Plan Review Details - Permit 04020284
Plan Review Stops For Permit 04020284
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-02 Cont ID  
Sent By lmartine Date 2004-07-02 Time 15:41 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-11 Cont ID  
Sent By jwitmer Date 2004-06-11 Time 08:42 Rev Time 2.22
Received By jwitmer Date 2004-06-11 Time 08:42 Sent To PC
Notes
2004-06-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020284
 ADD: 3308 45TH STREET
 CONT: STEVE THOMSON
 TEL: (561)758-3323
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) SHEET C-1 BUILDING INFORMATION:
 CORRECT: TABLE 500, TYPE IV, UNPROTECTED
 UNSPRINKLERED, ONE STORY, ALLOWABLE
 AREA IS 16,000 S.F.
  
 3)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) PLANS HAVE HAND WRITTEN INFORMATION
 ADDED TO A-2 AND STRUCTURAL SHEETS?IF
 THE DESIGN PROFESSIONAL ADDS THESE NOTES
 THEN BOTH THE ARCHITECT AND ENGINEER
 SHALL SIGN THEIR FULL NAME AND DATE
 THESE CHANGES, AND ADD THEM TO THE REVIS
 ION COLUMN, CLOUD OR DELTA EACH CHANGE.
  
 5) SHEET S-2 DETAIL 5 WHAT GUAGE IS THE
 VERTICAL METAL FRAMING IN THIS DETAIL?
  
 6) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR DOOR, GLAZED FRONT DOORS
 B) FIXED WINDOWS
 C) MULLIONS IF REQUIRED
 D) STANDING SEAM METAL ROOF
  
 7)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8) STORM SHUTTERS REMOVE REPORTS THAT
 ARE NOT APPLICABLE, IF THE ACCORDION
 SHUTTERS ARE TO BE USED THEN THE MANU-
 FACTURER ISTO FILL OUT LOCAL PRODUCT
 APPROVAL.
  
 9) REQUIREMENTS FOR STORM SHUTTERS:
 FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 10)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-10 Cont ID  
Sent By jwitmer Date 2004-03-09 Time 15:51 Rev Time 5.50
Received By jwitmer Date 2004-03-09 Time 14:13 Sent To PC
Notes
2004-03-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020284
 ADD: 3308 45TH STREET
 CONT: STEVE THOMPSON
 TEL: (561)758-3323
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
 PHASE (1)
  
 NOTE: UNLESS WORK WILL START WITHIN
 6 MONTH OF EACH OTHER A SEPERATE PERMIT
 WILL BE REQUIRED, ALSO CONSIDER WHEN A
 CERTIFICATE OF OCCUPANCY WILL BE
 ISSUED,WHEN BOTH PHASES ARE COMPLETE.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE
 REQUIRESAN ADDITIONAL 6". FINISH FLOOR
 ELEVATIONMINIMUM OF 16'-6" A-8 ZONE.
  
 3) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITEY KNOWN, OR IS IN
 QUESTIONTHE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 61G16.004 ARCH FIRM ADDRESS AND THE
 FIRMS LICENSE NUMBER REQUIRED ON THE
 TITLE BLOCK.
  
 4) PROVIDE THE UNITY OF TITLE FOR:
 74-42-43-01-02-000-0890
 74-42-43-01-02-000-0490
 74-42-43-01-02-000-0550
 OTHERWISE THERE WILL BE PROPERTY LINES
 THROUGH BUILDINGS REQUIRING RATED WALLS
 AND NO COMMUNICATING OPENINGS BETWEEN
 BUILDINGS, SEE TABLE 600.
  
 5) BLDG TYPE PLANS INDICATE A TYPE IV
 (1HR) ""UNPROTECTED"" EITHER UNPROTECTED
 OR (1HR) PROTECTED. FOR THIS REVIEW THE
 INTERPETATION AS "1HR PROTECTED/UNSPRINK
 LERED".SEE TABLE 600 FOR 1 HR RATING ON
 BEAMS, GIRDERS AND TRUSSES!!!!
  
 6)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY, BETWEEN THE SITE PLAN AND
 THE FLOOR PLAN, THE PHASE 1 BUILDING
 INDICATES THE USE OF A MEZZANINE ON THE
 SITE PLAN NOT SHOWN ON THE FLOOR PLAN?
  
 7) SHEET A-1.1 CORRECT THE MAXIMUM
 TRAVEL DISTANCE FOR UNSPRINKLERED BLDG.
  
 8) DISCREPANCY FLOOR PLAN VS THE EAST/
 WEST ELEVATIONS. THE ELEVATION WITH THE
 (4) LOUVERS IN THE WALL SHALL REQUIRE
 OPENING PROTECTIVES, 705.1.1.2.
  
