Plan Review Details - Permit 04011308
Plan Review Stops For Permit 04011308
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 08:40 Rev Time 0.66
Received By alange Date 2004-04-22 Time 08:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-04-08 Cont ID  
Sent By alange Date 2004-04-08 Time 14:02 Rev Time 1.00
Received By alange Date 2004-04-08 Time 14:02 Sent To E
Notes
2004-04-08 00:00:00DENIED
 1.SIGN ENERGY CALC'S.
  
 2.WINDOW BUCKS SHALL COMPLY WITH
 FBC1707.4.4.2 BUCKS SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW SUCH
 THAT FULL SUPPORT OF THE FRAME IS
 PROVIDED.SHOW ON DETAIL.
  
 3.SHOW GRADE ON FOOTING DETAIL AND
 SHOW DEPTH OF FOOTING AND DISTANCE
 FROM GRADE TO FINISH FLOOR.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 8056672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-02 Cont ID  
Sent By pkrauss Date 2004-02-12 Time 07:32 Rev Time 1.50
Received By alange Date 2004-03-02 Time 15:26 Sent To  
Notes
2004-03-02 00:00:00DENIED
 1.COMPLETE ENERGY CALCULATION FORM
 AND SIGN 2 COPIES.
  
 2.SUBMIT DETAIL SHOWING HEADERS WITH
 SIZE AND TYPE OF FRAMING AND TYPE OF
 STRAPS USED.
  
 3.WINDOW BUCK SHALL COMPLY WITH
 FBC 1707.4.4.2SUBMIT A DRAWING DETAIL.
  
 4.SUBMIT A SITE PLAN SHOWING NEW
 STRUCTURE IN RELATIONSHIP TO OTHER
 EXISTING BUILDINGS SO THAT WE CAN CHECK
 FOR POSSIBLE TABLE 600 ISSUES.
  
 5.FOUNDATION PLAN... FOOTING STOPS
 BEFORE EXISTING BUILDING.PLEASE VERIFY
  
 6.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ANY QUESTIONS PLEASE CALL...
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-04-09 Cont ID  
Sent By btrobaug Date 2004-04-09 Time 15:15 Rev Time 0.33
Received By btrobaug Date 2004-04-09 Time 14:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-06 Cont ID  
Sent By alange Date 2004-04-08 Time 14:04 Rev Time 0.50
Received By dpalmer Date 2004-02-06 Time 12:53 Sent To P
Notes
2004-02-06 00:00:00**************** UNSAT *********
  
  
 1)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR ATTACHED TO NEW FOOTER STEEL.
 250.50
  
 2)NOTE: PLEASE VERIFY KW RATING/LOAD
 SHOWN FOR AHU. 6.5KW IS NOT A STANDARD
 SIZE.
  
 3)NOTE: PLEASE INCLUDE ALL REQ'D INFOR-
 -MATION ON TITLE BLOCK AS SET FORTH
 IN FAC 61G1-16.004 PER FS 481
  
 4)NOTE: PLEASE SEE KW LOAD SHOWN FOR
 WATER HEATER AT 2.5 KW. PLEASE ALSO
 VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-06 Time 17:02 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 17:01 Sent To E
Notes
2004-04-06 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-02 Cont ID  
Sent By mmclean Date 2004-04-06 Time 15:29 Rev Time 0.00
Received By csiegber Date 2004-04-02 Time 08:54 Sent To Z
Notes
2004-04-02 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-02 Cont ID  
Sent By csiegber Date 2004-02-02 Time 09:07 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 09:07 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-28 Cont ID  
Sent By mmclean Date 2004-01-30 Time 15:30 Rev Time 0.00
Received By csiegber Date 2004-01-28 Time 11:16 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-12 Cont ID  
Sent By kstevens Date 2004-02-09 Time 17:09 Rev Time 0.55
Received By pkrauss Date 2004-02-12 Time 06:57 Sent To B
Notes
2004-02-12 00:00:00PROVISO:
 MECHANICAL PERMIT REQUIRED.PLEASE
 PROVIDE INFORMATION FOR THE VENTILATION
 TO THIS AREA.INDICATE NEW A/C DUCT
 SIZE, MATERIAL AND LAYOUT AS WELL AS
 GRILLE SIZE AND LOCATION.PROVIDE
 INFORMATION ON THE EXISTING A/C SYSTEM
 THAT IS INDICATED ON THE FORM 600C.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2004-02-09 Cont ID  
Sent By dpalmer Date 2004-02-06 Time 12:53 Rev Time 0.25
Received By kstevens Date 2004-02-09 Time 17:09 Sent To M
Notes
2004-02-09 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-06 Cont ID  
Sent By mmclean Date 2004-04-06 Time 15:29 Rev Time 0.00
Received By mmclean Date 2004-04-06 Time 15:29 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2004-01-30 Cont ID  
Sent By csiegber Date 2004-04-02 Time 08:54 Rev Time 0.00
Received By mmclean Date 2004-01-30 Time 15:30 Sent To I
Notes
2004-01-30 00:00:00DENIED, NEED TO SHOW ADDITION ON SURVEY