Plan Review Details - Permit 04010916
Plan Review Stops For Permit 04010916
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-07-27 Cont ID  
Sent By rmcdouga Date 2004-07-27 Time 16:17 Rev Time 1.00
Received By rmcdouga Date 2004-07-27 Time 16:17 Sent To  
Notes
2004-07-27 00:00:00REVISION TO CHANGE WINDOW MANUFACTURER.
 SUBMITTED NEW PRODUCT APPROVAL. REVISION
 IS OK. RM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-04-19 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:51 Rev Time 2.00
Received By rmcdouga Date 2004-04-19 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-03-26 Cont ID  
Sent By dpalmer Date 2004-04-18 Time 07:19 Rev Time 1.50
Received By rmcdouga Date 2004-03-26 Time 15:18 Sent To  
Notes
2004-03-26 00:00:00DENIED
  
 1) OLD PLAN SHEETS DO NOT HAVE THE FIRM
 OR ARCHITECT'S LICENSE NUMBER AS
 REQUIRED BY FBC 61G1-16.004.
  
 NOTE: SUBMIT OLD PLAN SHEETS THAT HAVE
 BEEN STAMPED ALONG WITH NEW SHEETS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2004-03-08 Cont ID  
Sent By btrobaug Date 2004-03-24 Time 12:52 Rev Time 2.00
Received By rmcdouga Date 2004-03-08 Time 16:45 Sent To  
Notes
2004-03-08 00:00:00DENIED
  
 1) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. FBC TABLE 1604.1 REQUIRES
 ATTICS WITHOUT STORAGE TO HAVE A LIVE
 LOAD OF 10 PSF AND 30 PSF FOR ATTICS
 WITH STORAGE.
  
 2) REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL ON A4 TO STATE THAT THEY ARE
 FASTENED THROUGH THE BUCK AND NOT TO THE
 BUCK. SEE FBC 1707.4.4.2.
  
 3) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS INSULATED OR SOLID CORE AS REQUIRED
 BY FBC CHAPTER 13 SECTION 603.
  
 4) THE HEIGHTS LISTED FOR THE MASONRY
 OPENINGS OF WINDOWS 12 AND 13 ARE
 INCORRECT (SHOULD BE 64") ON A4.
  
 5) UPDATE THE SEMCO TRUSS CONNECTOR
 SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT
 ANCHOR WITH STATE OR LOCAL PRODUCT
 APPROVAL.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE 16'
 LONG MULLION BETWEEN THE SLIDING GLASS
 DOOR AND TRANSOM AT THE GREAT ROOM. THE
 ONE SUBMITTED ONLY LISTS UP 12' MULL
 LENGTHS.
  
 8) ITEM #10 IN THE SHUTTER SCHEDULE
 WHICH HAS A SHUTTER SPAN OF OVER 10' HAS
 THE INCORRECT FASTENER SPACING SPECIFIED
 SEE MIAMI-DADE PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-10-19 Cont ID  
Sent By dpalmer Date 2004-10-19 Time 13:16 Rev Time 0.25
Received By dpalmer Date 2004-10-19 Time 13:16 Sent To  
Notes
2004-10-19 00:00:00REVISED ELECTRICAL

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-04-18 Cont ID  
Sent By csiegber Date 2004-10-13 Time 14:35 Rev Time 0.25
Received By dpalmer Date 2004-04-18 Time 07:19 Sent To B
Notes
2004-04-18 00:00:00STAMPED NEW ELECTRICAL SHEET.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-03-24 Cont ID  
Sent By kstevens Date 2004-04-17 Time 11:18 Rev Time 0.50
Received By btrobaug Date 2004-03-24 Time 12:36 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2004-02-03 Cont ID  
Sent By dpalmer Date 2004-02-03 Time 08:34 Rev Time 0.50
Received By dpalmer Date 2004-02-03 Time 08:34 Sent To M
Notes
2004-02-03 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 AND SEALED BY THE ARCH OF RECORD. PLANS
 DO NOT CORRELATE WITH SIGNATURE ON
 RECORD FOR ARCH.
 PLEASE NOTE, ONE SET OF PLANS IS BEING
 RETAINED FOR FILE FOR SAID VIOLATION.
 PER FS 481.221
  
 2)NOTE: PLANS ARE REQUIRED TO HAVE ALL
 LICENSE #'S ON TITLE BLOCK FOR ARCH/
 ARCH FIRM. INCLUDING NAME OF ARCH.
 FAC 61G1-16.004
  
 3)NOTE: PLEASE SEE REQUIRMENT SHOWN FOR
 ARC FAULT PROTECTION. SHOWS WHAT WAS
 REQ'D UNDER THE 99 NEC. WE ARE NOW UNDER
 THE 2002 CODE. PLEASE ADJUST
  
 4)NOTE; PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEM MAIN DISC
 AND PANEL. PER250.110,250.24 AND SIZE
 PER 250.122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-10-13 Cont ID  
Sent By csiegber Date 2004-10-13 Time 14:35 Rev Time 0.00
Received By csiegber Date 2004-10-13 Time 14:35 Sent To E
Notes
2004-10-13 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:51 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 16:51 Sent To B
Notes
2004-07-26 00:00:00TO RM DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-14 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:51 Rev Time 0.00
Received By csiegber Date 2004-04-14 Time 10:51 Sent To P
Notes
2004-04-14 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-03-16 Cont ID  
Sent By csiegber Date 2004-03-16 Time 16:23 Rev Time 0.00
Received By csiegber Date 2004-03-16 Time 16:23 Sent To P
Notes
2004-03-16 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-03-08 Cont ID  
Sent By mmclean Date 2004-01-22 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2004-01-21 Time 10:00 Sent To  
Notes
2004-01-23 00:00:00TO SFD RACK/E
2004-01-21 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2004-02-21 Cont ID  
Sent By kstevens Date 2004-03-20 Time 13:39 Rev Time 0.50
Received By rregueir Date 2004-02-21 Time 08:46 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-04-17 Cont ID  
Sent By kstevens Date 2004-04-17 Time 11:18 Rev Time 0.50
Received By kstevens Date 2004-04-17 Time 11:18 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-03-20 Cont ID  
Sent By csiegber Date 2004-04-14 Time 10:51 Rev Time 0.50
Received By kstevens Date 2004-03-20 Time 13:36 Sent To M
Notes
2004-03-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-1 SANITARY RISER DIAGRAM, A
 TRAP IS REQUIRED FOR THE SHOWER IN BATH
 NUMBER 3. SEE RED LINE CORRECTION.
 SECTION 104,2,1
 2) SIGNATURES ARE DIFFERENT ON DIFFERENT
 SHEETS. SHEET WITH OUT AUTHORIZED SIGNA-
 TURES HAVE BEEN VOIDED. SUBMIT NEW
 SHEETS FOR VOIDED SHEETS. FAC 61GQ-16.
 003
 3) NEW PLANS SUBMITTED ARE NOT COMPLETE.
 MANY SHEETS MISSING. SUBMIT TWO COMPLETE
 SETS OF PLANS FOR REVIEW. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-03-16 Time 16:23 Rev Time 0.50
Received By jleech Date 2004-02-09 Time 14:54 Sent To M
Notes
2004-02-09 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW NOTES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2004-01-22 Cont ID  
Sent By mmclean Date 2004-01-22 Time 16:14 Rev Time 0.00
Received By mmclean Date 2004-01-22 Time 16:14 Sent To I
Notes
***NONE***