 9) 1503.4.3. ROOF DRAINS, GUTTERS,
 SCUPPERS AND LEADERS SHALL BE SIZED
 AND DISCHARGED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
  
 10) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 11)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) OVERHEAD DOORS
 B) SWING EXTERIOR DOORS
 C) ROOFING ASSEMBLIES
 D) LOUVER( FIRE RATED 45MIN.)
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13) PLEASE NOTE THAT THE STEM WALL
 SHALL ALSO BE TREATED FOR TERMITES AS
 WELL AS SLAB.
  
 14) SHEET S-1 INDICATES A NOTE WHERE
 ADDITIONAL VERTICAL REBAR IS NECESSARY,
 BUT NOTHING IS INDICATED FOR THE NORTH
 AND SOUTH WALLS.
  
 15) SHEET A-5 INDICATES A TYPICAL WOOD
 FRAME WALL SECTION WITH WINDOW, IF NOT
 PART OF THIS PLAN REMOVE, IT IS OUTDATED
 WITH THE USE OF "HUGHES FASTENERS",
 OUT OF BUSINESS SINCE 1999.
  
 16) PROVIDE INFORMATION AS WHAT WILL BE
 FABRICATED, SICE FACTORY OCC, WHAT
 TYPE OF FUTURE EQUIPMENT WILL BE USED?
  
 PHASE II
  
 THE FIRST 5 COMMENTS FROM PHASE I ALSO
 PERTAIN TO THIS REVIEW.
  
 1) THE PLANS DO NOT INDICATE THE BLDG
 TYPE? PROTECED OR UNPROTECTED? FOR
 REVIEW PUPPOSES SINCE THE 1ST PHASE WAS
 TYPE IV 1 HR PROTECTED THIS REVIEW WILL
 TAKE THE SAME ASSUMPTION.
  
 2) SHEET A-3 INDICATES THE USE OF 5/8"
 FIRE SISTANT PLYWOOD TABLE 600 FOOTNOTE
 "E" INDICATES THAT THE WOOD BE " FIRE
 RETARDANT TREATED WOOD" THE PLANS ONLY
 INDICATE THE PLYWOOD, THE WOOD TRUSSES
 ALSO MUST MEET THIS REQUIREMENT.
  
 3) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLIONS VERTICAL
 C) SWING GLAZED DOORS
 D) SWING EXTERIOR DOORS/ NO GLAZING
 E) OVERHEAD DOORS
 F) STORM SHUTTERS IF GLAZING IS NOT
 LARGE MISSLE TESTED
 G) ROOFING ASSEMBLIES FOR FLAT AND
 METAL ROOFING
 H) TRUSS STRAPPING
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
  
 5) STRUCTURAL SHEET S-2 SECTION# 5,
 THE ARCHITECT TO ADD INFORMATION AFTER
 THE PLANS ARE PRINTED MUST SIGN NOT
 INTIAL PLANS AND DATE WHEN CHANGE IS
 MADE. WE ALSO NEED THE LOADS THAT THE
 STRAPIS TO HOLD, UPLIFT, GRAVITY OR
 HORIZONTAL LOADS. 1606.1.5 MAIN FORCE
 RESISTING SYSTEM. PROVIDE THE DIMENSIONS
 ON THE TRUSSES.WXH
  
 6) 2309.7.1 PROVIDE ATTIC VENTILATION.
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-06-02 Cont ID  
Sent By dpalmer Date 2004-06-02 Time 09:11 Rev Time 0.75
Received By dpalmer Date 2004-06-02 Time 09:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-20 Cont ID  
Sent By dpalmer Date 2004-02-20 Time 07:10 Rev Time 1.00
Received By dpalmer Date 2004-02-20 Time 07:10 Sent To  
Notes
2004-02-20 00:00:00************** UNSAT *************
  
 PLEASE NOTE: SCOPE OF WORK ON ONE APPLI-
 -CATION INCLUDES BOTH PHASES, THIS WILL
 PREVENT ONE OF THE BLDGS FROM BEING CO'D
 IF FINISHED FIRST.
 IF ONE MAY BE FINISHED BEFORE THE OTHER
 SEPARATE PERMIT APPLICATIONS MAY BE A
 THOUGHT. FYI
  
 ********* PHASE 1 ***********
  
 1)NOTE: PLEASE SHOW AND INCLUDE SIZE
 OF CONDUCTORS FROM MAIN TO PANEL.310.16
 PLEASE ALSO INCLUDE EQUIPMENT GROUNDING
 CONDUCTOR. 250.24, SIZE PER 250.122
  
 2)NOTE: PLEASE PROVIDE NOTE FOR USE
 OF "FUTURE" EQUIPMENT?
  
