Plan Review Details - Permit 04011300
Plan Review Stops For Permit 04011300
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-04-20 Cont ID  
Sent By alange Date 2004-04-20 Time 10:05 Rev Time 1.00
Received By alange Date 2004-04-20 Time 10:05 Sent To  
Notes
2004-04-20 00:00:00REVISION OK...

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-01 Cont ID  
Sent By csiegber Date 2004-04-16 Time 15:13 Rev Time 0.00
Received By alange Date 2004-04-01 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-26 Cont ID  
Sent By alange Date 2004-03-26 Time 10:41 Rev Time 0.75
Received By alange Date 2004-03-26 Time 10:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-09 Cont ID  
Sent By btrobaug Date 2004-03-25 Time 16:43 Rev Time 2.25
Received By alange Date 2004-03-09 Time 13:58 Sent To  
Notes
2004-03-09 00:00:00DENIED
 1. THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
 2.ENERGY CALCULATIONS NOT SIGNED.
 3.NOT ALL OF THE PAGES OF THE PLANS
 ARE SIGNED AND SEALED FS.471.025 471.221
 4.SIMPSOM HSTA 20 NO SUCH SIPMSON
 PRODUCT.SIMPSON ST 18 REQ. 14 -16D
 NAILS.
  
 ANY QUESTIONS CALL
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-12-15 Cont ID  
Sent By btrobaug Date 2004-12-15 Time 11:26 Rev Time 0.50
Received By btrobaug Date 2004-12-15 Time 11:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-01 Cont ID  
Sent By btrobaug Date 2004-04-01 Time 07:38 Rev Time 1.00
Received By btrobaug Date 2004-04-01 Time 06:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-03-25 Cont ID  
Sent By btrobaug Date 2004-03-25 Time 16:43 Rev Time 0.75
Received By btrobaug Date 2004-03-25 Time 16:08 Sent To B
Notes
2004-03-25 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~`
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 2} THE FEEDERS ON THE RISER DIAGRAM
 LISTED AT #00 ARE NOT RECOGNIZED AS AWG
 PER 110.6. SEE 310.16 OR 310.15(B)(6)
 FOR WIRE SIZE SELECTIONS.
  
 3} THE WATER HEATER ON THE PANEL
 SCHEDULE IS RATED AT 9000 WATTS, THE
 WIRE SIZE @ #10 DOES NOT COMPLY WITH
 310.16.
  
 4} THE TOTAL WATTAGE SHOWN FOR THE ARC
 FAULT BREAKERS IS INCORRECT FOR THE OCP
 AND WIRE SIZE LISTED FOR SAME. SEE
 310.16.
  
 5} THE OCP FOR THE AC COMPRESSORS LISTED
 @ 1200 WATTS(?) DOES NOT COMPLY WITH
 310.16.
  
 6} THE SMOKE DETECTORS BY THE GARAGE AND
 SECOND FLOOR BATH DO NOT COMPLY WITH
 8-1.4.2 NFPA-72, AS STATED IN THE
 PREVIOUS REVIEW, THEY MUST BE A MINIMUM
 OF 3'.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-03-12 Time 10:47 Rev Time 1.00
Received By dpalmer Date 2004-02-06 Time 15:22 Sent To M
Notes
2004-02-09 00:00:00**************** UNSAT ***************
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE SEC'S AND FEEDERS
 SHOWN AT #00. PLEASE SEE AWG STANDARD
 SIZES IN NEC 310.16. 3/0'S?
  
 4)NOTE: PERMIT APPLICATION IS FOR A NEW
 2-STORY RES. HOWEVER, RISER DIAGRAM NOTE
 -S BEING EXISTING. PANEL SCHEDULE NOTES
 NEW AND EXISTING??? PLEASE CLARIFY THIS?
  
