Plan Review Details - Permit 04020179
Plan Review Stops For Permit 04020179
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-07-12 Cont ID  
Sent By lsmith Date 2004-03-29 Time 08:11 Rev Time 0.25
Received By mjacobs Date 2004-07-12 Time 13:05 Sent To  
Notes
2004-07-12 00:00:00WINDOW SUBMITTALS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By jleech Date 2004-02-28 Time 08:27 Rev Time 0.00
Received By lsmith Date 2004-03-09 Time 09:43 Sent To  
Notes
2004-03-09 00:00:00BUILDING PLAN REVIEW: FAILED
  
 1. REVISE NOTE #11 UNDER PLAN NOTES ON
 C1 TO INCLUDE AREAS IN WIND BORNE DEBRIS
 REGIONS WHICH ALSO REQUIRE IMPACT
 PROTECTION FOR GLAZEDOPENINGS. SEE
 FBC 1606.1.4.
  
 2. REVISE NOTE #15 UNDER FRAMING NOTES
 ON C1 TO SPECIFY THAT HIGH RIB METAL
 LATH IS REQUIRED TO BE ATTACHED AT EACH
 RIB (4" O.C.) PER ASTM C 1063.
  
 3. SPECIFY THE TRUSS BOTTOM CORD LIVE
 LOAD ON THE PLANS. FBC TABLE 1604.1
 REQUIRES ATTICS WITHOUT STORAGE TO HAVE
 A LIVE LOAD OF 10 PSF AND 30 PSF FOR
 ATTICS WITH STORAGE.
  
 4. GLASS BLOCK ON ZERO LOT LINE MUST BE
 ONE HOUR FIRE RATED. SPECIFY THIS ON
 PLANS.
  
 5. REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL TO STATE THAT THEY ARE FASTENED
 THROUGH THE BUCK AND NOT TO THE BUCK.
  
 6. SPECIFY THE LENGTH/EMBED DEPTH OF THE
 1/2" ANCHOR BOLTS FOR THE GARAGE DOOR
 BUCKS ON A4.
  
 7. SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO CONDITIONED SPACE IS
 INSULATED OR SOLID CORE AS REQUIRED BY
 FBC CHAPTER 13 SECTION 603.
  
 8. REVISE THE SEMCO TRUSS CONNECTOR
 SPECIFIED IN DETAIL 9 ON A9 TO A
 CURRENT ANCHOR WITH STATE OR LOCAL
 PRODUCT APPROVAL.
  
 9. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 WWW.FLORIDABUILDING.ORG.
  
 10. THE GARAGE DOOR ON PLANS IS 16' WIDE
 THE SUBMITTAL FROM CLOPAY (DRAWING) IS
 FOR A MAXIMUM DOOR WIDTH OF 9'. PLEASE
 SUBMIT THE CORRECT DRAWING AND PRODUCT
 APPROVALS.
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-10-08 Cont ID  
Sent By btrobaug Date 2004-10-08 Time 16:44 Rev Time 0.50
Received By btrobaug Date 2004-10-08 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-27 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:35 Rev Time 0.50
Received By btrobaug Date 2004-03-27 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-17 Cont ID  
Sent By jleech Date 2004-03-20 Time 10:27 Rev Time 0.50
Received By dpalmer Date 2004-02-17 Time 09:07 Sent To M
Notes
2004-02-17 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT GFI RECEPT.
  
 2)NOTE: PLEASE SEE RECEPT IN MASTER
 BATH TO BE W/IN 3' FROM LAV. 210.52D
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. PER 250.24, SIZE PER 250.122
  
 4)NOTE: PLEASE SEE MISSING LT FIXTURE
 IN HALL OUTSIDE LAUNDRY ROOM. REQ'D
 PER 210.70 LS 101 5-8.
  
 5)NOTE: PLEASE SEE PLANS ARE MISSING ALL
 SERVICE EQUIPMENT. METER/ MAIN/ PANEL
 NOT SHOWN.
  
 6)NOTE: PLAN INDICATE POOL PUMP YET,
 PANEL SCHEDULE DOES NOT LIST POOL
 EQUIPMENT?
  
 7)NOTE: PLEASE HAVE PLANS SIGNED BY THE
 ARCH OF RECORD. SIGNATURE ON PLANS DO
 NOT CORRELATE WITH SIGNATURE ON FILE FOR
 ARCH. PER FS 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 12:35 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 12:35 Sent To E
Notes
2004-10-04 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-08-09 Cont ID  
Sent By csiegber Date 2004-08-09 Time 16:19 Rev Time 0.00
Received By csiegber Date 2004-08-09 Time 16:19 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 16:33 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 16:33 Sent To P
Notes
2004-03-16 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-09 Cont ID  
Sent By mmclean Date 2004-02-09 Time 12:53 Rev Time 0.00
Received By lsmith Date 2004-02-05 Time 14:51 Sent To  
Notes
2004-02-11 00:00:00TO SFD RACK/E
2004-02-05 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-21 Cont ID  
Sent By dpalmer Date 2004-02-17 Time 09:07 Rev Time 0.50
Received By rregueir Date 2004-02-21 Time 12:40 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-20 Cont ID  
Sent By csiegber Date 2004-08-09 Time 16:19 Rev Time 0.33
Received By jleech Date 2004-03-20 Time 10:26 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-28 Cont ID  
Sent By csiegber Date 2004-03-16 Time 16:33 Rev Time 0.33
Received By jleech Date 2004-02-28 Time 08:26 Sent To B
Notes
2004-02-28 00:00:00DENIED;
 HAVE PLANS SIGNED WITH SIGNATURE FROM
 ARCH OF RECORD PER FS 481.221.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-05 Time 14:51 Rev Time 0.00
Received By mmclean Date 2004-02-09 Time 12:53 Sent To I
Notes
***NONE***