 3)NOTE: PLEAESE INCLUDE NAMES AND ALL
 LICENSE #'S ON TITLE BLOCK(S).
 PLEASE SEE 61G15-23.002 (ENGS) 61G1-16.
 004 (ARCHS).
 PLEASE INCLUDE REQ'D CERT OF AUTH #S/
 FIRM LICENSE # FOR ARCHITECURE FIRM.
 THIS IS REQ'D ON ALL SHEETS, ALL TRADES,
 AND ALL TITLE BLOCKS FOR ENINEERS, ARCH'
 S. (SITE ALSO). PLEASE SEE FS 481.219
 FOR ARCHS.
 SINGLE ENG IS NOT REQ'D TO HAVE CA#,
 BUT MUST PROVIDE OTHER INFORMATION.
  
 ****** PHASE 2 *****************
  
 1)NOTE; PLEASE SEE NOTE:3 FROM PHASE
 1 COMMENTS.
  
 2)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 @125% 215.3,230.42 FOR BOTH PHASES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-02-13 Cont ID  
Sent By mamini Date 2004-02-13 Time 13:08 Rev Time 0.50
Received By mamini Date 2004-02-13 Time 13:08 Sent To  
Notes
2004-02-13 00:00:00PASSED:
 1. SEE 03111339 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-05-25 Cont ID  
Sent By mcarsill Date 2004-05-25 Time 12:18 Rev Time 0.00
Received By mcarsill Date 2004-05-25 Time 12:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2004-02-11 Cont ID  
Sent By mcarsill Date 2004-02-11 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2004-02-11 Time 15:50 Sent To  
Notes
2004-02-11 00:00:001) PLEASE INDICATE HOW FIRE AND
 PARAMEDICAL EQUIPMENT ARE EXPECTED
 TO PASS THROUGH THE GATES.
  
 2) A KNOX-BOX WILL BE REQUIRED ON
 THE BUILDING.
  
 3) BUILDING ADDRESS REQUIRED.
  
 4) MAXIMUM TRAVEL DISTANCE NOTED
 ON PAGE A-1.1. IS INCORRECT. 1200
 FEET IS INCORRECT. PLEASE REVISE
 PLANS.
  
 5) PLEASE EXPLAIN PURPOSE OF PLASTIC
 CURTAIN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By csiegber Date 2004-06-28 Time 15:43 Sent To  
Notes
2004-06-28 00:00:00TO COMM BD#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-05-21 Cont ID  
Sent By csiegber Date 2004-05-21 Time 13:24 Rev Time 0.00
Received By csiegber Date 2004-05-21 Time 13:24 Sent To  
Notes
2004-05-21 00:00:00TO COMM BD#48

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-10 Cont ID  
Sent By mmclean Date 2004-02-09 Time 16:35 Rev Time 0.00
Received By jwitmer Date 2004-02-09 Time 09:18 Sent To PC
Notes
2004-02-11 00:00:00TO COMM BD#32
2004-02-09 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2004-06-08 Cont ID  
Sent By pkrauss Date 2004-06-08 Time 13:53 Rev Time 0.20
Received By pkrauss Date 2004-06-08 Time 13:53 Sent To  
Notes
2004-06-08 00:00:00PER CONVERSATION & FAX WITH OWNERS REP.
 BUILDING SPACE IS FOR LEASE PURPOSE.
 SEPARATE PERMIT FOR A TENANT BUILD-OUT.
 NO MECHANICAL WITH THIS PERMIT
 APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2004-06-07 Cont ID  
Sent By pkrauss Date 2004-06-07 Time 14:12 Rev Time 0.25
Received By pkrauss Date 2004-06-07 Time 13:57 Sent To  
Notes
2004-06-07 00:00:00DENIED:PHASE II 2ND REQUEST
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 601.4.
 PLANS DO NOT REFERENCE ANY TYPE OF
 VENTILATION FOR THE WAREHOUSE AREA OR
 THE "FUTURE SPACE".
  
 2.PROVIDE EQUIPMENT SCHEDULE &
 LOCATION OF EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2004-03-04 Cont ID  
Sent By pkrauss Date 2004-03-04 Time 09:28 Rev Time 0.30
Received By pkrauss Date 2004-03-04 Time 09:14 Sent To  
Notes
2004-03-04 00:00:00DENIED:
 MECHANICAL PERMIT REQUIRED.
  
