Plan Review Details - Permit 04020383
Plan Review Stops For Permit 04020383
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:56 Rev Time 0.25
Received By mjacobs Date 2004-07-12 Time 13:15 Sent To  
Notes
2004-07-12 00:00:00WINDOW SUBMITTALS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By btrobaug Date 2004-03-24 Time 13:25 Rev Time 2.00
Received By rmcdouga Date 2004-03-09 Time 14:55 Sent To  
Notes
2004-03-09 00:00:00DENIED
  
 1) THE PLAN REVIEW NUMBER ON THE COPY OF
 THE PAID RECIEPT DOES NOT MATCH THE
 PLAN REVIEW NUMBER ON THE PLANS. SUBMIT
 THE CORRECT PAID RECIEPT.
  
 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. FBC TABLE 1604.1 REQUIRES
 ATTICS WITHOUT STORAGE TO HAVE A LIVE
 LOAD OF 10 PSF AND 30 PSF FOR ATTICS
 WITH STORAGE.
  
 3) REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL ON A4 TO STATE THAT THEY ARE
 FASTENED THROUGH THE BUCK AND NOT TO IT.
 SEE FBC 1707.4.4.2.
  
 4) THE HEIGHTS LISTED FOR THE MASONRY
 OPENINGS OF WINDOWS 12 AND 13 ON A4 ARE
 INCORRECT (SHOULD BE 64"). PLEASE
 REVISE.
  
 5) UPDATE THE SEMCO TRUSS HANGER
 SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT
 ANCHOR WITH STATE OR LOCAL PRODUCT
 APPROVAL.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 7) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS INSULATED OR SOLID CORE AS REQUIRED
 BY FBC CHAPTER 13 SECTION 603.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE 16'
 LONG MULLION BETWEEN THE SLIDING GLASS
 DOOR AND THE TRANSOM AT THE GREAT ROOM.
 THE ONE SUBMITTED ONLY LISTS UP TO A 12'
 MULL LENGTH.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-02-22 Cont ID  
Sent By btrobaug Date 2005-02-22 Time 12:14 Rev Time 0.50
Received By btrobaug Date 2005-02-22 Time 12:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-15 Cont ID  
Sent By btrobaug Date 2004-10-15 Time 11:18 Rev Time 0.50
Received By btrobaug Date 2004-10-15 Time 11:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-24 Cont ID  
Sent By csiegber Date 2004-10-13 Time 14:34 Rev Time 0.50
Received By btrobaug Date 2004-03-24 Time 13:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-03-22 Time 11:01 Rev Time 0.75
Received By btrobaug Date 2004-02-19 Time 09:23 Sent To M
Notes
2004-02-19 00:00:00 
 DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDER FROM THE DISCONNECT TO
 THEMETER NEEDS A GROUND WIRE TO COMPLY
 WITH 250.122.
  
 2} PLEASE INDICATE THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLAN.
  
 3} THE RECEPTACLE IN THE MASTER BATH
 DOES NOT COMPLY WITH 210.52(D),MUST BE
 WITHIN 3'.
  
 4} BATH #2 NEEDS A SECOND RECEPTACLE TO
 COMPLY WITH 210.52(D).
  
 5} A SMOKE DETECTOR MUST BE ADDED
 OUTSIDE DEN/BEDROOM #3 TO COMPLY WITH
 8-1.4.1.6.2 NFPA-72.
  
 6} THERE MUST BE A SMOKE DETECTOR
 "OUTSIDE" THE DOORS ENTERING THE HALL
 TO THE MASTER SUITE. THE DETECTOR IN
 THE HALL IS NOT "OUTSIDE" BY DEFINITION
 BECAUSE THERE IS NO DOOR IN THE ARCH
 LEADING INTO THE BEDROOM.
  
 7} PLEASE SEE NOTE #16 SHEET C-1, ELEC.
 NOTES, REFERS TO SMOKE DETECTORS BEING
 FED FROM KITCHEN OR BATH LIGHTING. THIS
 IS ACCEPTABLE PER CODE, BUT THOSE
 CIRCUITS WOULD HAVE TO BE ON AN ARC
 FAULT BREAKER FOR THE DETECTORS LOCATED
 INSIDE THE BEDROOMS TO COMPLY WITH
 210.12.
  
 8} SEE NOTE #16 AND THE REFERENCE TO ARC
 FAULT FOR ALL"DWELLING ROOM RECEPTCLES"
 TO BE SURE THIS INDICATES THE ARCHITECTS
 INTENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-02-18 Cont ID  
Sent By adarroug Date 2005-02-18 Time 15:34 Rev Time 0.00
Received By adarroug Date 2005-02-18 Time 15:34 Sent To E
Notes
2005-02-18 00:00:00TO BT DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-13 Time 14:34 Rev Time 0.00
Received By csiegber Date 2004-10-13 Time 14:34 Sent To E
Notes
2004-10-13 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-01 Time 14:56 Rev Time 0.00
Received By csiegber Date 2004-04-01 Time 14:56 Sent To B
Notes
2004-04-01 00:00:00TO RM DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-22 Cont ID  
Sent By csiegber Date 2004-03-22 Time 11:01 Rev Time 0.00
Received By csiegber Date 2004-03-22 Time 11:01 Sent To E
Notes
2004-03-22 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-09 Cont ID  
Sent By mmclean Date 2004-02-12 Time 12:35 Rev Time 0.00
Received By rmcdouga Date 2004-02-11 Time 14:04 Sent To  
Notes
2004-02-13 00:00:00TO SFD RACK/E
2004-02-11 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-26 Cont ID  
Sent By btrobaug Date 2004-02-19 Time 11:32 Rev Time 0.50
Received By hmoser Date 2004-02-26 Time 19:26 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-26 Cont ID  
Sent By rmcdouga Date 2004-03-26 Time 16:42 Rev Time 0.15
Received By rmcdouga Date 2004-03-26 Time 16:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-28 Cont ID  
Sent By hmoser Date 2004-02-26 Time 19:26 Rev Time 0.33
Received By jleech Date 2004-02-28 Time 11:31 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-03-26 Cont ID  
Sent By rmcdouga Date 2004-03-26 Time 16:35 Rev Time 0.00
Received By rmcdouga Date 2004-03-26 Time 16:35 Sent To  
Notes
2004-03-26 00:00:00RESTAMP REVISION; FENCE MAXIMUM SIX FEET
 HEIGHT PER M. MCLEAN 3/26/04

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-12 Cont ID  
Sent By mmclean Date 2004-02-12 Time 12:35 Rev Time 0.00
Received By mmclean Date 2004-02-12 Time 12:35 Sent To I
Notes
***NONE***