Plan Review Details - Permit 04020651
Plan Review Stops For Permit 04020651
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-04-20 Time 10:29 Rev Time 1.00
Received By dpalmer Date 2004-03-01 Time 09:12 Sent To  
Notes
2004-03-01 00:00:00*********** PROVISO/REVISION ******
  
 PLEASE SEE NOTES FROM FIRST REVIEW.
  
 1)NOTE: PLEASE SEE AHU-2, STILL SHOWS
 50A OCP FOR 10KW HEAT. PLEASE SEE 424.3B
  
 2)NOTE: PLEASE SEE A/C LOAD SHOWN ON
 LOAD CALCULATIONS, SHOWN AT 40%. PLEASE
 SEE NEC 220, CAN NOT USE 40% FOR TWO
 UNITS, ONLY FOUR OR MORE. MAX WOULD BE
 65%. 220.30C
  
 3)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULES.
 210.12B
  
 4)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2
 SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4.1.6.2
  
 5)NOTE: PLEASE SEE LOCAL AMENDMENTS,
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S INSIDE BUILDING. 230.70 AND 230.6
 NEC. 2" OF CONCRETE OR 18" BELOW BLDG.
  
 6)NOTE: KITCHEN SHOWS WHAT APPEARS TO BE
 A PENINSULAR? PLEASE SEE 210.52C, 210.8A
 -6.
  
 PLEASE REVISE PLANS ALONG WITH ANY OTHER
 CHANGES AND SUBMIT INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-17 Cont ID  
Sent By csiegber Date 2004-02-26 Time 17:05 Rev Time 1.50
Received By dpalmer Date 2004-02-17 Time 11:43 Sent To  
Notes
2004-02-17 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE 210.52D, 210.11C3
 FOR MIN #12 AWG AND 20A FOR BATH(S),
 POWDER ROOM.
  
 2)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU HEAT. PLEASE VERIFY KW RATING
 AT 10KW?
 PLEASE SEE LOAD CALCULATIONS. CALCS DO
 NOT INDICATE AHU/HEAT LOADS.
  
 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 PLEASE CLARIFY IF KITCHEN IS SHOWING
 WHAT APPEARS TO BE A PENINSULAR.?
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE ALSO SEE ANY ROOMS THAT MAY
 CONTAIN CLOSETS/ BATHS ARE CONSIDERED
 TO BE ADAPTABLE SLEEPING RMS.
 PLEASE SEE FIRST FLR DEN/PLAYROOM.
  
 5)NOTE: PLEASE SEE RISER DIAGRAM, SHOWS
 100A PANEL BEING FED FROM METER DIRECTLY
 TO 2ND FLOOR. PLEASE SEE 230.72 FOR
 GROUPING OF MAINS.
 IF PANEL "B" IS INDEED A SUB PANEL FROM
 PANEL "A", PLEASE INDICATE ON PANEL"A"'S
 PANEL SCHEDULE. OCP ETC.
  
 6)NOTEL PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250.50. COLD WATER AND FOOTER
 STEEL.
  
 7)NOTE:PLEASE SEE CU-2SHOWN ON PANEL
 SCHEDULE AS 1-P 15A ??? MISPRINT?
  
 8)NOTE: PLEASE SEE LOCAL AMENDMENTS,
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S(OCP) PERMITTED INSIDE BLDG.
 UNDER DWELLING IN CRAWL SPACE IS CONSID-
 -ERED INSIDE BLDG.
 A MEANS OF DISC AND OCP AT METER LOCAT-
 -ION.
  
 9)NOTE: PLEASE SEE 225.31 FOR MEANS OF
 DISC REQ'D AT DETACHED STRUCTURE.
 PLEASE ALSO SEE 250.32 IF MORE THAN ONE
 CIRCUIT. PLEASE SEE LOAD IS SHOWN WITH
 MORE THAN ONE CIRCUIT.
  
 10)NOTE: PLEASE LIST ALL CIRCUITS REQ'D
 WITH ARC FAULT PROTECTION ON PANEL
 SCHEDULE AND INDICATE AS SO. 210.12 OF
 THE 2002 NEC.
  
 11)NOTE: PLEASE SEE MASTER BEDROOM,
 PLANS DO NOT INDICATE GFI FOR JACUZZI
 AS SHOWN ON PANEL SCHEDULE.
  
 12)NOTE: PLEASE SEE MISSING RECEPT FOR
 2' OF WALL PER 210.52 MASTER BEDROOM.
  
 13)NOTE: PLEASE SEE PANEL"A", NOTES ON
 LOWER LEFTHAND CORNER AS BEING MLO? YET,
 TOP OF PANEL INDICATES MAIN BRKR?
 PLEASE CORRELATE AND SEE COMMENT #8.
  
 14)NOTE: PLEASE INCLUDE LICENSE # OF
 ARCH IN TITLE BLOCK. FAC 61G1-16.004
  
 15)NOTE: PLEASE INDICATE ALL GARAGE
 RECEPTS AS GFI/GFI PROTECTED.
 210.82/ ALSO SHED/STORAGE BLDG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-20 Cont ID  
Sent By csiegber Date 2004-04-20 Time 10:29 Rev Time 0.00
Received By csiegber Date 2004-04-20 Time 10:29 Sent To E
Notes
2004-04-20 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-02-26 Time 17:05 Rev Time 0.00
Received By csiegber Date 2004-02-26 Time 17:05 Sent To E
Notes
2004-02-26 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING