Plan Review Details - Permit 04020639
Plan Review Stops For Permit 04020639
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2007-01-29 Cont ID  
Sent By lmartine Date 2007-01-29 Time 11:19 Rev Time 0.00
Received By lmartine Date 2007-01-29 Time 11:19 Sent To  
Notes
2007-01-29 11:46:44REVISION FOR ADDED WINDOWS AND LAUNDRY CHUTE

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2006-08-23 Cont ID  
Sent By alange Date 2006-08-23 Time 14:07 Rev Time 0.75
Received By alange Date 2006-08-23 Time 10:48 Sent To E
Notes
2006-08-23 00:00:00REVISION DENIED
  
 1.ADJUST PERMIT VALUATION TO INCLUDE
 ALL ADDITION WORK.
  
 2.SCOPE OF WORK ON REVISION
 APPLICATION SPECIFIES WINDOWS, YET THE
 ENTIRE SECOND FLOOR HAS AN INTERIOR
 BUILD OUT.
  
 3.SUBMIT DETAILS FOR NEW LAUDRY CHUTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2006-08-11 Cont ID  
Sent By alange Date 2006-08-11 Time 15:37 Rev Time 0.00
Received By alange Date 2006-08-11 Time 15:37 Sent To  
Notes
2006-08-11 00:00:00RESTAMP PRODUCT APPROVALS AND DOCUMENTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2006-03-02 Cont ID  
Sent By alange Date 2006-03-02 Time 15:29 Rev Time 2.00
Received By alange Date 2006-03-02 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2006-01-25 Cont ID  
Sent By alange Date 2006-01-25 Time 11:20 Rev Time 1.75
Received By alange Date 2006-01-25 Time 09:11 Sent To  
Notes
2006-01-25 00:00:00REVISION DENIED
  
 1.REVISION SUBMITTED SHALL BE SIGNED
 AND SEALED BY GINOCCIO AND SPINA
 ARCHITECTS OF RECORD.OR SUBMIT A
 RELEASE FROM THEM TO THE NEW DESIGNER.
 NOTE; STEVE GINOCCHIO'S OFFICE WAS
 CONTACTED AND A RELEASE LETTER WAS
 REQUESTED ON 1-25-06
  
 2.DESIGNER OF RECORD SHALL SIGN ALL
 PAGES.
  
 5.TWO COMPLETE SETS OF PRODUCT
 APPROVALS REQUIRED.
  
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2006-01-05 Cont ID  
Sent By alange Date 2006-01-05 Time 13:04 Rev Time 0.00
Received By alange Date 2006-01-05 Time 09:11 Sent To  
Notes
2006-01-05 00:00:00DENIED
  
 PLANS SUBMITTED FOR RESTAMPING SHALL BE
 SIGNED AND SEALED BY THE DESIGNER OF
 RECORD.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2005-11-18 Cont ID  
Sent By alange Date 2005-11-18 Time 09:27 Rev Time 2.00
Received By alange Date 2005-11-17 Time 16:36 Sent To Z
Notes
2005-11-18 00:00:00REVISION DENIED
  
 1.REVISION SUBMITTED SHALL BE SIGNED
 AND SEALED BY GINOCCIO AND SPINA
 ARCHITECTS OF RECORD.OR SUBMIT A
 RELEASE FROM THEM TO THE NEW DESIGNER.
  
 2.DESIGNER OF RECORD SHALL SIGN ALL
 PAGES.
  
 3.INCREASED SQUARE FOOTAGE ON PLANS,
 PLEASE HAVE PLANS STAMPED FOR POSSIBLE
 IMPACT FEES.
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.ORIGONAL PERMITTED PLANS ARE
 DESIGNED UNDER THE 2001 FBC.THE
 REVISIONS SUBMITTED SHALL ALSO BE
 DESIGNED TO THE SAME CODE.
  
 5.SUBMIT PRODUCT APPROVALS FOR THE
 FOLLOWING; CASEMENT WINDOWS, LINTELS AND
 STRAPS AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.CORRECT SHEATHING TYPO OF 9/32"
  
 7.SHOW SIZE OF ATTIC ACCESS 2001 FBC
 2309.6
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-08-12 Cont ID  
Sent By alange Date 2005-08-12 Time 13:06 Rev Time 0.00
Received By alange Date 2005-08-12 Time 13:06 Sent To  
Notes
2005-08-12 00:00:00REVISION DENIED
  
 1.REVISION SUBMITTED SHALL BE SIGNED
 AND SEALED BY GINOCCIO AND SPINA
 ARCHITECTS OF RECORD.
  
 2.REVISION SUBMITTED DOES NOT CLEARLY
 SHOW WHAT IS BEING CHANGED.PLEASE
 SHOW ON REVISION APPLICATION AND ON
 PLANS WHAT THE CHANGES ARE.
  
 FOR EXAMPLE:ARE YOU ELIMINATING ALL
 VERTICAL REINFORCMENT, CHANGING WINDOWS
 AND DOORS, MOVING PLUMBING, ADDING
 COVEREDENTRY TO GARAGE.
 ADDITIONAL INFORMATION WILL BE NEEDED.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-10-21 Cont ID  
Sent By alange Date 2004-10-21 Time 13:47 Rev Time 1.00
Received By alange Date 2004-10-21 Time 13:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-15 Cont ID  
Sent By pkrauss Date 2004-10-21 Time 09:01 Rev Time 2.25
Received By alange Date 2004-03-15 Time 14:20 Sent To  
Notes
2004-03-15 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSEAND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.FBC 1005.4 SLEEPING ROOM EGRESS
 REQUIREMENTS. SHOW LOCATION OF EXISTING
 BEDROOMS ON NORTH SIDE OF EXISTING
 BUILDING AND LOCATIONS OF EGRESS WINDOWS
  
 4.SHOW ON SITE PLAN LOCATION OF ANY
 BUILDINGS NORTH OF ROOM ADDITION SO
 THATTABLE 600 OF THE FBC CAN BE CHECKED.
  
 5.VERIFY THAT THE NEW AND EXISTING
 STRUCTURES ARE 6 INCHES ABOVE THE BASE
 FLOOD ELEVATION.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-13 Cont ID  
Sent By pkrauss Date 2004-03-02 Time 11:21 Rev Time 0.00
Received By mmclean Date 2004-02-13 Time 15:40 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 08:31 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 07:19 Sent To M
Notes
2006-02-22 00:00:00********** UNSAT ***********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES FOR ITEMS ON
 PLANS.
  
 1)NOTE:OK.
  
 2)NOTE: OK, GENERATOR REMOVED,HOWEVER
 LOAD CALCULATION OF SOME SORT SHOWN ON
 RISER WHICH IS UNCLEAR HOW THIS IS
 INCORPORATED INTO PLANS? 215.5
  
  
 3)NOTE: OK, HOWEVER PLEASE SEE ALMOST
 ALL BRANCH CIRCUITS IN PANEL INDICATE
 ARC FAULT PROTECTION?? PLEASE SEE BATH
 CIRCUITS? ETC. THE ONLY AREAS WHICH
 REQUIRE ARC FAULT IS BEDRM(S).
  
 4)NOTE: OK.
  
 5)NOTE:OK, HOWEVER, PLEASE SEE NO NEW
 DINING RM CIRCUITS ARE ON PANEL
 SCHEDULE? THERE IS HOWEVER TWO SMALL
 APPLIANCE CIRCUITS? ARE THESE THE
 "DINING RM CIRCUITS"?
  
 **PLEASE SEE NEW DINING AREA CALLS
 FOR DEDICATED DINING BRANCH CIRCUITS AS
 REQUIRED UNDER 210.52B1, 210.11,220.16
 MUIST BE 20A AND #12.
  
 6)NOTE: NO, PLEASE SEE NOW LOAD
 CALCULATIONS INDICATE TWO LOADS FOR
 DRYERS AT 5KW, HOWEVER PANEL SCHEDULE
 ONLY INDICATES A 1-POLE 20A OCP FOR THIS
 ON THE STACKABLE UNIT? PLEASE SEE #10
 AWG IS SHOWN.
 PLEASE ALSO SEE LOAD CALCULATIONS FOR
 SERVICE DO NOT CORRELATE WITH THIS??
 PLEASE SEE LOAD CALCULATION COMMENT
 BELOW.
  
 ** PLEASE SEE PLANS CALL FOR A NEW
 WASHER AND DRYER LOCATE DON 1ST FLR AND
 ALSO A NEW STACKABLE UNIT ON 2ND FLR,
 HOWEVER PANEL SCHEDULE ONLY INDICATES
 ONE DRYER? GAS?
  
 **PLEASE SEE 220.16, 210.11C WHICH
 REQUIRES A MIN OF 1.5KW FOR LAUNDRY
 CIRCUIT, WASHER,ETC.
 PLEASE SEE 220.18 FOR A MIN OF 5KW TO BE
 FIGURED FOR DRYER(S).
 PLEASE ALSO NOTE OF EXISTING IN MAIN
 HOUSE ARE BEING REMOVED OR RELOCATED.
 PLEASE ADJUST LOAD CALCULATIONS AND
 CORRELATE.
 215.5,
  
 7)NOTE: NO, PLEASE SEE NOTES ABOVE AND
 PLEASE SEE LOAD CALCS.
 PLEASE ALSO INDICATE WHAT THW % FOR AHU
 HEAT LOADS.PLEASE SEE LOAD CALC AS
 NOTED ON FUTURE GEN PANEL SHOWS AHU AT
 10KW, LOAD ON PANEL "C" SHOWS 5.5KW,
 WHERE AND WHAT OTHER A/C HEAT LOADS ARE
 THERE?
  
 ** PLEASE SEE ALL LOAD CALCULATIONS
 SHALL BE FIGURED PER 220.31B FOR
 ADDITONS TO EXISITING DWELLINGS.
  
 8)NOTE: NO, PLEASE KNOW, PLANS WERE GONE
 OVER IN LOBBY IN A BRIEF REVIEW OF
 NOTES, AND IT WAS MENTIONED TO
 CONTRACTOR THAT THE "EQUIPMENT GROUNDING
 CONDUCTORS" WERE STILL BEING SHOWN,
 HOWEVER NOW PLANS HAVE COME BACK WITH
 WHITE-OUT ON RISER REMOVING ALL SEC'S???
 PLEASE SHOW THE CORRECT SEC'S FROM
 GUTTER TO EACH MAIN.
  
 ** PLEASE SEE SEC'S TO MAIN GUTTER
 INDICATE SERVICE AS A 3-PHASE SERVICE??
 PLEASE ALSO SEE AN "EQUIPMENT GROUNDING
 CONDUCTOR" IS STILL BEING SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24 WHICH ONLY
 PERMITS THE EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 9)NOTE: OK, PLEASE RE-PRINT WITH OUT
 WHITE-OUT.
  
 ** PLEASE SEE 310.15B6, 250.66 FOR
 THE MIN SIZE FOR THE GROUNDING ELECTRODE
 CONDUCTOR. 1/0 MIN.
 THIS SHALL ALSO INCLUDE ATTACHEMENT TO
 THE NEW FOOTER STEEL AS REQUIRED PER
 250.50
  
 10)NOTE:OK
  
 11)NOTE:OK.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-01-18 Cont ID  
Sent By dpalmer Date 2006-01-18 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2006-01-18 Time 09:16 Sent To M
Notes
2006-01-18 00:00:00*********** UNSAT ***********
  
 ** PLEASE SEE THE FOLLOWING COMMENTS AS
 THERE HAVE BEEN MANY CHANGES TO PLANS .
  
  
 1)NOTE: PLEASE COMPLETE ALL INFORMATION
 ON ALL TITLE BLOCKS ON SAID PLANS PER
 FLORIDA ADMIN CODE. 61G1-16.004.
 PLEASE SEE FBC 104.2.1 WHICH REQUIRES
 ALL PLANS TO CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR SAID PLANS/DESIGN. PLEASE KNOW, ALL
 PLANS WOULD ALSO BE REQUIRED TO BE
 SIGNED, DATED AND SEALED BY ANY
 ARCHITECT'S RESPONSIBLE FOR DESIGN.
 FS 481.221
 PLEASE SEE OTHER SHEETS APPEAR TO BE
 SIGNED WITH "INITIALS"? IF INDEED THIS
 IS THE LEGAL SIGNATURE OF THE ARCHITECT,
 PLEASE PROVIDE AND SIGNED, DATED AND
 SEALED LETTER WITH REFERENCE TO THE
 LEGAL SIGNATURE.( PLEASE BE SURE LTR IS
 CORRECTLY NOTORIZED UNDER FS 117.05).
  
 ** PLEASE KNOW, THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT(S) ARE MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE SEE RISER NOW INDICATES A
 NEW GENERATOR/ ATS ETC. PLEASE KNOW, A
 SEPARATE PERMIT IS REQUIRED FOR THE GEN
 ETC AND MUST SUBMIT PLANS, PERMIT APPL,
 SPECS, SURVEY ETC.
 PLEASE SEE ALL OF 225.31-225.39 FOR
 DISCONNECTING MEANS OF FEEDERS COMING
 FROM GEN, GROUPING WITH EXISTING, RATED
 FOR THE LOAD SERVED, SERVICE RATED ETC.
 PLEASE BEAR IN MIND, PLANS MAY NOT
 INCLUDE GENERATOR UNTIL SUCH TIME GEN
 PERMIT IS ISSUED.
  
  
 3)NOTE: PLEASE SEE ORIGINAL PLANS WERE
 REDLINED FOR 2002 NEC 210.12 WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 "OUTLETS" IN BEDRM AREAS. PLEASE SEE
 DOWNSTAIRS IS NOW CHANGED TO A DINING
 AREA AND UPSTAIRS IS NOTED AS FUTURE
 BEDRM.
 PLEASE IST THE REQUIRED ARC FAULT FOR
 ALL, SD'S, LTS, FANS, RECEPTS ETC.
 PLEASE LIST THESE REQUIRED CIRCUITS ON
 PANEL SCHEDULE.
  
 4)NOTE: RISER CALLS FOR A NEW PANEL "C",
 HOWEVER THIS PANEL COULD NOT BE LOCATED
 ON PLANS.
 215.5, 240.24, 408.7,110.26 ETC
  
 5)NOTE: PLEASE SEE NEW DINING AREA CALLS
 FOR DEDICATED DINING BRANCH CIRCUITS AS
 REQUIRED UNDER 210.52B1, 210.11,220.16
 MUIST BE 20A AND #12.
  
 6)NOTE: PLEASE SEE PLANS CALL FOR A NEW
 WASHER AND DRYER LOCATE DON 1ST FLR AND
 ALSO A NEW STACKABLE UNIT ON 2ND FLR,
 HOWEVER PANEL SCHEDULE ONLY INDICATES
 ONE DRYER?
 PLEASE SEE 220.16, 210.11C WHICH
 REQUIRES A MIN OF 1.5KW FOR LAUNDRY
 CIRCUIT, WASHER,ETC.
 PLEASE SEE 220.18 FOR A MIN OF 5KW TO BE
 FIGURED FOR DRYER(S).
 PLEASE ALSO NOTE OF EXISTING IN MAIN
 HOUSE ARE BEING REMOVED OR RELOCATED.
 PLEASE ADJUST LOAD CALCULATIONS AND
 CORRELATE.
 215.5,
  
 7)NOTE: PLEASE SEE ALL LOAD CALCULATIONS
 SHALL BE FIGURED PER 220.31B FOR
 ADDITONS TO EXISITING DWELLINGS.
  
 8)NOTE: PLEASE SEE SEC'S TO MAIN GUTTER
 INDICATE SERVICE AS A 3-PHASE SERVICE??
 PLEASE ALSO SEE AN "EQUIPMENT GROUNDING
 CONDUCTOR" IS STILL BEING SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24 WHICH ONLY
 PERMITS THE EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 9)NOTE: PLEASE SEE 310.15B6, 250.66 FOR
 THE MIN SIZE FOR THE GROUNDING ELECTRODE
 CONDUCTOR. 1/0 MIN.
 THIS SHALL ALSO INCLUDE ATTACHEMENT TO
 THE NEW FOOTER STEEL AS REQUIRED PER
 250.50
  
 10)NOTE: PLEASE SEE 210.8A2 FOR ALL
 RECEPTS LOCATED IN GARAGE SHALL BE SHOWN
 AS GFI/.
  
 11)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPT SPACING AS REQUIRED.
 PLEASE SEE PLANS HAVE BEEN REDLINED AT
 LOCATIONS.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 19:37 Rev Time 0.33
Received By dpalmer Date 2004-10-06 Time 19:29 Sent To P
Notes
2004-10-06 00:00:00*** PLEASE SEE ALL NEW ELECTRICAL SHEETS
 SUBMITTED.
  
 ** PLANS REDLINED ***
  
 1)NOTE: PLEASE SEE RISER STILL SHOWS
 EQUIPMENT GROUNDING CONDUCTORS FROM
 METER TO GUTTER AND GUTTER TO EACH MAIN
 DISC??
 EQUIPMENT GROUNDING IS ONLY INSTALL
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24.
  
