Plan Review Details - Permit 04011425
Plan Review Stops For Permit 04011425
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-03-08 Time 11:25 Rev Time 15.00
Received By lmartine Date   Time   Sent To  
Notes
2004-02-18 00:00:00 
 'PROVISO'
 -------
 SUBMIT 2 COMPLETE SIGNED AND SEALED
 DRAWINGS.
  
 PROVIDE PRODUCT APPROVALS FOR ANY
 EXTERIOR GLAZING AND OR DOORS.
  
 UPDATE ALL REFERENCES FROM THE STANDARD
 BUILDING CODE TO THE FLORIDA BUILDING
 CODE, ON THE DRAWINGS AND
 SPECIFICATIONS.
  
 PROVIDE WELDERS CERTIFICATE.
  
 ALL HANDRAILS AND GUARDRAIL SYSTEMS
 SHALL BE DESIGNED IN ACCORDANCE WITH
 SECT. 1608.2, 2001 FLA. BUILDING CODE.
  
  
  
  
 LUIS MARTINEZ
 805-6710

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-02-17 Cont ID  
Sent By dpalmer Date 2004-02-17 Time 13:08 Rev Time 0.25
Received By dpalmer Date 2004-02-17 Time 13:08 Sent To  
Notes
2004-02-17 00:00:00PASSED UNDER ORIG SUBMITTAL AND REVIEW
 JAN 02.
 CODE HAS CHANGED TO 2002 NEC, WORK TO
 ADJUST ACCORD.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2004-02-17 Cont ID  
Sent By mamini Date 2004-02-17 Time 14:22 Rev Time 0.50
Received By mamini Date 2004-02-17 Time 14:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-02-10 Cont ID  
Sent By mcarsill Date 2004-02-10 Time 14:42 Rev Time 0.00
Received By mcarsill Date 2004-02-10 Time 14:42 Sent To  
Notes
2004-02-10 00:00:001) BOLLARDS SHOULD BE AT LEAST 7 1/2
 FEET TO THE FRONT AND SIDES OF THE
 FIRE HYDRANTS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-30 Cont ID  
Sent By adarroug Date 2007-05-30 Time 10:09 Rev Time 0.00
Received By adarroug Date 2007-05-30 Time 10:09 Sent To P
Notes
2007-05-30 10:10:04TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-08 Cont ID  
Sent By csiegber Date 2004-03-08 Time 11:25 Rev Time 0.00
Received By csiegber Date 2004-03-08 Time 11:25 Sent To B
Notes
2004-03-08 00:00:00TO LM DESK/RESUB/PROVISO

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-17 Cont ID  
Sent By pkrauss Date 2004-02-17 Time 14:09 Rev Time 0.40
Received By pkrauss Date 2004-02-17 Time 14:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pschmitz Date 2007-05-25 Time 11:39 Sent To  
Notes
2007-05-25 11:40:25INVALID PERMIT NUMBER
 SEE COPY OF CORRECT PERMIT NUMBERS.PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-18 Cont ID  
Sent By kstevens Date 2004-02-18 Time 09:56 Rev Time 0.25
Received By kstevens Date 2004-02-18 Time 09:56 Sent To  
Notes
2004-02-18 00:00:00PASSED ON PREVIOUS REVIEW 1-14-02
 NEW PLANS SHALL COMPLY WITH FBC-2001
 PLUMBING.