| 2004-03-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-DESIGN CRITERIA: INCLUDE ATTIC LIVE |
| | LOAD: 30PSF OR 10PSF AS REQ'D BY TABLE |
| | 1604.1 FBC 2001. |
| | 3-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| | ENTRY DOORS SHOWING SIZE OF BUCK REQ'D |
| | TO CLOSE GAP GIVEN THE MASONRY OPENING |
| | SPECIFIED. SEC. 104.2.1.2 OF CITY |
| | AMENDMENTS TO FBC 2001. |
| | 4-ROOF SHEATHING NOTE ON DRAWINGS A3: |
| | SEE FIGURE 1606.2(C)FBC 2001 FOR ZONE |
| | 3 LOCATION OTHER THAN JUST AT GABLE |
| | ENDS AND REVISE NOTE AS REQUIRED. |
| | 5-PROVIDE DETAIL/SPECS FOR INSTALLATION |
| | OF CEILING AT ENTRY AND REAR PORCH. |
| | SEE ASTM C926 AND ASTM C-1063. |
| | SECTION 2504.2 FBC 2001. |
| | SPECIFY FASTENER SIZE AND SPACING. |
| | 6-REVISE ENERGY CALCULATIONS. SEE SEC. |
| | 604.1.A.1 CHAPTER 13 FBC 2001 FOR |
| | AREAS TO BE CONSIDERED FOR UNDER ATTIC |
| | AREAS. |
| | 7-PROVIDE FLORIDA OR LOCAL PRODUCT APPRO |
| | VAL FOR ALL STRUCTURAL CONNECTORS. |
| | 8-PROVIDE PRODUCT APPROVAL FOR FRENCH |
| | DOORS WITH TRANSOM ABOVE ASSEMBLY AS |
| | SHOWN ON PLANS. |
| | 9-SPECIFY ROOF TILE FASTENERS AS REQ'D |
| | BY SEC. 104.2.1.1 CITY AMENDMENTS TO |
| | FBC AND SEC. 1606.3 FBC 2001. |
| | 10-SPECIFY FASTENERS FOR 2X4 BLOCKING AT |
| | ARCHED & OVAL FRAMING DETAILS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 11-SPECIFY 7/8" MIN. STUCCO THICKNESS AT |
| | FRAMED WALLS AS REQ'D BY ASTM C-926. |
| | 12-PROVIDE COMPLETE KNEE WALL FRAMING |
| | DETAILS. SPECIFY ALL FASTENERS. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | 13-PROVIDE UPLIFT CALCS FOR SIZE OF |
| | FOOTING SPECIFIED FOR COLUMN AT REAR |
| | PORCH. SEC. 2103.1(EXCEPTION 7.1)FBC |
| | & SEC 104.2.1.2 CITY AMENDMENTS TO FBC |
| | 14-STORM SHUTTERS: A)PROVIDE FLORIDA OR |
| | LOCAL PRODUCT APPROVAL. |
| | B)PROVIDE KEY PLAN AND COMPLETE INSTALLA |
| | TION SCHEDULE SHOWING EMERGENCY EGRESS |
| | C)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE & |
| | SPACING TO BE USED. |
| | 15-SPECIFY SAFETY GLASS AT MASTER BATH |
| | WINDOW. SEC. 2405.2 FBC 2001. |
| | 16-PROVIDE CORRECT DETAIL FOR STEEL COLS |
| | @ ENTRY PORCH. DETAIL F/6 DOESN'T WORK |
| | 17-ROOF FRAMING PLAN: CLARIFY HOW ARE |
| | TRUSSES AT REAR PORCH SUPPORTED IF THE |
| | RE IS NOT BEAM TO SUPPORT THEM. SEE |
| | COMMENTS ON PLAN. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 18-SITE PLAN ON DWG A6: CLARIFY SETBACK |
| | DIMENSIONS. SEE COMMENTS ONPLAN. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |