Plan Review Details - Permit 04020394
Plan Review Stops For Permit 04020394
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-07-12 Cont ID  
Sent By rmcdouga Date 2004-07-12 Time 09:13 Rev Time 2.00
Received By rmcdouga Date 2004-07-12 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-06-15 Cont ID  
Sent By csiegber Date 2004-07-07 Time 16:42 Rev Time 3.00
Received By rmcdouga Date 2004-06-15 Time 12:54 Sent To  
Notes
2004-06-15 00:00:00DENIED
  
 1) THE NOC SUBMITTED DOES NOT COMPLY
 WITH FS 713.13. PROPERTY NOT IDENTIFIED.
 SEE ATTACHED.
  
 2) PRIVACY WALL EXCEEDS MAXIMUM HEIGHT
 ALLOWED BY ZONING. CHECK WITH THE ZONING
 DEPARTMENT. A SEPARATE PERMIT WILL BE
 REQUIRED. REVISE SHEETS A1 AND A5.
  
 3) THE PRODUCT APPROVAL DRAWINGS FOR THE
 CLOPAY GARAGE DOORS DOES NOT CONCUR WITH
 PLANS. THE WIDTH AND PRESSURES EXCEED
 LIMITS ON PROD. APPROVAL DRAWINGS.
  
 4) THERE ARE NO CASEMENT WINDOWS SHOWN
 ON THE ARCHITECTURAL PLANS. REMOVE THIS
 PRODUCT APPROVAL FROM SUBMITTAL.
  
 5) NO STATE OF FL PRODUCT APPROVAL #S
 WERE SUBMITTED FOR THE FOLLOWING ITEMS:
 - FRENCH DOORS WITH SIDELITES
 - FRENCH DOORS
 - SINGLE HUNG WINDOWS
 - STRUCTURAL MULLIONS
  
 6) NO INSTALLATION INSTRUCTIONS WERE
 SUBMITTED FOR FL 328 SLIDING GLASS DOORS
  
 7) THE NOA NUMBER FOR THE PW 701 FIXED
 WINDOWS DOES NOT MATCH THE NOA #S LISTED
 ON THE FL 243 STATE PROD. APP.
  
 8) SUBMIT STATE PRODUCT APPROVAL FOR THE
 WINDOWS IN THE BREAKFAST ROOM, BAR AND
 MASTER BATH. INDICATE WHAT TYPE OF
 ASSEMBLY WILL BE INSTALLED IN THESE
 AREAS (STOREFRONTS, BUTT GLASS, ETC.).
  
 9) THE PRODUCT APPROVALS SUBMITTED FOR
 THE MULLIONS WILL NOT WORK BETWEEN THE
 WINDOWS AT THE LIVING ROOM OR THE 16'SGD
 AND THE TRANSOM AT THE FAMILY ROOM.
 SUBMIT APPROPRIATE PRODUCT APPROVAL OR
 ADD LINTEL BETWEEN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-05-20 Cont ID  
Sent By jleech Date 2004-06-12 Time 11:10 Rev Time 2.00
Received By rmcdouga Date 2004-05-20 Time 13:59 Sent To  
Notes
2004-05-20 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) OWNER OR AGENT IS REQUIRED TO SIGN
 AND DATE THE ENERGY CALC. FORM.
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 IN ADDITION TO THE STATE PRODUCT
 APPROVAL COVER SHEET (WITH FL#), THE
 CORRESPONDING EVALUATION REPORT, NOA,
 TEST REPORT,ETC. CONTAINING INSTALLATION
 INSTRUCTIONS, LIMITATIONS, ETC. IS
 REQUIRED TO BE SUBMITTED FOR EACH ITEM.
  
 4) CLARIFY WHAT SYSTEM IS BEING USED FOR
 THE WINDOWS ON ANGLES AT THE BREAKFAST
 ROOM, BAR AND MASTER BATH.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-22 Cont ID  
Sent By kstevens Date 2004-05-17 Time 15:28 Rev Time 2.00
Received By rmcdouga Date 2004-04-22 Time 10:59 Sent To  
Notes
2004-04-22 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE A/C AREA LISTED ON THE PLANS IS
 5783 SQFT AND THE ENERGY CALC. FORM
 LISTS 5779 SQFT. PLEASE CORRECT.
  
 3) IN ADDITION TO THE STATE PRODUCT
 APPROVAL COVER SHEET, THE CORRESPONDING
 EVALUATION REPORT, NOA, TEST REPORT, ETC
 CONTAINING INSTALLATION INSTRUCTIONS,
 DESIGN PRESSURES, LIMITATIONS, ETC. IS
 REQUIRED TO BE SUBMITTED.
  
 4) SUBMIT STATE PRODUCT APPROVAL WITH
 INSTALLATION INSTRUCTIONS, LIMITS, ETC.
 FOR THE FOLLOWING:
 - SINGLE HUNG WINDOWS
 - OUTSWING GLAZED DOORS
 - OUTSWING DOUBLE DOORS WITH SIDELITES
 - ARCHED TOP FIXED GLASS WINDOWS
 (DESIGNER SHAPES)
 - RECTANGULAR FIXED GLASS WINDOWS
 - STRUCTURAL MULLIONS
 - STOREFRONT WINDOWS AT BREAKFAST ROOM,
 BAR AND MASTER BATH
 - ALL EXTERIOR WINDOWS AND DOORS USED IN
 THIS STRUCTURE
  
 5) SUBMIT ADDITIONAL COPIES OF THE BBQ
 AND HOOD INFORMATION THAT WAS SUBMITTED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-22 Cont ID  
Sent By kstevens Date 2004-04-21 Time 09:02 Rev Time 3.00
Received By rmcdouga Date 2004-03-22 Time 16:44 Sent To  
Notes
2004-03-22 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SPECIFY ON PLANS THAT WIRE MESH IN
 SLAB IS TO BE SUPPORTED ON APPROVED
 MATERIAL AT 3'O.C. PER FBC 1909.3.
  
 4) INDICATE THE APPLICABLE ENCLOSURE
 CLASSIFICATION AND,IF DESIGNING BY ASCE
 7-98, THE INTERNAL PRESSURE COEFFICENT
 PER FBC 1606.1.7.
  
 5) SPECIFY THE SIZE OF THE ATTIC
 ACCESSES ON THE PLANS. THE MINIMUM SIZE
 IS 20 X 36 INCHES PER FBC 2309.6.
  
 6) THE A/C AREA LISTED ON THE PLANS DOES
 NOT MATCH THE CONDITIONED AREA ON THE
 ENERGY CALC. FORM. PLEASE CORRECT.
  
 7) SPECIFY THE AREA OF THE COVERED
 PORCHES AND GARAGE ON THE AREA CALCS. ON
 SHEET A3.
  
 8) SPECIFY ON THE PLANS THAT THE DOOR TO
 THE GARAGE FROM THE CONDITIONED SPACE IS
 INSULATED OR SOLID CORE AS REQUIRED BY
 FBC 13-603.
  
 9) REVISE THE ROOF SHEATHING FASTENING
 SCHEDULE ON A8. FOR A MEAN ROOF HEIGHT
 LESS THAN 25'FASTENERS ARE REQUIRED TO
 BE SPACED 4"OC AT THE EDGES AND 6"OC
 INTERMEDIATE IN ZONE 3 AND FOR A MEAN
 ROOF HEIGHT 25'TO 35' FASTENERS ARE
 REQUIRED TO BE 8D RING SHANK NAILS
 SPACED 4"OC EDGES AND 6"OC INTERMEDIATE
 IN ZONE 3. SEE CITY AMENDMENTS TO FBC
 TABLE 2306.1.
  
 10) IN THE TRUSS ANCHOR SCHEDULE ON A8
 THE (I) HETA 16 W/10- 10D X 1-1/2 NAILS
 IS LISTED WITH UPLIFT OF 810#. THE
 SIMPSON CATALOG LISTS 1810#. PLEASE
 CORRECT.
  
 11) SOME OF THE TRUSSES ON THE TRUSS
 LAYOUT ON A7 DO NOT HAVE AN ANCHOR
 SPECIFIED. PLEASE SPECIFY ANCHORS FOR
 ALL TRUSS TO WALL CONNECTIONS.
  
 12) PROVIDE A DETAIL OF THE 2X4 FRAME
 WALLS AT THE TOWER. SPECIFY THE SPACING
 OF THE 2X4S AND STRAPPING REQUIRED TO
 ACHIEVE A CONTINOUS LOAD PATH FROM THE
 TOWER ROOF TO THE GIRDER TRUSSES BELOW.
  
 13) PROVIDE DETAILS AND PRODUCT APPROVAL
 FOR THE ANGLED FIXED GLASS WINDOW
 ASSEMBLIES AT THE MASTER BATH AND
 BREAKFAST/BAR AREA.
  
 14) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 15) THE DRAWING SUBMITTED FOR THE CLOPAY
 GARAGE DOORS ARE LIMITED TO A MAXIMUM
 WIDTH OF 9'. THE DOORS ON THE PLANS ARE
 10' WIDE. SUBMIT APPROPRIATE DRAWINGS.
  
 16) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING FOR THE GAS BBQ AND HOOD.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-06-29 Cont ID  
Sent By dpalmer Date 2005-06-29 Time 16:15 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-06-29 00:00:00NEEDS NEW SHEETS, NO REVIEW DONE.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2005-06-21 Cont ID  
Sent By dpalmer Date 2005-06-21 Time 08:08 Rev Time 0.50
Received By dpalmer Date 2005-06-21 Time 08:05 Sent To  
Notes
2005-06-21 00:00:00************* UNSAT *************
  
  
 1)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT/ PANELS ON PLANS. PLEASE
 CORRELATE PANELS WITH RISER.
 MISSING D, E ETC.
 215.5
  
  
 2)NOTE: PLEASELOADS SHOWN ON MAIN
 PANEL SCHEDULES. PLEASE SEE SOME ARE NOT
 CLEAR AND NEED TO DARKER.
  
  
 3)NOTE: PLEASE SEE MISSING KITCHEN
 COUTERSPACE RECEPT PER 210.52C1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2005-06-15 Cont ID  
Sent By dpalmer Date 2005-06-15 Time 17:41 Rev Time 0.50
Received By dpalmer Date 2005-06-15 Time 17:37 Sent To  
Notes
2005-06-15 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS SUBMITTED MUST
 BE REVISED BY THE ARCH OF RECORD. PLANS
 MUST BE SIGNED, DATED AND SEALED BY
 ARCH. FS 481.221
 PLANS MUST ALL TITLE BLOCKS AS REQUIRED
 UDNER FAC 61G1-16.004.
  
 2)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT/ PANELS ON PLANS.
 MISSING D, E ETC.
 215.5
  
 3)NOTE: PLEASE SEE 230.72. 225.24 FOR
 GROUPING OF DISCONNECTING MEANS.
 PLEASE SEE GEN SUB PANEL APPEARS TO BE
 SHOWN AS MLO, WHERE ARE MCB IS REQUIRED.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 ON PANEL SCHEDULES AND FOR SERVICE WHICH
 MEET 2002 NEC 220.31. PLEASE SEE THE
 SAME LOAD OF 41 A'S IS INDICATED AND
 SHOWN ON EACH PANEL LOAD CALC.???
 215.5
  
 5)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS SHOWN BEFORE THE FIRST MEANS
 OF DISCONNECT. PLEASE SEE 250.6,250.24
 THESE ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 6)NOTE: PLEASE SEE MISSING KITCHEN
 COUTERSPACE RECEPT PER 210.52C1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-18 Cont ID  
Sent By dpalmer Date 2004-04-18 Time 08:17 Rev Time 0.33
Received By dpalmer Date 2004-04-18 Time 08:17 Sent To P
Notes
2004-04-18 00:00:00CORRECTIONS MADE, PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-23 Cont ID  
Sent By pkrauss Date 2004-04-16 Time 15:42 Rev Time 0.50
Received By btrobaug Date 2004-02-23 Time 12:33 Sent To M
Notes
2004-02-23 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDER FOR PANEL "C" IS #3 ON
 THERISER.IT IS LISTED AS #6 ON PANEL
 SCHEDULE "B". PLEASE CORRELATE
  
 2} PLEASE NOTE THE #6 CONDUCTORS WITH
 100 AMP OCP IS IN VIOLATION OF
 310.16,CKTS 20 & 22, PANEL "B".
  
 3} THE KW RATING FOR PANEL "C" IS LISTED
 @ 20KW IN PANEL "B" AND 18 KW ON PANEL
 "C".PLEASE CORRELATE.
  
 4} NOTE THAT PANEL "B" READS "VA"
 INSTEAD OF "KW".
  
 5} THE REFRIGERATOR IN PANEL "A" IS
 LISTED @ 3KW. THAT WUOLD BE 25 AMPS ON
 THE 20 BREAKER THAT IS SHOWN.
  