 2)NOTE: CABANA REQUIRED TO HAVE SD
 WIRED IN-LINE WITH OTHERS.
  
 3)NOTE: PLEASE SEE CABANA ALSO REQUIRED
 TO HAVE ARC-FAULT PROTECTION FOR RECEPTS
 ,SD'S AND LTS. 210.12 2002 NEC.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-07-28 Cont ID  
Sent By alange Date 2004-10-06 Time 14:30 Rev Time 0.50
Received By dpalmer Date 2004-07-28 Time 13:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-24 Cont ID  
Sent By dpalmer Date 2004-02-24 Time 07:02 Rev Time 0.75
Received By dpalmer Date 2004-02-24 Time 07:02 Sent To P
Notes
2004-02-24 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SEE RISER, RISER NOW
 SHOWS REMOVING FEED FROM METER TO BOTH
 PANELS, YET NO NEW FEED IS SHOWNTO
 GUTTER? PLEASE INDICATE , CONDUITS,AWG
 ETC. 215.5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5 NEW MAIN.
  
 3)NOTE: : PLEASE SEE 250.24, AN EQUIP-
 -MENT GROUNDING CONDUCTOR IS ONLY
 INSTALLED AFTER THE FIRST MEANS OF DISC-
 -ONNECT.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 5)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 6))NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12
  
 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 8)NOTE: PLEASE CLARIFY SECOND A/C COND
 UNIT SHOWN. IS THIS FOR AN EXISTING
 SYSTEM ON MAIN HOUSE?
 PLEASE SEE PANEL SCHEDULE, SHOWS A
 SECOND A/C SYSTEM,BOTH AS 1-POLE
 CIRCUITS, 15A OCP AND #14 AWG??
  
 9) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2006-12-20 Cont ID  
Sent By adarroug Date 2006-12-20 Time 11:50 Rev Time 0.00
Received By adarroug Date 2006-12-20 Time 11:50 Sent To M
Notes
2006-12-20 11:50:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 13:23 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 13:23 Sent To P
Notes
2006-12-17 13:24:08TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 09:18 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 09:18 Sent To E
Notes
2006-09-29 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 15:16 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 15:16 Sent To B
Notes
2006-08-18 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 12:06 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 12:06 Sent To B
Notes
2006-08-03 00:00:00TO "ALANGE" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 15:30 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 15:30 Sent To P
Notes
2006-06-22 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2006-02-19 Cont ID  
Sent By adarroug Date 2006-02-19 Time 10:45 Rev Time 0.00
Received By adarroug Date 2006-02-19 Time 10:45 Sent To E
Notes
2006-02-19 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 15:40 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 15:40 Sent To Z
Notes
2006-02-13 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-01-12 Cont ID  
Sent By adarroug Date 2006-01-12 Time 14:07 Rev Time 0.00
Received By adarroug Date 2006-01-12 Time 14:07 Sent To E
Notes
2006-01-12 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-12-30 Cont ID  
Sent By adarroug Date 2005-12-30 Time 16:01 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 16:01 Sent To Z
Notes
2005-12-30 00:00:00TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-12-30 Cont ID  
Sent By adarroug Date 2005-12-30 Time 11:15 Rev Time 0.00
Received By adarroug Date 2005-12-30 Time 11:15 Sent To B
Notes
2005-12-30 00:00:00TO "ALANGE" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-11-22 Cont ID  
Sent By adarroug Date 2005-11-22 Time 09:25 Rev Time 0.00
Received By adarroug Date 2005-11-22 Time 09:25 Sent To B
Notes
2005-11-22 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 17:42 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 17:42 Sent To B
Notes
2005-11-15 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-08-09 Cont ID  
Sent By adarroug Date 2005-08-09 Time 11:48 Rev Time 0.00
Received By adarroug Date 2005-08-09 Time 11:48 Sent To B
Notes
2005-08-09 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-06 Cont ID  
Sent By alange Date 2004-10-06 Time 14:30 Rev Time 0.00
Received By alange Date 2004-10-06 Time 14:30 Sent To E
Notes
2004-10-06 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-09-17 Cont ID  
Sent By csiegber Date 2004-09-17 Time 09:03 Rev Time 0.00
Received By csiegber Date 2004-09-17 Time 09:03 Sent To B
Notes
2004-09-17 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-09-14 Cont ID  
Sent By mmclean Date 2004-09-16 Time 10:23 Rev Time 0.00
Received By csiegber Date 2004-09-14 Time 15:50 Sent To Z
Notes
2004-09-14 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-02 Cont ID  
Sent By mmclean Date 2004-02-13 Time 15:44 Rev Time 0.00
Received By csiegber Date 2004-02-13 Time 11:39 Sent To  
Notes
2004-02-17 00:00:00TO SFD RACK/E
2004-02-13 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-12-28 Cont ID  
Sent By pkrauss Date 2006-12-28 Time 07:27 Rev Time 0.00
Received By pkrauss Date 2006-12-28 Time 07:27 Sent To  
Notes
2006-12-28 07:30:37REVISION TO MASTER BEDROOM, & 1ST FLOOR AHU#1.PLEASE
 NOTE, THE ORIGINAL APPROVED SET OF PLANS WERE NOT IN
 THE CITY'S FILE.A CHECKOUT CARD WAS NOT FILLED OUT
 IDENTIFYING WHO CHECKED THE PLANS OUT.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-22 Cont ID  
Sent By tgordon Date 2006-02-22 Time 10:50 Rev Time 0.25
Received By tgordon Date 2006-02-22 Time 10:50 Sent To P
Notes
2006-02-22 00:00:00REV. TO MECH. PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-01-23 Cont ID  
Sent By tgordon Date 2006-01-23 Time 08:55 Rev Time 0.30
Received By tgordon Date 2006-01-23 Time 08:55 Sent To P
Notes
2006-01-23 00:00:00*** DENIED ***
 1) NEED TO SUBMIT TWO COPYS OF THE
 ENERGY CALCULATIONS.
  
