| Plan Review Stops For Permit 04020434 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
F |
Date |
2005-05-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-19 |
Time |
14:12 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-05-19 |
Time |
14:12 |
Sent To |
Z |
|
| Notes |
| 2005-05-19 00:00:00 | ****CORRECTIONS**** | | | REVISION, ES1 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)PLEASE RESUBMIT WITH CALCS. | | | | | | 2.)SUBJECT TO ZONING APPROVAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2005-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-16 |
Time |
16:29 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-05-16 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2005-05-16 00:00:00 | DOOR/HARDWARE SUBMITTAL, PROVISO IN | | | ACCORDANCE WITH FBC AND APPROVED PLAN |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2005-05-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-16 |
Time |
10:53 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-05-16 |
Time |
10:53 |
Sent To |
PC |
|
| Notes |
| 2005-05-16 00:00:00 | ****CORRECTIONS**** | | | SITE LIGHTING SHOP SUBMITTALS | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED AND SEALED, FAC61G15-23.002.THE | | | PRINTED NAME AND LICENSE NUMBER OF THE | | | INDIVIDUAL SEALING THE DOCUMENT IS TO BE | | | ON THE PLAN (COVER LETTER FROM TSENG). | | | | | | 2.)THE CALCS PREPARED BY HARDY | | | ENGINEERING (PAGE 6) NEED A TITLE BLOCK | | | IN COMPLIANCE WITH FAC61G15-23.002. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2005-02-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-19 |
Time |
14:16 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-02-24 |
Time |
09:40 |
Sent To |
PC |
|
| Notes |
| 2005-02-24 00:00:00 | 02-25-05 BLDG #1 SUBMITTALS: | | | SOIL PRE-TREATMENT | | | CONCRETE MIX DESIGN | | | ALTERNATE CONCRETE MIX DESIGN | | | NON SHRINKING HS GROUT | | | FORM RELEASE | | | BONDING AGENT | | | STUCCO & ACCESSORIES | | | EXTERIOR CAULKING | | | STEEL COLUMNS | | | INSULATION | | | EXT WALL SHEATHING | | | TRUSS ANCHORS | | | CONSTRUCTION & SUB FLOOR ADHESIVE | | | TUNNEL TIES | | | ROOFING MATERIALS | | | TRUSS SHOP DRAWINGS | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2004-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-11-22 |
Time |
09:07 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-02-24 |
Time |
09:37 |
Sent To |
PC |
|
| Notes |
| 2004-11-22 00:00:00 | 11-22-04 EXTERIOR METAL FRAMING SHOP | | | DRAWINGS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2004-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-11-22 |
Time |
08:20 |
Rev Time |
0.25 |
| Received By |
jwitmer |
Date |
2004-11-22 |
Time |
08:20 |
Sent To |
|
|
| Notes |
| 2004-11-22 00:00:00 | 11-22-04 SUBMITTALS, PRODUCT APPROVALS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-05-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-23 |
Time |
14:30 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2004-05-19 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2004-05-19 00:00:00 | RELOCATION OF GAZEBO |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2004-05-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-05-10 |
Time |
12:32 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2004-05-10 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2004-05-10 00:00:00 | REVISION MOVE GAZEBO TO NEXT TOO TOT LOT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-03-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-28 |
Time |
14:17 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2004-03-17 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2004-03-17 00:00:00 | 04020434 SHALL BE MASTER PERMIT FOR | | | TYPE 2A BUILDINGS!!!!!!!JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2004-03-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-03-05 |
Time |
16:27 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2004-03-05 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2004-03-05 00:00:00 | PERMIT# 04020434 | | | 800 MALIBU BAY DR | | | BLD#1 | | | TYPE II-A | | | ACTION DENIED | | | | | | MISSING PRODUCT TESTING REPORT | | | A) FRENCH DOORS 45 MIN | | | B) SLIDING GLASS DOORS 45 MIN | | | C) LOUVER 45 MIN | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-02-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-12 |
Time |
15:03 |
Rev Time |
3.00 |
| Received By |
jwitmer |
Date |
