Plan Review Details - Permit 04011062
Plan Review Stops For Permit 04011062
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-23 Cont ID  
Sent By shill Date 2004-03-22 Time 14:03 Rev Time 1.00
Received By shill Date 2004-03-22 Time 14:01 Sent To  
Notes
2004-03-23 00:00:00PASSED 3/23
2004-03-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE THE PREVIOUS LISTED, ITEM #1.
 THE LICENSE NUMBER OF THE PERSON
 SEALING THE PLAN IS TO BE PRINTED ON
 EACH SHEET FAC61G1-16.THE BUSINESS
 LICENSE NUMBER IS ON THE PLAN BUT THE
 LICENSE NUMBER FOR THE ARCHITECT IS NOT
 ON EACH SHEET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-02-24 Cont ID  
Sent By shill Date 2004-02-24 Time 14:31 Rev Time 3.00
Received By shill Date 2004-02-24 Time 14:25 Sent To  
Notes
2004-02-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE LICENSE NUMBER OF THE PERSON
 SEALING THE PLAN IS TO BE PRINTED ON
 EACH SHEET, FAC61G1-16.
  
 2.)FBC1012.1.4, DURING ITS SWING ANY
 DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED 1/2 THE REQUIRED WIDTH OF
 THE CORRIDOR, NOR PROJECT MORE THAN 7"
 WHEN FULLY OPEN (HC LAV. DOOR).

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-23 Cont ID  
Sent By btrobaug Date 2004-03-23 Time 10:06 Rev Time 0.00
Received By btrobaug Date 2004-03-23 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2004-01-26 Cont ID  
Sent By dpalmer Date 2004-01-26 Time 16:22 Rev Time 0.33
Received By dpalmer Date 2004-01-26 Time 16:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-03-23 Cont ID  
Sent By mcarsill Date 2004-03-23 Time 16:58 Rev Time 0.00
Received By mcarsill Date 2004-03-23 Time 16:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2004-01-29 Cont ID  
Sent By nmccray Date 2004-01-29 Time 12:03 Rev Time 0.00
Received By nmccray Date 2004-01-29 Time 12:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-12 Cont ID  
Sent By csiegber Date 2004-03-12 Time 11:56 Rev Time 0.00
Received By csiegber Date 2004-03-12 Time 11:56 Sent To  
Notes
2004-03-12 00:00:00TO COMM BD#42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-02-24 Cont ID  
Sent By shill Date 2004-02-24 Time 14:31 Rev Time 0.00
Received By shill Date 2004-01-22 Time 15:11 Sent To  
Notes
2004-01-22 00:00:00TO COMM BD#6

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-03-24 Cont ID  
Sent By pkrauss Date 2004-03-24 Time 11:13 Rev Time 0.40
Received By pkrauss Date 2004-03-24 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-02 Cont ID  
Sent By pkrauss Date 2004-02-02 Time 06:33 Rev Time 0.40
Received By pkrauss Date 2004-02-02 Time 06:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-03-23 Cont ID  
Sent By kstevens Date 2004-03-23 Time 15:22 Rev Time 0.33
Received By kstevens Date 2004-03-23 Time 15:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-01-31 Cont ID  
Sent By kstevens Date 2004-01-31 Time 12:32 Rev Time 1.00
Received By kstevens Date 2004-01-31 Time 12:32 Sent To  
Notes
2004-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 SINK IN COPY ROOM SHALL COM-
 PLY WITH SECTION 11-4.24 AND ALL SUBSEC-
 TIONS. SUBMIT DETAIL. DOOR SHALL NOT
 SWING INTO CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
 2) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN. IF AVAILABLE IN THE COMMON
 AREA, CALL OUT ON PLANS.
 3) COPY ROOM SINK SHALL NOT DRAIN INTO
 THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES. 909.1 - CONNECT SINK DOWN-
 STREAM OF BATHROOM FIXTURES ON FLOOR
 PLAN AND RISER DIAGRAM.
 4) SUBMIT MANUF SPEC SHEET FOR INSTA-
 HOT. SHALL BE LISTED BY APPROVED TESTING
 AGENCY.
 5) PLUMBING FIXTURE SCHEDULE, NO SINK IS
 SHOWN FOR COPY ROOM SINK.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]