Plan Review Details - Permit 04011169
Plan Review Stops For Permit 04011169
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-12 Cont ID  
Sent By mmclean Date 2004-05-12 Time 09:28 Rev Time 2.00
Received By jgomez Date 2004-05-12 Time 11:40 Sent To PC
Notes
2004-05-12 00:00:00BUILDING REVIEW PROVISO:
 1-A)PROVIDE COMPLETE PRODUCT APPROVAL
 FOR FRENCH DOORS WITH SIDELITES AND
 TRANSOM ABOVE SINGLE ASSEMBLY AS SHOWN
 ON PLANS UNDER A SEPARATE PERMIT.
 B)PROVIDE PRODUCT APPROVAL FOR FIXED
 GLASS WITH LONG DIMENSION AS SHOWN ON
 PLANS (PROVIDE THIS ON ABOVE PERMIT).
 C)PROVIDE COMPLETE INFORMATION FOR ENTRY
 DOORS PRODUCT APPROVAL AS WELL.
 2-CEILING INSTALLATION AT ENTRY AND REAR
 PORCHES: CLARIFY WHAT'S A 1"X2" 16 GA
 PNEUMATIC FASTENER AS SPECIFIED ON
 PLANS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 3-PROVIDE CURRENT UL LISTING & COMPLETE
 SPECS FOR FIREPLACE. SEC 2806 FBC 2001
 4-SPECIFY MIN. 7/8" STUCCO THICKNESS AT
 FRAMED WALLS AS REQUIRED BY ASTM C-926
 5-COMPLETE INFORMATION ON DETAIL F/6:
 SPECIFY HOW MUCH EMBEDMENT IS REQ'D
 FOR ANCHORS AT BOTTOM PLATE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-15 Cont ID  
Sent By csiegber Date 2004-04-28 Time 11:49 Rev Time 3.50
Received By jgomez Date 2004-03-12 Time 18:49 Sent To PC
Notes
2004-03-12 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-DESIGN CRITERIA: INCLUDE THE ATTIC
 LIVE LOAD. 30PSF OR 10PSF. SEE TABLE
 1604.1 FBC 2001.
 3-PROVIDE BBQ UL LISTING AND SPECS.
 SECTION 2808 FBC 2001.
 4-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ENTRY DOORS SHOWING SIZE OF BUCK REQ'D
 TO CLOSE GAP GIVEN THE OPENING SIZE.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-ROOF SHEATHING NOTE ON DRAWING A3:
 A)REVISE MINIMUM THICKNESS. SEE TABLE
 2306.1 CITY AMENDMENTS TO FBC 2001
 B)SEE FIGURE 1606.2(C) FBC 2001 FOR ROOF
 AREAS TO BE CONSIDERED ZONE 3 AND
 REVISE NOTE AS REQUIRED.
 6-PROVIDE DETAIL/SPECS FOR CEILING INSTA
 LLATION AT ENTRY AND REAR PORCH. SEE
 ASTM C-926 AND ASTM C-1063 AS REQUIRED
 BY SEC. 2504.2 FBC 2001.
 7-REVISE ENERGY CALCULATIONS. SEE SEC.
 604.1.A.1 CHAPTER 13 FBC 2001 FOR
 AREA TO BE CONSIDERED FOR UNDER ATTIC
 AREA.
 8-PROVIDE FLORIDA OR LOCAL PRODUCT APPRO
 VAL FOR: A)ALL STRUCTURAL CONNECTORS.
 B)FIXED WINDOWS WITH SIZE AS SHOWN ON
 PLANS. EG. SEE KITCHEN WINDOW.
 C)PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOORS WITH TRANSOM ABOVE ASSEMBLY AS
 SHOWN ON PLAN.
 9-SPECIFY ROOF TILE FASTENERS AS REQ'D
 BY SEC. 104.2.1.1 CITY AMENDMENTS TO
 FBC 2001 AND SEC. 1606.3 FBC 2001.
 10-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR FIREPLACE. SEC. 2806 FBC 2001.
 11-DESIGN PRESSURES FOR OPENINGS SHOWN
 ON SEPARATE SHEET DON'T MATCH THOSE
 SHOWN ON PLANS. REVISE AS REQUIRED.
 12-SPECIFY SIZE AND REINFORCEMENT FOR
 CONCRETE PAD NUMBER 4 FOR STEEL COLS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 13-SPECIFY FASTENERS FOR 2X4 BLOCKING AT
 ARCHED & OVAL FRAMING DETAIL. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 14-SPECIFY 7/8" MIN. STUCCO THICKNESS AT
 FRAMED AREAS AS REQUIRED BY ASTM C-926
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-11-30 Cont ID  
Sent By dpalmer Date 2004-11-30 Time 08:08 Rev Time 1.00
Received By dpalmer Date 2004-11-30 Time 08:08 Sent To  
Notes
2004-11-30 00:00:00REV FOR RISER AND PANEL SCHEDULES.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-02-17 Cont ID  
Sent By btrobaug Date 2004-02-17 Time 09:44 Rev Time 0.00
Received By btrobaug Date 2004-02-17 Time 07:03 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-04-28 Cont ID  
Sent By csiegber Date 2004-04-28 Time 11:49 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 11:49 Sent To B
Notes
2004-04-28 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-15 Cont ID  
Sent By mmclean Date 2004-01-29 Time 09:06 Rev Time 0.00
Received By jgomez Date 2004-01-27 Time 08:23 Sent To PC
Notes
2004-02-13 00:00:002/13/04 TO SFD RACK/E
2004-01-29 00:00:00TO JW DESK/MASTERED
2004-01-27 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-21 Cont ID  
Sent By btrobaug Date 2004-02-17 Time 09:44 Rev Time 0.50
Received By rregueir Date 2004-02-21 Time 08:56 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2004-02-28 Cont ID  
Sent By rregueir Date 2004-02-21 Time 08:56 Rev Time 0.50
Received By jleech Date 2004-02-28 Time 07:07 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-05-12 Cont ID  
Sent By mmclean Date 2004-05-12 Time 09:28 Rev Time 0.00
Received By mmclean Date 2004-05-12 Time 09:28 Sent To B
Notes
2004-05-12 00:00:00PASS CHANGED SURVEY. VOIDED SITEPLAN

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-29 Cont ID  
Sent By mmclean Date 2004-01-29 Time 09:06 Rev Time 0.00
Received By mmclean Date 2004-01-29 Time 09:06 Sent To I
Notes
***NONE***