2004-02-25 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2004-02-25 00:00:00 | BUILDING PLAN REVIEW TYPE- II-A BLD | | | PERMIT: 04020434BLD#1 | | | ADD: 800 MALIBU BAY DR | | | | | | PERMIT: 04020443BLD# 3 | | | ADD: 780 MALIBU BAY DR | | | | | | PERMIT:04020444BLD# 4 | | | ADD: 770 MALIBU BAY DR | | | | | | PERMIT: 04020445BLD# 5 | | | ADD: 760 MALIBU BAY DR | | | | | | PERMIT: 04020452BLD# 10 | | | ADD: 740 MALIBU BAY DR | | | | | | PERMIT: 04020454BLD# 11 | | | ADD: 730 MALIBU BAY DR | | | | | | CONT: MILLENNIUM GENERAL CONTRACTOR | | | TEL: (305)218-7895 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | PERMIT APP/ 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PROVIDE A COPY OF THE VARIANCE RE- | | | QUIRED FOR 1014.1.1 BALCONIES, PORCHES | | | AND GALLERIES, AN APPROVED BY THE BOARD | | | OF ADJUSTMENT & APPEAL. | | | | | | 2) THIS COMMENT APLLIES ONLY TO BLD# 1. | | | ALTHOUGH THIS BUILDING SETS OVER THE | | | 15' FROM THE PROPERTY LINE SATISFYING | | | 705.1.1.2, CLASSIFYING THE BUILD, TYPE | | | VI 1 HR PROTECTED TABLE 600 FOR WALLS | | | LOCATED 10'-20' FROM PROPERTY LINE, | | | OPENING PROTECTIVES REQUIRED 45 MIN FOR | | | OPENINGS < 40% WALL AREA. | | | | | | 3) BUILDINGS 4 & 5 WILL HAVE THE SAME | | | ISSUE BECAUSE OF THE LOCATION OF THE | | | GAZEBO.TABLE 600 ASSUMED PROPERTY LINES! | | | | | | 4) NOTE THE FIRE RATED TEST REPORT FROM | | | D. V. FRYE-TEC FOR HORIZONTAL SLIDING | | | WINDOWS WITH A LIMITATION OF 670 SQ IN | | | PER FRAME. THE MAXIMUM GLASS LIGHT WIDTH | | | OF 32"AND HEIGHT OF 42".NOTE 32X42=1344. | | | | | | 5) PLEASE INDICATE HOW THE HORIZONTAL | | | SLIDING UNITS WILL BE SELF CLOSING. | | | REQUIRED FOR THE < 20' FROM PROPERTY | | | LINE. | | | IN CASE OF THE WINDOWS NEXT TO THE | | | STAIRWAY INDICATE IF A FIXED FIRE RATED | | | WINDOW OR OTHER MEANS OF CODE COMPLIANCE | | | | | | 6) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) LOUVER | | | B) TRUSS ANCHORS | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 7) PLEASE DELETE ALL REFRENCES OF SEMCO | | | PRODUCTS FROM PLANS, THIS PRODUCT WAS | | | BOUGHT OUT IN 1999. THERE IS NO STATE | | | APPROVALS FOR THIS PRODUCT!!!!!!!!!!!!! | | | | | | 8) PLANS INDICATE THE USE OF MONIER ROOF | | | TILE VS SUBMITTING PRODUCT APPROVAL FOR | | | ENTEGRA ROOF TILE??????????/ | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2005-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-05-18 |
Time |
11:50 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-05-18 |
Time |
11:50 |
Sent To |
B |
|
| Notes |
| 2005-05-18 00:00:00 | ELEC REV.OK. | | | REV #15 FOR LT POLES SENT TO BLDG. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2005-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-28 |
Time |
17:33 |
Rev Time |
0.20 |
| Received By |
dpalmer |
Date |
2005-02-28 |
Time |
17:33 |
Sent To |
FIRE |
|
| Notes |
| 2005-02-28 00:00:00 | SUBMITTALS FOR ELECTRICAL | | | EQUIPMENT/DEVICES , STRAPS, BOXES ETC |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2005-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-02-28 |
Time |
15:59 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2005-02-28 |
Time |
15:59 |
Sent To |
B |
|
| Notes |
| 2005-02-28 00:00:00 | SITE LIGHTING FIXTURES. | | | SENT TO BLDG FOR WIND LOAD CALCS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-09-22 |
Time |
15:16 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2004-09-22 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-04-21 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-15 |
Time |
09:56 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-04-21 |
Time |
20:34 |
Sent To |
|
|
| Notes |
| 2004-04-21 00:00:00 | REDLINED | | | NO EGC FROM METER TO MAIN. 250.6/250.24 | | | | | | ROMEX PER 2002 NEC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-03-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-03-09 |
Time |
16:44 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-03-09 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2004-03-09 00:00:00 | PASSED PENDING FIRE REVIEW | | | REDLINED LOCK-OFF BRKR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-02-26 |
Time |
08:06 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2004-02-26 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2004-02-26 00:00:00 | *** ELECTRICAL PLANS STAMPED, HOWEVER | | | E-U2,E-U3 WERE VOIDED DUE TO FIRE | | | REVIEW COMMENTS. | | | | | | REDLINED 250.24, NO EQUIPMENT GROUNDING | | | CONDUCTOR FROM METER TO MAIN ON TRASH | | | RISER. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2005-04-13 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-04-13 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-04-13 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2005-04-13 00:00:00 | FIRE ALARM SUBMITTIALS |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-04-07 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-04-07 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-04-07 |
