Plan Review Details - Permit 04020408
Plan Review Stops For Permit 04020408
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-06 Cont ID  
Sent By jwitmer Date 2004-04-06 Time 16:23 Rev Time 0.55
Received By jwitmer Date 2004-04-06 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-06 Cont ID  
Sent By jwitmer Date 2004-03-06 Time 16:16 Rev Time 1.00
Received By jwitmer Date 2004-03-06 Time 16:16 Sent To  
Notes
2004-03-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020408
 ADD: 10130 NORTHLAKE BLVD# 108
 CONT: FIVE STAR SERVICES INC
 TEL: (954)553-9661
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE VOMPLETE ADDRESS ON THE PER-
 MIT APPLICATION MISSING SUITE.
  
 3) PROVIDE THE WIDTH DIMENSION OF THE
 RESTROOM, THE DRAWING INDICATES A 5'-8"
 CIRCLE THAT IS IN THE WALL, WATERCLOSET
 AND LAV?
  
 4)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 17:29 Rev Time 0.50
Received By btrobaug Date 2004-04-06 Time 16:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-18 Cont ID  
Sent By dpalmer Date 2004-02-18 Time 12:35 Rev Time 0.50
Received By dpalmer Date 2004-02-18 Time 12:05 Sent To  
Notes
2004-02-18 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN
 RECEPTS REQ'D TO BE GFI.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 3)NOTE: PLEASE SEE 210.62 FOR RECEPTS
 IN SHOW WINDOWS.
  
 4)NOTE: PLEASE PROVIDE ADDRESS ON TITLE
 BLOCK. PLEASE ALSO PROVIDE SUITE/ BAY
 # TO APPLICATION AND FRONT COUNTER STAFF
 TO ADD TO PERMITS. INSPECTORS WILL NOT
 BE ABLE TO FIND JOB.
 NOTE: THERE IS NO "W" NORTHLAKE. JUST
 NORTHLAKE.
  
 5)NOTE: PLEASE SEE LOADS SHOWN FOR
 WATER HEATER AND AHU, BOTH SHOWN AS 5KW
 LOAD W/ 60A AND 50A OCP WITH #6 AWG.
 PLEASE VERIFY.
 MAX OCP IS 150% AND MIN IS 125%.
 424.3B,422.13
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS
 FUSES AS BEING MEANS OF OCP. PLEASE
 VERIFY IF BRKR??
  
 7)NOTE: PLEASE PROVIDE NOTE ON REQ'D
 SHUNT TRIP FOR HOOD/ SHUT OFF.
 NFPA-96
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-02-11 Cont ID  
Sent By mcarsill Date 2004-02-11 Time 15:48 Rev Time 0.00
Received By mcarsill Date 2004-02-11 Time 15:48 Sent To  
Notes
2004-02-11 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE HOOD, DUCT, AND EXTINGUISHING
 SYSTEM.
  
 2) ENSURE PROPER FIRE SEPARATION
 BETWEEN TENANTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-23 Cont ID  
Sent By csiegber Date 2004-03-23 Time 14:36 Rev Time 0.00
Received By csiegber Date 2004-03-23 Time 14:36 Sent To  
Notes
2004-03-23 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-04-06 Cont ID  
Sent By btrobaug Date 2004-04-06 Time 17:29 Rev Time 0.00
Received By btrobaug Date 2004-02-11 Time 09:12 Sent To  
Notes
2004-02-11 00:00:00TO COMM BD#7

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-20 Cont ID  
Sent By pkrauss Date 2004-02-20 Time 13:50 Rev Time 0.45
Received By pkrauss Date 2004-02-20 Time 13:50 Sent To  
Notes
2004-02-20 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIRED FOR THE
 WALK-IN COOLER.STAND FOR C.U. 2 SHALL
 COMPLY WITH 2001 FBC 1511.7 FOR THE
 HEIGHT REQUIREMENT FROM THE ROOF
 SURFACE TO THE BOTTOM OF THE SUPPORT
 RAIL (SEE ATTACHED)
  
 ADDITIONAL PERMIT REQUIRED FOR HOOD
 SUPPERSSION.PLANS SUBMITTED WITH
 BUILDING PERMIT ARE APPROVED.
  
 TERMINATION OF EXHAUST FOR GREASE DUCT
 SHALL BE A MINIMUM OF 10 FT FROM
 PROPERTY LINES, INTAKE OPENINGS AND
 PARTS OF THE SAME OR CONTIGUOUS
 BUILDING PER 2001 FBC(M) 506.3.14.3.A
 MINIMUM OF 2 FT BETWEEN PARAPET AND
 VERTICAL DISCHARGE.
  
 HOOD PERMIT MAY BE ISSUED WITH BUILDING
 PERMIT IN LIEU OF HVAC PERMIT.PLAN
 SHEET H-1 INDICATES NO WORK TO BE DONE
 ON THE EXISTING A/C.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-26 Cont ID  
Sent By kstevens Date 2004-03-26 Time 16:02 Rev Time 1.50
Received By kstevens Date 2004-03-26 Time 16:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-20 Cont ID  
Sent By csiegber Date 2004-03-23 Time 14:36 Rev Time 1.50
Received By kstevens Date 2004-02-20 Time 10:28 Sent To  
Notes
2004-02-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) PLANS SHALL BE ROUTED TO THE DEPT. OF
 BUSINESS REGULATION HOTEL AND RESTURANT
 DIVISION. PLANS SHALL BE STAMPED AND
 WORK SHEET ATTACHED PRIOR TO RESUBMITT-
 ING TO CITY WPB FOR REVIEW.
 2) SHT A-1 TOILET ROOM NOT LARGE ENOUGH.
 SUBMIT A DETIAL SHOWING COMPLIANCE WITH
 SECTION 11-4.16 AND ALL SUBSECTIONS,
 SECTION 11-4.19 AND ALL SUBSECTIONS, AND
 SECTION 11-4.22 AND ALL SUBSECTIONS.
 3) SHT P-1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL REQUIRED PER SECTION
 607.3.2 BECAUSE AN RPZ BACKFLOW IS RE-
 QUIRED.
 4) SHT P-1 GREASE RISER DIAGRAM. THE
 DRAINAGE FROM THE STEAM TABLE SHALL
 DRAIN INTO A FLOOR SINK. FLOOR DRAINS
 ARE NOT AN APPROVED INDIRECT WASTE
 RECEPTOR. SECTION 802.3
 5) SHT P-1 INDICATE WALL AND FLOOR
 THICKNESS FOR GREASE INTECEPTOR. SEE
 ATTACHED SHEET FOR WPB STANDARD FOR
 GREASE INTERCEPTORS.
 6) THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - TOTAL ON PLAN SHOWS 1,105K,
 BUT ADDING UP BTU'S ON RISER DIAGRAM
 ADDS UP TO 1,080K. PLEASE CLAIRFY
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 ALL GAS APPLIANCES SHALL SHOW A LISTING
 BY AN APPROVED TESTING AGENCY ON MANUF.
 SHEETS.
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 7) GREASE INTECEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 WASTE ORD. #2938-96- (561) 837-4074.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]