 PLANS DO NOT REFERENCE MEANS OF
 VENTILATION.PROVIDE EQUIPMENT
 SCHEDULE OUTSIDE AIR CALCULATIONS,
 DUCT/GRILLE SIZE & LAYOUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-07-02 Cont ID  
Sent By kstevens Date 2004-07-02 Time 07:56 Rev Time 0.33
Received By kstevens Date 2004-07-02 Time 07:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-06-07 Cont ID  
Sent By kstevens Date 2004-06-07 Time 08:59 Rev Time 1.50
Received By kstevens Date 2004-06-07 Time 08:58 Sent To  
Notes
2004-06-07 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW: PER 61G1-16.004
 ARCHITEC'S ADDRESS IS REQUIRED ON TITLE
 BLOCK. FS 481.2055
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-17 Cont ID  
Sent By kstevens Date 2004-02-17 Time 15:27 Rev Time 1.25
Received By kstevens Date 2004-02-17 Time 15:27 Sent To  
Notes
2004-02-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURES PER TABLE 403.1
 2) SUBMIT DETAILS FOR TOILET ROOM PER
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 3) SUBMIT DETAIL FOR DRINKING FOUNTAIN
 PER 11-4.15 AND ALL SUBSECTIONS.
 4) SUBMIT CALCULATIONS FOR ROOF DRAINS
 PER SECTION 1106 AND ALL SUBSECTIONS.
 SHOW SIZE OF GUTTER PER TABLE 1106.6.
 SHOW SLOPE OF GUTTER AND SHOW HIGH POINT
 OF GUTTER. SHOW LOCATION AND SIZE OF ALL
 DOWNSPOUTS.
 5) SANITARY AND WATER RISER DIAGRAM ARE
 REQUIRED PER SECTION 104.3.1.1
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BLDG.
 7) PER 616G1-16.004 FIRM ADDRESS, FIRM
 LICENSE NUMBER REQUIRED. FS 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-17 Cont ID  
Sent By kstevens Date 2004-02-17 Time 12:37 Rev Time 2.00
Received By kstevens Date 2004-02-17 Time 12:37 Sent To  
Notes
2004-02-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 1) SHT A-1 TOILET ROOMS SHALL BE ACCESS-
 IBLE. SUBMIT DETAILS TO SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, AND
 11-4.22 AND ALL SUBSECTIONS.
 2) SHT A-1 DRINKING FOUNTAIN SHALL BE
 COMPLIANT WITH 11-4.15 AND ALL SUBSECT-
 IONS. SUBMIT DETAIL.
 3) SHT A-1 INDICATE THE USE OF THE
 SEPTIC TANKS. OUTFALL FROM SEPTIC TANKS
 SHALL DRAIN TO SANITARY SEWER SYSTEM,
 NOT STORMWATER RETENTION AREA.
 4) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF TANKS. WASTE
 ORD.2938-96. (561) 837-4074
 5) SUBMIT MANUF. SPECIFICATION SHEETS
 TO DETERMINE TYPE OF BACKFLOW DEVICE TO
 BE USED FOR FUTURE EQUIPMENT TO PREVENT
 CROSS CONNECTION. SECTION 608.13
 6) SUBMIT CALCULATIONS FOR ROOF DRAINAGE
 PER SECTION 1106 AND ALL SUBSECTIONS.
 INDICATE GUTTER SIZE, & SLOPE. SHOW THE
 HIGH POINT OF EACH GUTTER. TABLE 1106.6
 SHOW LOCATION AND SIZE OF ALL DOWNSPOUTS
 SIZE PER TABLE 1106.2
 7) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. JANITOR SINK
 SHALL DISCHARGE DOWN STREAM OF ALL
 TOILET ROOM FIXTURES. (SEE SANITARY RIS-
 ER DIAGRAM AND FLOOR PLAN). SEC 909.1
 8) SHT P-1 SANITARY RISER DIAGRAM, THE
 LAVS ARE NOT VENTED. VENT REQUIRED AT
 LAVS PER SECTION 901.2.1
 9) SHT P-1 WATER RISER DIAGRAM, SHUT-OFF
 VALVES REQUIRED AT EACH HOSE BIBB PER
 SECTION 606.2(2).
 10) PER 61G1-16.004 FIRM ADDRESS, FIRM
 LICENSE NUMBER. FS 481.2055
 11) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-09 Cont ID  
Sent By mmclean Date 2004-02-09 Time 16:35 Rev Time 0.00
Received By mmclean Date 2004-02-09 Time 16:35 Sent To I
Notes
2004-02-09 00:00:00APPROVED BY JOSH LONG PLANNER 659-8031 M