| 2004-03-15 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT 2 COPIES OF SOIL BORING TEST |
| | REPORT AS REQUIRED BY FBC 1804.2.2. |
| | |
| | 4) THE REDLINED CHANGES TO THE WINDLOAD |
| | PRESSURES FOR THE GARAGE DOOR IN THE |
| | SCHEDULE ON A1, ARE REQUIRED TO BE |
| | SIGNED AND DATED BY THE DESIGNER OF |
| | RECORD. |
| | |
| | 5) SUBMIT THE MANUFACTURER'S SPECS. AND |
| | UL LISTING INFORMATION FOR THE ONE HOUR |
| | FIRE RATED GLASS BLOCK. |
| | |
| | 6) SUBMIT STATE OR LOCAL PRODUCT |
| | APPROVALS FOR THE FOLLOWING: |
| | - OUTSWING GLAZED DOOR (G) |
| | - STRUCTURAL WINDOW MULLIONS |
| | - ROOFING MATERIAL |
| | |
| | 7) CLARIFY ON SHEET A4 THAT THE 2" STR. |
| | MULLIONS SPECIFIED BETWEEN THE SGDS AND |
| | THE TRANSOM AND THE WINDOWS AND TRANSOMS |
| | IS THE 2X6 STEEL HEADER THAT IS DETAILED |
| | ON SHEET A8. IF THIS IS NOT THE CASE, |
| | SUBMIT PRODUCT APPROVAL FOR MULLIONS |
| | CAPABLE OF THE SPANS AND LOADS INDICATED |
| | |
| | 8)THE 112"X 96" FIXED WINDOW (M) EXCEEDS |
| | THE MAXIMUM SIZE IN THE PRODUCT APPROVAL |
| | THE LEFT ELEVATION SHOWS THREE PANELS IN |
| | THIS OPENING, WHICH WOULD BE ACCEPTABLE. |
| | PLEASE CLARIFY AND CHANGE SCHEDULE OR |
| | DRAWING AND SUBMIT APPROPRIATE PRODUCT |
| | APPROVAL. |
| | |