 6} THE HEAT STRIPS ON THE MECHANICAL
 PLAN THE ONES ON THE ELECTRICAL PLAN
 ARE NOT THE SAME. PLEASE CORRELATE AND
 RECALCULATE THE LOAD ACCORDINGLY.
  
 7} PLEASE INDICATE THE LOCATION OF "C"
 PANEL.
  
 8} THE DISCONNECT FOR A/C #4 DOES NOT
 COMPLY WITH 110.26 FOR CLEARANCES.
  
 9} PLEASE NOTE THE SPA RECEPTACLE MUST
 BE GFI PER 680.43(A)(1).
  
 10} PLEASE NOTE THAT THE FIRM LICENSE
 NUMBER MUST BE ADDED TO THE TITLE
 BLOCK TO COMPLY WITH 61G1-16.004(2) FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 09:51 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 09:51 Sent To P
Notes
2005-06-24 00:00:00TO "P" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-06-24 Cont ID  
Sent By adarroug Date 2005-06-24 Time 09:49 Rev Time 0.00
Received By adarroug Date 2005-06-24 Time 09:49 Sent To E
Notes
2005-06-24 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-06-17 Cont ID  
Sent By shill Date 2005-06-17 Time 11:48 Rev Time 0.00
Received By shill Date 2005-06-17 Time 11:48 Sent To E
Notes
2005-06-17 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-06-10 Cont ID  
Sent By shill Date 2005-06-10 Time 11:42 Rev Time 0.00
Received By shill Date 2005-06-10 Time 11:42 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-06-08 Cont ID  
Sent By shill Date 2005-06-08 Time 09:35 Rev Time 0.00
Received By shill Date 2005-06-08 Time 09:35 Sent To E
Notes
2005-06-08 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-05-10 Cont ID  
Sent By adarroug Date 2005-05-10 Time 15:40 Rev Time 0.00
Received By adarroug Date 2005-05-10 Time 15:40 Sent To P
Notes
2005-05-10 00:00:00TO "KSTEVENS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-04-12 Cont ID  
Sent By adarroug Date 2005-04-12 Time 17:23 Rev Time 0.00
Received By adarroug Date 2005-04-12 Time 17:23 Sent To B
Notes
2005-04-12 00:00:00TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-07-07 Cont ID  
Sent By csiegber Date 2004-07-07 Time 16:42 Rev Time 0.00
Received By csiegber Date 2004-07-07 Time 16:42 Sent To B
Notes
2004-07-07 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-09 Cont ID  
Sent By csiegber Date 2004-06-09 Time 10:38 Rev Time 0.00
Received By csiegber Date 2004-06-09 Time 10:38 Sent To P
Notes
2004-06-09 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-05-03 Cont ID  
Sent By csiegber Date 2004-05-03 Time 15:33 Rev Time 0.00
Received By csiegber Date 2004-05-03 Time 15:33 Sent To M
Notes
2004-05-03 00:00:00TO PK DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-12 Cont ID  
Sent By csiegber Date 2004-04-12 Time 12:01 Rev Time 0.00
Received By csiegber Date 2004-04-12 Time 12:01 Sent To M
Notes
2004-04-12 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-22 Cont ID  
Sent By mmclean Date 2004-02-13 Time 15:12 Rev Time 0.00
Received By rmcdouga Date 2004-02-11 Time 15:06 Sent To  
Notes
2004-02-13 00:00:00TO SFD RACK/E
2004-02-11 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-05-13 Cont ID  
Sent By pkrauss Date 2004-05-13 Time 14:16 Rev Time 0.40
Received By pkrauss Date 2004-05-13 Time 13:47 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-05-03 Time 15:33 Rev Time 0.45
Received By pkrauss Date 2004-04-16 Time 15:13 Sent To E
Notes
2004-04-16 00:00:00DENIED:
 2ND REQUEST:
 1.DUCT SIZES ARE NOT INDICATED ON
 PLAN.PLEASE REVISE PLANS TO REFLECT
 DUCT SIZE.
  