 2) NEED NAME OF THE PREPARER ON THE
 ENERGY CALCULATIONS.
  
 3) NO RETURN AIR IS PROVIDED FOR ON
 MECH. PLANS, SEE NOTE #3.
  
 4)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 5) CLOTHES DRYER EXHAUST NOT SHOWING ON
 MECH. PLANS, NOTE EXHAUST TERMINATION
 MUST BE 4 FEET FROM A/C CONDENSER UNIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-10-21 Cont ID  
Sent By kstevens Date 2004-10-13 Time 17:58 Rev Time 0.30
Received By pkrauss Date 2004-10-21 Time 08:39 Sent To B
Notes
2004-10-21 00:00:00PROVISO:
 PLAN 6 OF 7 INDICATES AN OVERFLOW PAN
 BUT DOES NOT INDICATE SECONDARY DRAIN
 LINE OR FLOAT SWITCH.PER 2001 FBC(M)
 307.2.3, A SECONDARY DRAIN LINE SHALL
 TERMINATE A CONSPICUOUS POINT TO SERVE
 AS AN ALARM THAT THE PRIMARY DRAIN IS
 RESTRICTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-03-02 Cont ID  
Sent By kstevens Date 2004-02-26 Time 17:43 Rev Time 0.35
Received By pkrauss Date 2004-03-02 Time 10:40 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-01-06 Cont ID  
Sent By jleech Date 2007-01-06 Time 10:42 Rev Time 0.00
Received By jleech Date 2007-01-06 Time 10:42 Sent To B
Notes
2007-01-06 10:43:22REVISED PLUMBING RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 11:00 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 11:00 Sent To  
Notes
2006-07-08 00:00:00REVISION; REVISED SANITARY RISER DIAGRAM

