| Plan Review Stops For Permit 04011366 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-01-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-28 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-28 |
Time |
14:59 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2004-02-11 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-28 |
Time |
14:59 |
Rev Time |
0.33 |
| Received By |
pkrauss |
Date |
2004-02-11 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2004-02-11 00:00:00 | PROVISO: | | | 2ND FLOOR - EXISTING BEDROOM WITH 200 | | | CFM OF SUPPLY AIR WILL REQUIRE A LARGER | | | TRANSFER.PER 2001 FBC(M) 601.4 | | | EXCEPTION #2, TRANSFER GRILLES SHALL | | | USE 50 SQUARE INCHES PER 100 CFM OF | | | SUPPLY AIR.PLAN INDICATES A 12" X 6" | | | WHICH EQUALS ONLY 72 SQUARE INCHES. | | | PLEASE REVISE PLANS TO COMPLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|