Time |
14:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2004-03-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-03-12 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-03-12 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2004-03-12 00:00:00 | APPROVED PROVISO: | | | | | | 1) THE FIRE ALARM SYSTEMS ARE TO BE | | | CLASS A OR FULLY ADDRESSABLE NOT | | | CLASS B PER THE VALUE ENGINEERING | | | STATEMENT. | | | | | | 2) THE FIRE EXTINGUISHERS WERE NOTED | | | TO BE LOCATED ON HOOKS PER THE VALUE | | | ENGINEERING STATEMENT. THESE ITEMS | | | MAY BECOME STOLEN HENCE RESULTING IN | | | ADDITIONAL COSTS DUE TO REPLACEMENTS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-02-26 |
Time |
08:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-02-25 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2004-02-26 00:00:00 | 1) PLEASE SUBMIT PRODUCT APPROVALS FOR | | | THE 45 MINUTE FIRE RATED SLIDING GLASS | | | DOORS AND THE 45 MINUTE RATED FRENCH | | | DOORS AND EGRESS WINDOWS. | | | | | | 2) BUILDING ADDRESS REQUIRED ON PROPER | | | ELEVATION. | | | | | | 3) ALL NEW FIRE ALARM SYSTEMS SHALL BE | | | UL LISTED FOR CENTRAL STATION SERVICE. | | | | | | 4) FIRE ALARM AUDIO AND VISUAL DEVICES | | | ARE TO BE INSTALLED IN UNITS DESIGNED | | | FOR THE HANDICAP. | | | | | | 5) FDC SHALL BE A SINGLE 2 1/2 NOT | | | A SINGLE 1 1/2 AS SHOWN ON THE PLANS. | | | | | | 6) ENTRY DOOR JAMB SHALL BE B LABEL | | | NOT C LABELED AS SHOWN ON ENTRY DOOR | | | HEAD JAMB DETAIL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
|
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
|
Time |
13:52 |
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2005-02-08 00:00:00 | TO DPALMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
31 |
Status |
N |
Date |
2005-04-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-19 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-19 |
Time |
15:37 |
Sent To |
E |
|
| Notes |
| 2005-04-19 00:00:00 | TO "DPALMER"DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
30 |
Status |
N |
Date |
2005-04-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-04-14 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-04-14 |
Time |
16:06 |
Sent To |
B |
|
| Notes |
| 2005-04-14 00:00:00 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
29 |
Status |
N |
Date |
2005-03-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-25 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-25 |
Time |
15:42 |
Sent To |
B |
|
| Notes |
| 2005-03-25 00:00:00 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
28 |
Status |
N |
Date |
2005-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-14 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-14 |
Time |
11:33 |
Sent To |
B |
|
| Notes |
| 2005-02-14 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
27 |
Status |
N |
Date |
2005-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-14 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-14 |
Time |
11:28 |
Sent To |
B |
|
| Notes |
| 2005-02-14 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
26 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-14 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2005-02-14 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
25 |
Status |
N |
Date |
2005-02-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-11 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-11 |
Time |
12:41 |
Sent To |
B |
|
| Notes |
| 2005-02-11 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
24 |
Status |
N |
Date |
2005-02-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-11 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-11 |
Time |
12:33 |
Sent To |
B |
|
| Notes |
| 2005-02-11 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
23 |
Status |
N |
Date |
2005-02-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-11 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-11 |
Time |
12:27 |
Sent To |
B |
|
| Notes |
| 2005-02-11 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
10:13 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
10:08 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
10:00 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
09:54 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
09:49 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
09:42 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
08:22 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2005-02-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-10 |
Time |
08:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-10 |
Time |
08:13 |
Sent To |
B |
|
| Notes |
| 2005-02-10 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-08 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-08 |
Time |
14:37 |
Sent To |
B |
|
| Notes |
| 2005-02-08 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-08 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-08 |
Time |
14:20 |
Sent To |
B |
|
| Notes |
| 2005-02-08 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-08 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-08 |
Time |
13:58 |
Sent To |
B |
|
| Notes |
| 2005-02-08 00:00:00 | TO JWITMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-02-08 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-02-08 |
Time |
13:44 |
Sent To |
E |
|
| Notes |
| 2005-02-08 00:00:00 | TO DPALMER DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-02-08 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-02-08 |
Time |
13:06 |
Sent To |
P |
|
| Notes |
| 2005-02-08 00:00:00 | TO "P" BOX/SUBMITTALS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2005-02-08 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2005-02-08 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2005-02-08 |
Time |
12:41 |
Sent To |
M |
|
| Notes |
| 2005-02-08 00:00:00 | TO "M/AC" BOX/SUBMITTALS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2004-11-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-10 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-10 |
Time |
13:23 |
Sent To |
B |
|
| Notes |
| 2004-11-10 00:00:00 | TO JW DESK/SUBMITTAL/EXTERIOR METAL | | | FRAMING SHOP DRAWINGS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2004-09-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-15 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-15 |
Time |
09:56 |
Sent To |
E |
|
| Notes |
| 2004-09-15 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-08-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-23 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-23 |
Time |
14:30 |
Sent To |
B |
|
| Notes |
| 2004-08-23 00:00:00 | TO JW DESK/SUBMITTAL/SHOP DRAWS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-05-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-13 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-13 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2004-05-13 00:00:00 | TO COMM BD#53 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-04-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-28 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-28 |
Time |
14:17 |
Sent To |
B |
|
| Notes |
| 2004-04-28 00:00:00 | TO COMM BD#53 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-04-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-06 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-06 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2004-04-06 00:00:00 | TO COMM BD#8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-03-04 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2004-03-04 |
Time |
16:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-02-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-12 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-12 |
Time |
15:02 |
Sent To |
B |
|
| Notes |
| 2004-02-12 00:00:00 | TO JW DESK/MASTERED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-04-21 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-21 |
Time |
07:24 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-04-21 |
Time |
06:43 |
Sent To |
|
|
| Notes |
| 2004-04-21 00:00:00 | PROVISO: | | | TOILET EXHAUST TERMINATING AT THE WALL | | | SHALL BE SCREENED.BACKDRAFT DAMPER | | | SHOULD BE A PART OF THE FAN ASSEMBLY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2004-03-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-03-05 |
Time |
13:40 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2004-03-05 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2004-03-05 00:00:00 | PROVISO: | | | PER CONVERSATION WITH SHAWN WILSON: | | | ENGINEER TO PROVIDE REVISED PLAN OR | | | LETTER ADDRESSING FRESH AIR INTAKE, DUCT | | | SIZE AND MATERIAL, PRIOR TO CONSTRUCTION | | | OUTSIDE AIR CALCULATION INDICATED ON | | | PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2004-02-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-02-27 |
Time |
12:42 |
Rev Time |
0.55 |
| Received By |
pkrauss |
Date |
2004-02-27 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2004-02-27 00:00:00 | DENIED: | | | PLANS INDICATE REFRIGERANT LINES IN A | | | NON-RATED ENCLOSURE.PER ASHRAE 15-92 | | | SECTION 11.12.3 (B), PIPING TO BE | | | CARRIED IN AN APPROVED RIGID, TIGHT, | | | CONTINUOUS FIRE RESISTING PIPE DUCT OR | | | SHAFT. | | | | | | THE FOLLOWING WAS REVISED WITH THE CODE | | | CHANGE EFFECTIVE JUNE 30, 2003: | | | VENTILATION SYSTEMS OTHER THAN R-3 | | | (ONE & TWO FAMILY), SHALL HAVE THE | | | MINIMUM REQUIREMENTS FOR OUTSIDE AIR | | | IN ACCORDANCE WITH TABLE 403.3. | | | PLEASE REVISE PLANS TO REFLECT THE | | | CODE CHANGE. | | | | | | PLEASE NOTE, DETAIL FOR THE DRYER BOX | | | IS NOT LEGIBLE.PLEASE PROVIDE | | | MANUFACTURER SUBMITTAL DATA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2005-02-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-02-19 |
Time |
13:42 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2005-02-19 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2005-02-19 00:00:00 | PLUMBING FIXTURE SUBMITALS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2004-05-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-05-15 |
Time |
13:05 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2004-05-15 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2004-05-15 00:00:00 | REVISION OK - SHTS P-U2, P-U3, P2A.1, | | | P2A.2, P2A.3, PD-1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2004-05-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-05-12 |
Time |
12:29 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-05-12 |
Time |
12:28 |
Sent To |
|
|
| Notes |
| 2004-05-12 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | | | | 1) COMMENTS FROM PREVIOUS REVISION WERE | | | NOT ADDRESSED. ALL REVISIONS TO A PLAN | | | SHALL BE CLOUDED AND A REVISION NUMBER | | | SHALL INDICATE LOCATION OF REVISION. | | | SEE COMMENTS FROM PRIOR REVISION REVIEW | | | ATTACHED TO THIS COMMENT SHEET. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2004-04-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-04-19 |
Time |
12:36 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2004-04-17 |
Time |
18:54 |
Sent To |
|
|
| Notes |
| 2004-04-19 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT PT2A.1 REVISIONS INDICATED ON THE | | | SANT. BLDG. DRAIN AND WATER SERVICES BUT | | | WERE NOT CLOUDED NOR NUMBERED AS A REV- | | | ISION. PLEASE CLARIFY. | | | 2) SHT PT2A.3 REVISIONS SHOWN ON SANT. | | | BLDG DRAIN, SANT. RISER P/3, AND WATER | | | ISOMETRICS W/WATER SERVICE. NO CLOUDS | | | NOR REVISION NUMBERS SHOWN. PLEASE | | | CLARIFY. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-03-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-03-13 |
Time |
10:06 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2004-03-13 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2004-03-13 00:00:00 | NEW SHEETS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2004-02-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-02-25 |
Time |
09:19 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2004-02-24 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2004-02-25 00:00:00 | PASSED/PROVISO | | | | | | WATER HAMMER ARRESTOR SHALL BE LOCATED | | | AT THE REFRIG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2005-05-26 |
|
|
Cont ID |
|
| Sent By |
dkanning |
Date |
2005-05-26 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
dkanning |
Date |
2005-05-26 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2005-05-26 00:00:00 | PHOTOMETRIC READINGS SHALL NOT EXCEED | | | 0.5 FOOT CANDLES ACROSS PROPERTY LINES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2004-05-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-05-19 |
Time |
14:15 |
Rev Time |
0.10 |
| Received By |
gjoyce |
Date |
2004-05-18 |
Time |
12:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-03-17 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-03-17 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-03-17 |
Time |
14:15 |
Sent To |
B |
|
| Notes |
| 2004-03-17 00:00:00 | APPROVED BY DAVID KANNING, PLANNER | | | 659-8031.PROVISO: SIGNED & SEALED | | | LANDSCAPE PLANS MUST BE APPROVED PRIOR | | | TO LANDSCAPE INSPECTION. |
|
|