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-03-01 Cont ID  
Sent By jleech Date 2006-03-01 Time 14:02 Rev Time 0.50
Received By jleech Date 2006-03-01 Time 13:54 Sent To B
Notes
2006-03-01 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM IS NOT TO CODE.
 A)AUTOMATIC CLOTHES WASHER IS NOT
 VENTED, AND A CLEANOUT IS REQUIRED TO BE
 48" ABOVE FINISH FLOOR.
 B)HORIZONTAL DRY VENTS ARE NOT
 PERMITED. SEC.905.3
 C)AUTO MATIC CLOTHES WASHER AND
 LOUNDRY TUB MUST DISCHARGE DOWN STREAM
 OF THE BATHROOM GROUP. SEC.909.1.
 D) LAV. IS NOT VENTED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-01-23 Cont ID  
Sent By jleech Date 2006-01-23 Time 12:06 Rev Time 0.50
Received By jleech Date 2006-01-23 Time 12:06 Sent To B
Notes
2006-01-23 00:00:00DENIED;
 1. NOT ENOUGH INFORMATION TO DO A
 PLUMBING PLAN REVIEW. PLEASE PROVIDE A
 PLUMBING SANITARY RISER DIAGRAM. SHOW
 ALL DRAINAGE A VENT PIPING AND SIZE.
 SEE ELECTRICAL PLAN REVIEWERS COMMENTS
 ABOUT TITLE BLOCK INFORMATION MISSING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-10-13 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 19:37 Rev Time 0.33
Received By kstevens Date 2004-10-13 Time 17:58 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-26 Cont ID  
Sent By dpalmer Date 2004-02-24 Time 07:03 Rev Time 0.50
Received By kstevens Date 2004-02-26 Time 17:42 Sent To M
Notes
2004-02-26 00:00:00PASSED/PROVISO
  
 NO HORIZONTAL DRY VENTS - 905.3

Review Stop Z ZONING
Rev No 5 Status P Date 2006-02-17 Cont ID  
Sent By mmclean Date 2006-02-17 Time 08:29 Rev Time 0.00
Received By mmclean Date 2006-02-17 Time 08:29 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2006-01-11 Cont ID  
Sent By mmclean Date 2006-01-11 Time 17:21 Rev Time 0.00
Received By mmclean Date 2006-01-11 Time 17:21 Sent To I
Notes
2006-01-11 00:00:00DENIED,
 1. MUST SUBMIT THE TWO COPY OF SURVEY
 SHOWING THE PROPOSED ADDITION (SURVEY
 NOT ENCLOSED).
 2. NEED EXPLAINATION TO WHAT IS EX. REF(
 A-1)? A SECOND REF CAN ONLY BE AN U/C
 REF.(MUST SHOW ON PLANS AS A U/C REF).
 OLD PLANS SHOWS STAIRS AND THIS IS A NEW
 PROPOSED 2 STORY STRUCTURE.
 3. PLEASE EXPLAIN FIREPLACE? ON A-1 EX.
 FAMILY ROOM.
 4. 2ND FLOOR PLANS (A-1) SHOWS WHAT
 LOOKS LIKE AN ACESS, PLEASE CLARIFY.
 5. A-1 SECOND FLOORS 3 S-4 SHOWS A SOLID
 WALL, PLEASE CLARIFY?
 6. THE PROPOSED 2ND STORY CAN ONLY BE A
 MAXIMUM OF 30FT HIGH.PLANS SHOWS
 34/35+ FEET HIGH.IF CHIMENY TO BE
 ADDED (WITH PLANS SHOWING) THE HEIGHT
 CAN BE 33FT (30 + 10%) = 33FT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 3 Status F Date 2005-11-21 Cont ID  
Sent By mmclean Date 2005-11-21 Time 16:47 Rev Time 0.00
Received By mmclean Date 2005-11-21 Time 16:22 Sent To I
Notes
2005-11-21 00:00:00DENIED, - REVISION
 1. PLEASE EXPLAIN THE CHANGES TO THE OLD
 PLANS OF EXISTING STAIRS TO REVISION OF
 NEW SHOWING EXISTING REF.
 2. PLEASE SHOW HOW THE 2ND FLOOR WILL BE
 ACCESS FROM FIRST FLOOR.
 3. PLEASE PROVIDE CHIMNEY DETAIL FROM
 THE OLD PLANS TO NEW PLANS.
 4. DOOR IN DINNING AREA, WHERE DOES IT
 LEAD TO.
 5. EXPLAIN THE 2ND STORY HOLD?
 6. PLEASE PROVIDE NEW MEAN ROOF HEIGHT.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status P Date 2004-09-16 Cont ID  
Sent By mmclean Date 2004-09-16 Time 10:23 Rev Time 0.00
Received By mmclean Date 2004-09-16 Time 10:23 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-02-13 Cont ID  
Sent By csiegber Date 2004-09-14 Time 15:50 Rev Time 0.00
Received By mmclean Date 2004-02-13 Time 15:44 Sent To I
Notes
2004-02-13 00:00:00DENIED, NEED TO REMOVE MICRO IN SECOND
 STORY ADDITION CALLED CONTR (NO COOKING
 FACILITY ALLOWED SF7)