.ANY CHANGES | | | TO THE LANDSCAPE PLAN ON SITE REQUIRE A | | | NGELLA VANN'S APPROVAL. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2004-04-05 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-04-02 |
Time |
20:04 |
Rev Time |
0.25 |
| Received By |
ajones |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-04-05 00:00:00 | 1. NO LANDSCAPING PLAN IS PROVIDED | | | 2. UNITY TO TITLE NEEDED AS REQUIRED BY | | | ORD. | | | 3. 10 FOOT RESERVATION SHOWN ON PLAN HAS | | | NOT BEEN RESOLVED | | | 4. WAS DUMPSTER LOCATION APPROVED IN ORI | | | GINAL APPROVAL. |
|
|