 5)NOTE: PLEASE SIZE SIZING OF CONDUIT
 FOR 3-3/0'S AND AN EQUIPMENT GROUNDING
 CONDUCTOR REQ'D FROM MAIN TO PANEL.
 CONDUIT SHOWN AS 1 1/2".
 PLEASE ALSO SEE THAT LOCATION OF PANEL
 IS NOT SHOWN ON PLANS AND THEREFORE
 MAIN MAY OR MAY NOT BE REQ'D.
 PLEASE SEE LOCAL AMENDMENTS, 210.70
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S ARE PERMITTED INSIDE THE HOUSE.
  
 6)NOTE: PLEASE LIST ALL THE REQ'D ARC
 FAULT PROECTED CIRCUITS ON PANEL SCHED-
 -ULE. PER 210.12 2002 NEC
  
 7)NOTE: PLEASE SEE PLANS ON A-10 REF
 ELECTRICAL CODE PER SEC .2701??
 PLEASE SEE THAT PLANS ARE PER 2002 NEC.
  
 8)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS PER 210.52E.
  
 9)NOTE: PLEASE SEE REQ'D MISSING EGRESS
 LIGHTING AND MEANS OF CONTROL PER 210.70
 AND LS 101 5-8
  
 10)NOTE: PLEASE CLARIFY CORNER IN WHICH
 KITCHEN COUNTER TOP INTERSECTS WITH
 PENINSULAR? IS THIS COUNTERSPACE OR AN
 EMPTY CORNER? PLEASE SEE 210.52C1 FOR
 RECEPT SPACING IF COUNTER-TOP.
  
 11)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A6 THIS INCLUDES RECEPT
 SERVING PENINSULAR.
  
 12)NOTE: PLEASE SEE MISSING RECEPT(S)
 FOR BATHROOM(S) PER 210.52D AND LIST
 PER 210.11C3. MUST BE DEDICATED, 20A AND
 #12.
  
 13)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C EQUIPMENT. PER 210.63
 PLANS ONLY SHOW ONE AHU IN ATTIC ON 2ND
 FLOOR. PLEASE SHOW 2ND UNIT. DISC'S TO
 BE SHOWN PER 440.11
  
 14)NOTE: PLANS THAT CONTAIN A TITLE
 BLOCK FOR AND ENGINEER OR ARCH MUST BE
 SIGNED, DATED AND SEALED BY THE DESIGNER
 OF RECORD. PER FS 471.025 AND 481.221
  
  
 PLEASE SEE THAT PLANS DO NOT CONTAIN
 ANY LOW VOLTAGE ITEMS. (TV,PHONE ETC)
 PLEASE SHOW AT THIS TIME OR SEPARATE
 PLANS WILL BE REQ'D WITH LV PERMIT
 APPLICATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-16 Cont ID  
Sent By csiegber Date 2004-04-16 Time 15:13 Rev Time 0.00
Received By csiegber Date 2004-04-16 Time 15:13 Sent To B
Notes
2004-04-16 00:00:00TO AL DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-12 Cont ID  
Sent By csiegber Date 2004-03-12 Time 10:47 Rev Time 0.00
Received By csiegber Date 2004-03-12 Time 10:47 Sent To E
Notes
2004-03-12 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-09 Cont ID  
Sent By mmclean Date 2004-01-29 Time 12:36 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 16:25 Sent To  
Notes
2004-01-29 00:00:00TO SFD RACK/E
2004-01-27 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-21 Cont ID  
Sent By jleech Date 2004-02-09 Time 15:18 Rev Time 0.33
Received By rregueir Date 2004-02-21 Time 10:42 Sent To B
Notes
2004-02-21 00:00:00NO MECHANICAL PLANS WERESUBMITTED WITH
 THIS APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-09 Cont ID  
Sent By jleech Date 2004-02-09 Time 15:18 Rev Time 0.33
Received By jleech Date 2004-02-09 Time 15:18 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-29 Cont ID  
Sent By mmclean Date 2004-01-29 Time 12:36 Rev Time 0.00
Received By mmclean Date 2004-01-29 Time 12:36 Sent To I
Notes
***NONE***