| Plan Review Stops For Permit 04020025 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2004-07-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-03-26 |
Time |
14:44 |
Rev Time |
0.25 |
| Received By |
mjacobs |
Date |
2004-07-12 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2004-07-12 00:00:00 | WINDOW SUBMITTALS OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2004-03-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-03-24 |
Time |
12:35 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
2004-03-09 |
Time |
09:58 |
Sent To |
|
|
| Notes |
| 2004-03-09 00:00:00 | DENIED | | | | | | SAME COMMENTS AS PERMIT # 04010916 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-10-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2004-10-12 |
Time |
08:28 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-10-12 |
Time |
08:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-09-21 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-04 |
Time |
12:56 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-09-21 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2004-09-21 00:00:00 | | | | PLEASE SHOW THE LOCATION OF PANEL"B" ON | | | THE PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2004-03-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-14 |
Time |
09:28 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2004-03-24 |
Time |
12:35 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2004-02-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-16 |
Time |
15:56 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-02-17 |
Time |
06:02 |
Sent To |
M |
|
| Notes |
| 2004-02-17 00:00:00 | *************** UNSAT *********** | | | | | | 1)NOTE: PLEASE HAVE PLANS SIGNED,DATED | | | AND SALED BY THE ARCH OF RECORD. | | | SIGNATURE DOES NOT COORALET WITH | | | SIGNATURE ON FILE. | | | PER FS 481.221 | | | | | | 2)NOTE: SD MISSING OUTSIDE BEDROOM #3 | | | NFPA-72 8-1.4.1.6.2 | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL | | | PER 250.110,250.24 SIZE PER 250.122 | | | | | | 4)NOTE: PLEASE SEE GFI TO BE W/IN 3' | | | FROM LAV IN MASTER AND BATH #2. | | | 210.52 | | | | | | 5)NOTE: PLEASE SEE PLANS DO NOT SHOW | | | MAIN NEXT TO METER? PLEASE CORRELATE | | | WITH RISER. | | | | | | 6)NOTE: PLEASE SEE MISSING RECEPT IN | | | WHAT APPEARS TO BE A BEDROOM #4. 210.52 | | | 2' OF WALL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-10-04 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-10-04 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-10-04 |
Time |
12:56 |
Sent To |
E |
|
| Notes |
| 2004-10-04 00:00:00 | TO BT DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-09-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-09-14 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-09-14 |
Time |
09:27 |
Sent To |
E |
|
| Notes |
| 2004-09-14 00:00:00 | TO BT DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2004-03-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-03-16 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-03-16 |
Time |
15:56 |
Sent To |
E |
|
| Notes |
| 2004-03-16 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-03-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-02-04 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2004-02-02 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2004-02-05 00:00:00 | TO SFD RACK/E | | 2004-02-02 00:00:00 | TO Z |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-02-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-02-17 |
Time |
06:40 |
Rev Time |
0.50 |
| Received By |
rregueir |
Date |
2004-02-21 |
Time |
11:45 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2004-03-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2004-03-26 |
Time |
14:41 |
Rev Time |
0.15 |
| Received By |
rmcdouga |
Date |
2004-03-26 |
Time |
14:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2004-02-28 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2004-02-21 |
Time |
11:46 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2004-02-28 |
Time |
08:21 |
Sent To |
B |
|
| Notes |
| 2004-02-28 00:00:00 | DENIED; | | | HAVE PLANS SIGNED WITH SIGNATURE FROM | | | ACCH OF RECORD PER FS 481.221. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2004-02-04 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-02 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-02-04 |
Time |
10:23 |
Sent To |
I |
|
| Notes |
|
|