 2.RETURN AIR SHALL BE EQUAL TO THE
 SUPPLY AIR TO THAT AREA PER 2001 FBC(M)
 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-04-12 Time 12:01 Rev Time 0.50
Received By hmoser Date 2004-02-26 Time 18:55 Sent To B
Notes
2004-02-26 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 AND RESUBMIT PLANS FOR REVIEW
 1) REFER TO SECTION 601.4 BALANCED
 RETURN AIR.
 2) SOME OF THE DUCT SIZES ARE NOT MARKED
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6734

Review Stop P PLUMBING
Rev No 6 Status P Date 2005-06-28 Cont ID  
Sent By kstevens Date 2005-06-28 Time 11:26 Rev Time 0.63
Received By kstevens Date 2005-06-28 Time 11:26 Sent To  
Notes
2005-06-28 00:00:00REVISION OK - SANT. RISER DIAGRAM - SEE
 RED LINE CORRECTIONS

Review Stop P PLUMBING
Rev No 5 Status F Date 2005-06-27 Cont ID  
Sent By kstevens Date 2005-06-27 Time 16:41 Rev Time 0.50
Received By kstevens Date 2005-06-27 Time 16:41 Sent To  
Notes
2005-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 A. SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN. CORRECT THE FOLLOWING:
 1. TRAPS ARE REQUIRED ON THE TUB &
 SHOWER BATH #4. SECTION 1002.1.
 2. RISER SHOWS A TUB AND FLOOR PLAN
 SHOWS A SHOWER. SECTION 104.2.1.
 3. THE WASH MACHINE SHALL CONNECT
 DOWNSTREAM OF THE LAUNDRY SINK ON THE
 STACK, AS THE VERTICAL DRAIN PIPE
 CONNECTING THE TWO FIXTURE DRAINS SHALL
 BE CONSIDERED THE VENT FOR THE LOWER
 FIXTURE. SECTION 908.3
 4. THE WASH MACHINE REQUIRES A MIN. 2'
 STANDPIPE. SECTION 1002.1.
 5. THE CLEANOUT FOR THE WASHMACHINE
 SHALL BE LOCATED 4' ABOVE THE FLOOR.
 SECTION 708.10.
 6. THE WATER CLOSET AND THE BIDET IN
 THE MASTER BATH ARE NOT VENTED. SECTION
 901.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-06-12 Cont ID  
Sent By jleech Date 2004-06-12 Time 11:10 Rev Time 0.50
Received By jleech Date 2004-06-12 Time 11:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-05-17 Cont ID  
Sent By csiegber Date 2004-06-09 Time 10:38 Rev Time 0.50
Received By kstevens Date 2004-05-17 Time 15:17 Sent To B
Notes
2004-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) NEW SANITARY RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS
 A) POWDER ROOM WATER CLOSET IS NOT
 VENTED.
 B) SINK IN GARAGE SHALL NOT DRAIN THRU
 THE BATHROOM FIXTURES. SINK SHALL DIS-
 CHARGE DOWNSTREAM OF THE BATHROOM FIX-
 TURES. SECTION 909.1
 C) WASHMACHINE AND LAUNDRY SINK DO NOT
 REFLECT THE FLOOR PLAN. WASH MACHINE IS
 ON THE RIGHT SIDE AND LAUNDRY SINK IS ON
 THE LEFT SIDE OF THE STACK. 104.2.1
 D) BATH #2 SHOWS TUB ON RISER AND SHOWS
 A SHOWER ON THE FLOOR PLAN. CLARIFY.
 E) SIZE ALL PIPES IN BATH #4, 3" REQ'D
 UP TO SHOWER. TABLE 909.3
 F) SEE PIPE SIZING FOR BIDET AND SHOWER
 IN MASTER BATH. MINIMUM 2" REQUIRED.
 TABLE 709.1
 *********SEE RED LINE CORRECTIONS*******
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-04-21 Cont ID  
Sent By pkrauss Date 2004-05-13 Time 14:16 Rev Time 0.50
Received By kstevens Date 2004-04-20 Time 15:15 Sent To B
Notes
2004-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN NOR DOES IT
 MEET CODE REQUIREMENTS. SECTION 104.2.1
 A) VEGETABLE SINK NOT SHOWN ON RISER.
 B) WASH MACHINE SHALL NOT CONNECT TO
 STACK ABOVE THE LAUNDRY SINK.
 C) BBQ SINK IDENTIFIED AS A LAV.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-19 Cont ID  
Sent By jleech Date 2004-02-19 Time 10:50 Rev Time 0.33
Received By jleech Date 2004-02-19 Time 10:50 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-13 Cont ID  
Sent By mmclean Date 2004-02-13 Time 15:12 Rev Time 0.00
Received By mmclean Date 2004-02-13 Time 15:12 Sent To I
Notes
***NONE***