Plan Review Details - Permit 04020587
Plan Review Stops For Permit 04020587
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-06-24 Cont ID  
Sent By jwitmer Date 2004-06-24 Time 10:02 Rev Time 0.33
Received By jwitmer Date 2004-06-24 Time 10:02 Sent To PC
Notes
2004-06-24 00:00:00RESTAMP PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-06-22 Time 14:57 Rev Time 0.50
Received By jwitmer Date 2004-04-05 Time 12:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-06 Cont ID  
Sent By jwitmer Date 2004-03-06 Time 16:35 Rev Time 0.50
Received By jwitmer Date 2004-03-06 Time 16:35 Sent To  
Notes
2004-03-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020587
 ADD: 8901 OKEECHOBEE BLVD
 CONT: KOLTER SIGNATURE HOMES
 TEL: (561)441-5358
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIW
 ACTION: DENIED
  
 1)11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE. MISSING BOTTOM LANDING.
  
 2)11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60". THE 60" DIMEN-
 SION ON THE PLAN IS TO THE EDGE OF THE
 RAMP, NOT THE INSIDE TURNING RADIUS.
 INDICATE TURNING RADIUS FOR THE UPPER
 LANDING, 60" CLEAR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 18:14 Rev Time 0.75
Received By btrobaug Date 2004-04-06 Time 18:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-03-05 Cont ID  
Sent By dpalmer Date 2004-03-05 Time 06:09 Rev Time 0.33
Received By dpalmer Date 2004-03-05 Time 06:08 Sent To  
Notes
2004-03-05 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 A COMPLETE SIGNATURE AS REQ'D UNDER FS
 471.025, 481.221
  
 2)NOTE: PLEASE SEE 250.24, NO EQIPMENT
 GROUNDING CONDUCTOR INSTALLED FROM
 METER TO FIRST MEANS OF DISC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-22 Cont ID  
Sent By csiegber Date 2004-06-22 Time 14:57 Rev Time 0.00
Received By csiegber Date 2004-06-22 Time 14:57 Sent To B
Notes
2004-06-22 00:00:00TO JW DESK/RE-STAMP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-25 Cont ID  
Sent By csiegber Date 2004-03-25 Time 14:30 Rev Time 0.00
Received By csiegber Date 2004-03-25 Time 14:30 Sent To  
Notes
2004-03-25 00:00:00TO COMM BD#58

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-03 Cont ID  
Sent By csiegber Date 2004-03-03 Time 10:08 Rev Time 0.00
Received By csiegber Date 2004-03-03 Time 10:08 Sent To  
Notes
2004-03-03 00:00:00TO COMM BD#41

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 14:58 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 14:58 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-03-02 Cont ID  
Sent By csiegber Date 2004-02-12 Time 14:58 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***